14 vulnerabilities found for OPC UA Modicon Communication Module by Schneider Electric

CVE-2022-34765 (GCVE-0-2022-34765)

Vulnerability from nvd – Published: 2022-07-13 21:11 – Updated: 2024-09-16 19:40
VLAI?
Summary
A CWE-73: External Control of File Name or Path vulnerability exists that could cause loading of unauthorized firmware images when user-controlled data is written to the file path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-73 - External Control of File Name or Path
Assigner
References
Impacted products
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.856Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "BMENOR2200H*",
              "status": "affected",
              "version": "V2.01",
              "versionType": "custom"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-73: External Control of File Name or Path vulnerability exists that could cause loading of unauthorized firmware images when user-controlled data is written to the file path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "LOW",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-73",
              "description": "CWE-73 External Control of File Name or Path",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:11:13.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34765",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003e",
                            "version_name": "BMENOR2200H",
                            "version_value": "V2.01"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-73: External Control of File Name or Path vulnerability exists that could cause loading of unauthorized firmware images when user-controlled data is written to the file path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "LOW",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-73 External Control of File Name or Path"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34765",
    "datePublished": "2022-07-13T21:11:13.251Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T19:40:21.506Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34764 (GCVE-0-2022-34764)

Vulnerability from nvd – Published: 2022-07-13 21:11 – Updated: 2024-09-16 18:29
VLAI?
Summary
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause denial of service when parsing the URL. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-119 - Improper Restriction of Operations within the Bounds of a Memory Buffer
Assigner
References
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.270Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "status": "affected",
              "version": "BMENOR2200H V1.0"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause denial of service when parsing the URL. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-119",
              "description": "CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:11:05.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34764",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "=",
                            "version_name": "BMENOR2200H",
                            "version_value": "V1.0"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause denial of service when parsing the URL. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34764",
    "datePublished": "2022-07-13T21:11:05.954Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T18:29:14.835Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34763 (GCVE-0-2022-34763)

Vulnerability from nvd – Published: 2022-07-13 21:11 – Updated: 2024-09-16 18:59
VLAI?
Summary
A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists that could cause loading of unauthorized firmware images due to improper verification of the firmware signature. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-345 - Insufficient Verification of Data Authenticity
Assigner
References
Impacted products
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:10.447Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "BMENOR2200H*",
              "status": "affected",
              "version": "V2.01",
              "versionType": "custom"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists that could cause loading of unauthorized firmware images due to improper verification of the firmware signature. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-345",
              "description": "CWE-345 Insufficient Verification of Data Authenticity",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:11:02.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34763",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003e",
                            "version_name": "BMENOR2200H",
                            "version_value": "V2.01"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists that could cause loading of unauthorized firmware images due to improper verification of the firmware signature. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-345 Insufficient Verification of Data Authenticity"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34763",
    "datePublished": "2022-07-13T21:11:02.182Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T18:59:40.882Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34762 (GCVE-0-2022-34762)

Vulnerability from nvd – Published: 2022-07-13 21:10 – Updated: 2024-09-16 16:22
VLAI?
Summary
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause unauthorized firmware image loading when unsigned images are added to the firmware image path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-22 - Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')
Assigner
References
Impacted products
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:10.298Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "BMENOR2200H*",
              "status": "affected",
              "version": "V2.01",
              "versionType": "custom"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-22: Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027) vulnerability exists that could cause unauthorized firmware image loading when unsigned images are added to the firmware image path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-22",
              "description": "CWE-22 Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:10:56.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34762",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003e",
                            "version_name": "BMENOR2200H",
                            "version_value": "V2.01"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-22: Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027) vulnerability exists that could cause unauthorized firmware image loading when unsigned images are added to the firmware image path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-22 Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34762",
    "datePublished": "2022-07-13T21:10:56.827Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T16:22:52.936Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34761 (GCVE-0-2022-34761)

