ADVISORY2026-13_VDE-2026-145

Vulnerability from csaf_codesysgmbh - Published: 2026-11-17 10:00 - Updated: 2026-11-17 10:00
Summary
CODESYS Automation Server Connector and CODESYS Service Tool - multiple vulnerabilities
Severity
High
Notes
Summary: The CODESYS Automation Server Connector is an Add-on for the CODESYS Development System that enables project synchronization with the CODESYS Automation Server and the configuration of CODESYS Edge Gateways. The CODESYS Service Tool is a stand-alone application for configuring CODESYS Edge Gateways. Multiple vulnerabilities in the affected products could allow an unauthenticated remote attacker to manipulate trusted CODESYS Automation Server interactions. Successful exploitation may result in the interception and manipulation of Automation Server communications or arbitrary code execution with the privileges of the user running the affected product.
Impact: Successful exploitation of these vulnerabilities may allow an unauthenticated remote attacker to intercept and manipulate Automation Server communications with the PLC network, or execute arbitrary code on the host running the affected products, resulting in a loss of confidentiality, integrity, and availability.
Remediation: Update the following products to version 1.40.0.0. * CODESYS Automation Server Connector * CODESYS Service Tool The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
General Recommendation: As part of a security strategy, CODESYS GmbH strongly recommends at least the following best-practice defense measures: * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside * Use firewalls to protect and separate the control system network from other networks * Activate and apply user management and password features * Limit the access to both development and control system by physical means, operating system features, etc. * Use encrypted communication links * Use VPN (Virtual Private Networks) tunnels if remote access is required * Protect both development and control system by using up to date virus detecting solutions For more information and general recommendations for protecting machines and plants, see also the CODESYS Security Whitepaper [here.](https://www.customers.codesys.com/fileadmin/data/customers/security/CODESYS-Security-Whitepaper.pdf)
Disclaimer: CODESYS GmbH assumes no liability whatsoever for indirect, collateral, accidental or consequential losses that occur by the distribution and/or use of this document or any losses in connection with the distribution and/or use of this document. All information published in this document is provided on good faith by CODESYS GmbH. Insofar as permissible by law, however, none of this information shall establish any guarantee, commitment or liability on the part of CODESYS GmbH. Note: Not all CODESYS features are available in all territories. For more information on geographic restrictions, please contact sales@codesys.com.

The affected products process a server-supplied URL without sufficient validation. An unauthenticated remote attacker controlling a malicious Automation Server and tricking a user to trust it or performing a man-in-the-middle attack, can exploit this vulnerability by causing the affected product to process unintended content. Successful exploitation may result in arbitrary code execution with the privileges of the user running the affected product.

CWE-706 - Use of Incorrectly-Resolved Name or Reference
Vendor Fix Update the following products to version 1.40.0.0. * CODESYS Automation Server Connector * CODESYS Service Tool The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
Affected products
Product Identifier Version Remediation
CODESYS Automation Server Connector 1.40.0.0
CODESYS / Software / CODESYS Automation Server Connector
cpe:2.3:a:codesys:codesys_automation_server_connector:1.40.0.0:*:*:*:*:*:*:* 1.40.0.0
CODESYS Service Tool 1.40.0.0
CODESYS / Software / CODESYS Service Tool
cpe:2.3:a:codesys:codesys_service_tool:1.40.0.0:*:*:*:*:*:*:* 1.40.0.0
Product Identifier Version Remediation
CODESYS Automation Server Connector 1.0.0.0<1.40.0.0
CODESYS / Software / CODESYS Automation Server Connector
cpe:2.3:a:codesys:codesys_automation_server_connector:*:*:*:*:*:*:*:* vers:generic/>=1.0.0.0|<1.40.0.0
CODESYS Service Tool 1.0.0.0<1.40.0.0
CODESYS / Software / CODESYS Service Tool
cpe:2.3:a:codesys:codesys_service_tool:*:*:*:*:*:*:*:* vers:generic/>=1.0.0.0|<1.40.0.0

The affected products do not sufficiently validate CODESYS Automation Server TLS certificates when a user starts the certificate enrollment. An unauthenticated remote attacker performing a man-in-the-middle attack can exploit this vulnerability by supplying an untrusted certificate that is accepted as trusted. Successful exploitation may allow an attacker to intercept and manipulate communications between the CODESYS Automation Server and the PLC network.

