CVE-2025-27257 (GCVE-0-2025-27257)

Vulnerability from cvelistv5 – Published: 2025-03-10 09:05 – Updated: 2025-03-12 11:10
VLAI
Summary
Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware. The firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed.
SSVC
Exploitation: none Automatable: no Technical Impact: partial
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2025-03-10 13:23 UTC
CWE
  • CWE-345 - Insufficient Verification of Data Authenticity
Assigner
Nozomi CNA under the mitre root
CNA scorecard B 80/100 over 55 records in the last 180 days details
Impacted products
Vendor Product Version CPE status
GE Vernova N60 multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova B30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova B90 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova C30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova C60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova C70 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova C95 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova D30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova D60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova F35 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova F60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova G30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova G60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova L30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova L60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova L90 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova M60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova T35 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova T60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-27257",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-03-10T13:23:04.580273Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-03-10T13:23:20.325Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "N60 multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "B30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "B90 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "C30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "C60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "C70 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "C95 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "D30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "D60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "F35 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "F60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "G30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "G60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "L30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "L60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "L90 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "M60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "T35 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "T60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "M60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware.\u003cbr\u003eThe firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, a\u003cspan style=\"background-color: var(--wht);\"\u003ellowing the integration check to be bypassed.\u003c/span\u003e\u003cbr\u003e\u003cbr\u003e"
            }
          ],
          "value": "Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware.\nThe firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed."
        }
      ],
      "impacts": [
        {
          "capecId": "CAPEC-638",
          "descriptions": [
            {
              "lang": "en",
              "value": "CAPEC-638 Altered Component Firmware"
            }
          ]
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "ADJACENT_NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 6.1,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-345",
              "description": "CWE-345 Insufficient Verification of Data Authenticity",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-03-12T11:10:57.902Z",
        "orgId": "bec8025f-a851-46e5-b3a3-058e6b0aa23c",
        "shortName": "Nozomi"
      },
      "references": [
        {
          "url": "https://www.gevernova.com/grid-solutions/app/DownloadFile.aspx?prod=urfamily\u0026type=21\u0026file=76"
        },
        {
          "url": "https://www.nozominetworks.com/labs/vulnerability-advisories-cve-2025-27257"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "bec8025f-a851-46e5-b3a3-058e6b0aa23c",
    "assignerShortName": "Nozomi",
    "cveId": "CVE-2025-27257",
    "datePublished": "2025-03-10T09:05:34.817Z",
    "dateReserved": "2025-02-21T08:32:26.974Z",
    "dateUpdated": "2025-03-12T11:10:57.902Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1",
  "vulnerability-lookup:meta": {
    "epss": {
      "cve": "CVE-2025-27257",
      "date": "2026-11-16",
      "epss": "0.00181",
      "percentile": "0.07781"
    },
    "nvd": {
      "cve": {
        "affected": [
          {
            "affectedData": [
              {
                "defaultStatus": "unaffected",
                "product": "N60 multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "B30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "B90 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "C30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "C60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "C70 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "C95 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "D30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "D60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "F35 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "F60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "G30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "G60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "L30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "L60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "L90 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "M60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "T35 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "T60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "M60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              }
            ],
            "source": "prodsec@nozominetworks.com"
          }
        ],
        "cveTags": [],
        "descriptions": [
          {
            "lang": "en",
            "value": "Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware.\nThe firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed."
          },
          {
            "lang": "es",
            "value": "La vulnerabilidad de verificaci\u00f3n insuficiente de la autenticidad de los datos en los dispositivos de la familia GE Vernova UR IED permite que un usuario autenticado instale un firmware modificado. La verificaci\u00f3n de la firma del firmware se aplica \u00fanicamente en el software dedicado del lado del cliente Enervista UR Setup, lo que permite omitir la comprobaci\u00f3n de integraci\u00f3n."
          }
        ],
        "id": "CVE-2025-27257",
        "lastModified": "2026-06-17T09:03:17.423",
        "metrics": {
          "cvssMetricV31": [
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "ADJACENT_NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 6.1,
                "baseSeverity": "MEDIUM",
                "confidentialityImpact": "NONE",
                "integrityImpact": "HIGH",
                "privilegesRequired": "HIGH",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H",
                "version": "3.1"
              },
              "exploitabilityScore": 0.9,
              "impactScore": 5.2,
              "source": "prodsec@nozominetworks.com",
              "type": "Secondary"
            }
          ],
          "ssvcV203": [
            {
              "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "ssvcData": {
                "id": "CVE-2025-27257",
                "options": [
                  {
                    "exploitation": "none"
                  },
                  {
                    "automatable": "no"
                  },
                  {
                    "technicalImpact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-03-10T13:23:04.580273Z",
                "version": "2.0.3"
              }
            }
          ]
        },
        "published": "2025-03-10T09:15:11.613",
        "references": [
          {
            "source": "prodsec@nozominetworks.com",
            "url": "https://www.gevernova.com/grid-solutions/app/DownloadFile.aspx?prod=urfamily\u0026type=21\u0026file=76"
          },
          {
            "source": "prodsec@nozominetworks.com",
            "url": "https://www.nozominetworks.com/labs/vulnerability-advisories-cve-2025-27257"
          }
        ],
        "sourceIdentifier": "prodsec@nozominetworks.com",
        "vulnStatus": "Deferred",
        "weaknesses": [
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-345"
              }
            ],
            "source": "prodsec@nozominetworks.com",
            "type": "Secondary"
          }
        ]
      }
    },
    "redhat_vex": {
      "current_release_date": "2025-05-28T17:32:06+00:00",
      "cve": "CVE-2025-27257",
      "id": "CVE-2025-27257",
      "initial_release_date": "2025-01-01T00:00:00+00:00",
      "product_status:known_not_affected": "1",
      "source": "Red Hat CSAF VEX",
      "status": "final",
      "title": "CVE-2025-27257",
      "url": "https://security.access.redhat.com/data/csaf/v2/vex/2025/cve-2025-27257.json",
      "version": "3"
    },
    "vulnrichment": {
      "containers": {
        "adp": [
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2025-27257",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2025-03-10T13:23:04.580273Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2025-03-10T13:23:13.911Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "N60 multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "B30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "B90 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "C30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "C60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "C70 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "C95 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "D30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "D60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "F35 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "F60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "G30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "G60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "L30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "L60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "L90 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "M60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "T35 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "T60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "M60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware.\u003cbr\u003eThe firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, a\u003cspan style=\"background-color: var(--wht);\"\u003ellowing the integration check to be bypassed.\u003c/span\u003e\u003cbr\u003e\u003cbr\u003e"
                }
              ],
              "value": "Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware.\nThe firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-638",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-638 Altered Component Firmware"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "ADJACENT_NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 6.1,
                "baseSeverity": "MEDIUM",
                "confidentialityImpact": "NONE",
                "integrityImpact": "HIGH",
                "privilegesRequired": "HIGH",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-345",
                  "description": "CWE-345 Insufficient Verification of Data Authenticity",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2025-03-12T11:10:57.902Z",
            "orgId": "bec8025f-a851-46e5-b3a3-058e6b0aa23c",
            "shortName": "Nozomi"
          },
          "references": [
            {
              "url": "https://www.gevernova.com/grid-solutions/app/DownloadFile.aspx?prod=urfamily\u0026type=21\u0026file=76"
            },
            {
              "url": "https://www.nozominetworks.com/labs/vulnerability-advisories-cve-2025-27257"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "bec8025f-a851-46e5-b3a3-058e6b0aa23c",
        "assignerShortName": "Nozomi",
        "cveId": "CVE-2025-27257",
        "datePublished": "2025-03-10T09:05:34.817Z",
        "dateReserved": "2025-02-21T08:32:26.974Z",
        "dateUpdated": "2025-03-12T11:10:57.902Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }
  }
}



Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Drag nodes to arrange them. Double-click a related vulnerability to open it, or a source to visit its link. The Physics button on the left tunes the layout and the simulation; the legend at the bottom left hides or shows nodes by kind and by sighting type.

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Vulnerability timeline

Sightings and recorded dates, grouped by day · UTC

JSON
How durations are calculated

Following the VTEM framework (Black Hat USA 2015), time to patch starts when the vendor or a coordinator was informed, total time to patch at discovery, and disclosure to patch at public disclosure; vendor response time runs from the report to its acknowledgement. Time to exploit and time unpatched start at the earliest discovery or report, falling back to public disclosure. Unpatched time ends at the first recorded patch, or the calculation time when no patch is recorded. Exploitation to patch shows the interval between those two events; a published proof of concept is a public exploit, not exploitation.

Each result shows its source dates. A negative interval means the end event came first; when date-only inputs leave the order open, the result says so. Date-only inputs are approximate. The earliest evidence wins: KEV report dates and sightings are labelled as such. Records describing another vulnerability are listed but never calculated from, and a PoC alone does not establish exploitation. Missing patch evidence does not prove that no patch exists. Filters below change the event list only.

Events included in the timeline

Loading timeline…


    Loading…

    Loading…

    Loading…

    Related by attack behaviour

    Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.