Vulnerability from nvd – Published: 2022-07-13 21:10 – Updated: 2024-09-16 16:52
VLAI?
Summary
A CWE-476: NULL Pointer Dereference vulnerability exists that could cause a denial of service of the webserver when parsing JSON content type. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-476 - NULL Pointer Dereference
Assigner
References
Impacted products
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.282Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "BMENOR2200H*",
              "status": "affected",
              "version": "V2.01",
              "versionType": "custom"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-476: NULL Pointer Dereference vulnerability exists that could cause a denial of service of the webserver when parsing JSON content type. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-476",
              "description": "CWE-476 NULL Pointer Dereference",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:10:52.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34761",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003e",
                            "version_name": "BMENOR2200H",
                            "version_value": "V2.01"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-476: NULL Pointer Dereference vulnerability exists that could cause a denial of service of the webserver when parsing JSON content type. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-476 NULL Pointer Dereference"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34761",
    "datePublished": "2022-07-13T21:10:52.734Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T16:52:55.761Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34760 (GCVE-0-2022-34760)

Vulnerability from nvd – Published: 2022-07-13 21:10 – Updated: 2024-09-17 01:30
VLAI?
Summary
A CWE-835: Loop with Unreachable Exit Condition ('Infinite Loop') vulnerability exists that could cause a denial of service of the webserver due to improper handling of the cookies. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-835 - Loop with Unreachable Exit Condition ('Infinite Loop')
Assigner
References
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.307Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "status": "affected",
              "version": "BMENOR2200H V1.0"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-835: Loop with Unreachable Exit Condition (\u0027Infinite Loop\u0027) vulnerability exists that could cause a denial of service of the webserver due to improper handling of the cookies. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-835",
              "description": "CWE-835: Loop with Unreachable Exit Condition (\u0027Infinite Loop\u0027)",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:10:49.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34760",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "=",
                            "version_name": "BMENOR2200H",
                            "version_value": "V1.0"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-835: Loop with Unreachable Exit Condition (\u0027Infinite Loop\u0027) vulnerability exists that could cause a denial of service of the webserver due to improper handling of the cookies. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-835: Loop with Unreachable Exit Condition (\u0027Infinite Loop\u0027)"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34760",
    "datePublished": "2022-07-13T21:10:49.692Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-17T01:30:30.169Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34759 (GCVE-0-2022-34759)

Vulnerability from nvd – Published: 2022-07-13 21:10 – Updated: 2024-09-16 22:29
VLAI?
Summary
A CWE-787: Out-of-bounds Write vulnerability exists that could cause a denial of service of the webserver due to improper parsing of the HTTP Headers. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
Assigner
References
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.229Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "status": "affected",
              "version": "BMENOR2200H V1.0"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-787: Out-of-bounds Write vulnerability exists that could cause a denial of service of the webserver due to improper parsing of the HTTP Headers. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-787",
              "description": "CWE-787 Out-of-bounds Write",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:10:46.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34759",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "=",
                            "version_name": "BMENOR2200H",
                            "version_value": "V1.0"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-787: Out-of-bounds Write vulnerability exists that could cause a denial of service of the webserver due to improper parsing of the HTTP Headers. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-787 Out-of-bounds Write"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34759",
    "datePublished": "2022-07-13T21:10:46.820Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T22:29:47.753Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34765 (GCVE-0-2022-34765)

Vulnerability from cvelistv5 – Published: 2022-07-13 21:11 – Updated: 2024-09-16 19:40
VLAI?
Summary
A CWE-73: External Control of File Name or Path vulnerability exists that could cause loading of unauthorized firmware images when user-controlled data is written to the file path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-73 - External Control of File Name or Path
Assigner
References
Impacted products
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.856Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "BMENOR2200H*",
              "status": "affected",
              "version": "V2.01",
              "versionType": "custom"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-73: External Control of File Name or Path vulnerability exists that could cause loading of unauthorized firmware images when user-controlled data is written to the file path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "LOW",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-73",
              "description": "CWE-73 External Control of File Name or Path",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:11:13.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34765",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003e",
                            "version_name": "BMENOR2200H",
                            "version_value": "V2.01"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-73: External Control of File Name or Path vulnerability exists that could cause loading of unauthorized firmware images when user-controlled data is written to the file path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "LOW",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-73 External Control of File Name or Path"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34765",
    "datePublished": "2022-07-13T21:11:13.251Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T19:40:21.506Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34764 (GCVE-0-2022-34764)

Vulnerability from cvelistv5 – Published: 2022-07-13 21:11 – Updated: 2024-09-16 18:29
VLAI?
Summary
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause denial of service when parsing the URL. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-119 - Improper Restriction of Operations within the Bounds of a Memory Buffer
Assigner
References
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.270Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "status": "affected",
              "version": "BMENOR2200H V1.0"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause denial of service when parsing the URL. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-119",
              "description": "CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:11:05.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34764",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "=",
                            "version_name": "BMENOR2200H",
                            "version_value": "V1.0"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause denial of service when parsing the URL. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34764",
    "datePublished": "2022-07-13T21:11:05.954Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T18:29:14.835Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34763 (GCVE-0-2022-34763)

Vulnerability from cvelistv5 – Published: 2022-07-13 21:11 – Updated: 2024-09-16 18:59
VLAI?
Summary
A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists that could cause loading of unauthorized firmware images due to improper verification of the firmware signature. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-345 - Insufficient Verification of Data Authenticity
Assigner
References
Impacted products
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:10.447Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "BMENOR2200H*",
              "status": "affected",
              "version": "V2.01",
              "versionType": "custom"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists that could cause loading of unauthorized firmware images due to improper verification of the firmware signature. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-345",
              "description": "CWE-345 Insufficient Verification of Data Authenticity",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:11:02.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34763",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003e",
                            "version_name": "BMENOR2200H",
                            "version_value": "V2.01"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists that could cause loading of unauthorized firmware images due to improper verification of the firmware signature. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-345 Insufficient Verification of Data Authenticity"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34763",
    "datePublished": "2022-07-13T21:11:02.182Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T18:59:40.882Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34762 (GCVE-0-2022-34762)

Vulnerability from cvelistv5 – Published: 2022-07-13 21:10 – Updated: 2024-09-16 16:22
VLAI?
Summary
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause unauthorized firmware image loading when unsigned images are added to the firmware image path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-22 - Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')
Assigner
References
Impacted products
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:10.298Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "BMENOR2200H*",
              "status": "affected",
              "version": "V2.01",
              "versionType": "custom"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-22: Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027) vulnerability exists that could cause unauthorized firmware image loading when unsigned images are added to the firmware image path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-22",
              "description": "CWE-22 Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:10:56.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34762",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003e",
                            "version_name": "BMENOR2200H",
                            "version_value": "V2.01"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-22: Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027) vulnerability exists that could cause unauthorized firmware image loading when unsigned images are added to the firmware image path. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-22 Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34762",
    "datePublished": "2022-07-13T21:10:56.827Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T16:22:52.936Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34761 (GCVE-0-2022-34761)

Vulnerability from cvelistv5 – Published: 2022-07-13 21:10 – Updated: 2024-09-16 16:52
VLAI?
Summary
A CWE-476: NULL Pointer Dereference vulnerability exists that could cause a denial of service of the webserver when parsing JSON content type. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-476 - NULL Pointer Dereference
Assigner
References
Impacted products
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.282Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "BMENOR2200H*",
              "status": "affected",
              "version": "V2.01",
              "versionType": "custom"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-476: NULL Pointer Dereference vulnerability exists that could cause a denial of service of the webserver when parsing JSON content type. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-476",
              "description": "CWE-476 NULL Pointer Dereference",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:10:52.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34761",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003e",
                            "version_name": "BMENOR2200H",
                            "version_value": "V2.01"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-476: NULL Pointer Dereference vulnerability exists that could cause a denial of service of the webserver when parsing JSON content type. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V2.01 and later), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-476 NULL Pointer Dereference"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34761",
    "datePublished": "2022-07-13T21:10:52.734Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T16:52:55.761Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34760 (GCVE-0-2022-34760)

Vulnerability from cvelistv5 – Published: 2022-07-13 21:10 – Updated: 2024-09-17 01:30
VLAI?
Summary
A CWE-835: Loop with Unreachable Exit Condition ('Infinite Loop') vulnerability exists that could cause a denial of service of the webserver due to improper handling of the cookies. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
  • CWE-835 - Loop with Unreachable Exit Condition ('Infinite Loop')
Assigner
References
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.307Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "status": "affected",
              "version": "BMENOR2200H V1.0"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-835: Loop with Unreachable Exit Condition (\u0027Infinite Loop\u0027) vulnerability exists that could cause a denial of service of the webserver due to improper handling of the cookies. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-835",
              "description": "CWE-835: Loop with Unreachable Exit Condition (\u0027Infinite Loop\u0027)",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:10:49.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34760",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "=",
                            "version_name": "BMENOR2200H",
                            "version_value": "V1.0"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-835: Loop with Unreachable Exit Condition (\u0027Infinite Loop\u0027) vulnerability exists that could cause a denial of service of the webserver due to improper handling of the cookies. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-835: Loop with Unreachable Exit Condition (\u0027Infinite Loop\u0027)"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34760",
    "datePublished": "2022-07-13T21:10:49.692Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-17T01:30:30.169Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2022-34759 (GCVE-0-2022-34759)

Vulnerability from cvelistv5 – Published: 2022-07-13 21:10 – Updated: 2024-09-16 22:29
VLAI?
Summary
A CWE-787: Out-of-bounds Write vulnerability exists that could cause a denial of service of the webserver due to improper parsing of the HTTP Headers. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)
CWE
Assigner
References
Date Public ?
2022-07-12 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T09:22:09.229Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "OPC UA Modicon Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "lessThan": "V1.10",
              "status": "affected",
              "version": "BMENUA0100",
              "versionType": "custom"
            }
          ]
        },
        {
          "product": "X80 advanced RTU Communication Module",
          "vendor": "Schneider Electric",
          "versions": [
            {
              "status": "affected",
              "version": "BMENOR2200H V1.0"
            }
          ]
        }
      ],
      "datePublic": "2022-07-12T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-787: Out-of-bounds Write vulnerability exists that could cause a denial of service of the webserver due to improper parsing of the HTTP Headers. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-787",
              "description": "CWE-787 Out-of-bounds Write",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2022-07-13T21:10:46.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "DATE_PUBLIC": "2022-07-12T11:00:00.000Z",
          "ID": "CVE-2022-34759",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "OPC UA Modicon Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "\u003c",
                            "version_name": "BMENUA0100",
                            "version_value": "V1.10"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "X80 advanced RTU Communication Module",
                      "version": {
                        "version_data": [
                          {
                            "version_affected": "=",
                            "version_name": "BMENOR2200H",
                            "version_value": "V1.0"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-787: Out-of-bounds Write vulnerability exists that could cause a denial of service of the webserver due to improper parsing of the HTTP Headers. Affected Products: X80 advanced RTU Communication Module (BMENOR2200H) (V1.0), OPC UA Modicon Communication Module (BMENUA0100) (V1.10 and prior)"
            }
          ]
        },
        "generator": {
          "engine": "Vulnogram 0.0.9"
        },
        "impact": {
          "cvss": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          }
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "CWE-787 Out-of-bounds Write"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf",
              "refsource": "MISC",
              "url": "https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf"
            }
          ]
        },
        "source": {
          "discovery": "UNKNOWN"
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2022-34759",
    "datePublished": "2022-07-13T21:10:46.820Z",
    "dateReserved": "2022-06-28T00:00:00.000Z",
    "dateUpdated": "2024-09-16T22:29:47.753Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",