CWE-295 - Improper Certificate Validation
Vendor Fix Update the following products to version 1.40.0.0. * CODESYS Automation Server Connector * CODESYS Service Tool The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
Affected products
Fixed 2 products, the same list as for CVE-2026-118496
Known affected 2 products, the same list as for CVE-2026-118496

{
  "document": {
    "acknowledgments": [
      {
        "organization": "CERT@VDE",
        "summary": "coordination",
        "urls": [
          "https://www.certvde.com"
        ]
      },
      {
        "names": [
          "f0rw4rd aka Felix Eberstaller"
        ],
        "organization": "Limes Security / QuellSec",
        "summary": "reporting"
      }
    ],
    "aggregate_severity": {
      "namespace": "https://www.first.org/cvss/v3.1/specification-document#Qualitative-Severity-Rating-Scale",
      "text": "High"
    },
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "tlp": {
        "label": "WHITE",
        "url": "https://www.first.org/tlp/"
      }
    },
    "lang": "en-GB",
    "notes": [
      {
        "category": "summary",
        "text": "The CODESYS Automation Server Connector is an Add-on for the CODESYS Development System that enables project synchronization with the CODESYS Automation Server and the configuration of CODESYS Edge Gateways. The CODESYS Service Tool is a stand-alone application for configuring CODESYS Edge Gateways.\n\nMultiple vulnerabilities in the affected products could allow an unauthenticated remote attacker to manipulate trusted CODESYS Automation Server interactions. Successful exploitation may result in the interception and manipulation of Automation Server communications or arbitrary code execution with the privileges of the user running the affected product.",
        "title": "Summary"
      },
      {
        "category": "description",
        "text": "Successful exploitation of these vulnerabilities may allow an unauthenticated remote attacker to intercept and manipulate Automation Server communications with the PLC network, or execute arbitrary code on the host running the affected products, resulting in a loss of confidentiality, integrity, and availability.",
        "title": "Impact"
      },
      {
        "category": "description",
        "text": "Update the following products to version 1.40.0.0.\n* CODESYS Automation Server Connector\n* CODESYS Service Tool\n\nThe CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.",
        "title": "Remediation"
      },
      {
        "category": "general",
        "text": "As part of a security strategy, CODESYS GmbH strongly recommends at least the following best-practice\ndefense measures:\n\n* Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside\n* Use firewalls to protect and separate the control system network from other networks\n* Activate and apply user management and password features\n* Limit the access to both development and control system by physical means, operating system features, etc.\n* Use encrypted communication links\n* Use VPN (Virtual Private Networks) tunnels if remote access is required\n* Protect both development and control system by using up to date virus detecting solutions\n\nFor more information and general recommendations for protecting machines and plants, see also the\nCODESYS Security Whitepaper [here.](https://www.customers.codesys.com/fileadmin/data/customers/security/CODESYS-Security-Whitepaper.pdf)",
        "title": "General Recommendation"
      },
      {
        "category": "legal_disclaimer",
        "text": "CODESYS GmbH assumes no liability whatsoever for indirect, collateral, accidental or consequential losses\nthat occur by the distribution and/or use of this document or any losses in connection with the distribution and/or use of this document. All information published in this document is provided on good faith by CODESYS GmbH.\nInsofar as permissible by law, however, none of this information shall establish any guarantee, commitment or\nliability on the part of CODESYS GmbH.\n\nNote: Not all CODESYS features are available in all territories. For more information on geographic restrictions,\nplease contact sales@codesys.com.",
        "title": "Disclaimer"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "security@codesys.com",
      "name": "CODESYS GmbH",
      "namespace": "https://www.codesys.com"
    },
    "references": [
      {
        "category": "external",
        "summary": "CERT@VDE Security Advisories for CODESYS GmbH",
        "url": "https://www.certvde.com/en/advisories/vendor/codesys"
      },
      {
        "category": "self",
        "summary": "Advisory2026-13_VDE-2026-145: CODESYS Automation Server Connector and CODESYS Service Tool - multiple vulnerabilities - HTML",
        "url": "https://www.certvde.com/en/advisories/VDE-2026-145/"
      },
      {
        "category": "self",
        "summary": "Advisory2026-13_VDE-2026-145: CODESYS Automation Server Connector and CODESYS Service Tool - multiple vulnerabilities - CSAF",
        "url": "https://codesys.csaf-tp.certvde.com/.well-known/csaf/white/2026/advisory2026-13_vde-2026-145.json"
      },
      {
        "category": "external",
        "summary": "CODESYS Security Advisories",
        "url": "https://www.codesys.com/security/security-reports.html"
      },
      {
        "category": "self",
        "summary": "Advisory2026-13_VDE-2026-145: CODESYS Automation Server Connector and CODESYS Service Tool - multiple vulnerabilities - PDF",
        "url": "https://api-www.codesys.com/fileadmin/user_upload/CODESYS_Group/Ecosystem/Up-to-Date/Security/Security-Advisories/Advisory2026-13_CAS-5434.pdf"
      }
    ],
    "title": "CODESYS Automation Server Connector and CODESYS Service Tool - multiple vulnerabilities",
    "tracking": {
      "aliases": [
        "VDE-2026-145",
        "CODESYS Security Advisory 2026-13"
      ],
      "current_release_date": "2026-11-17T10:00:00.000Z",
      "generator": {
        "date": "2026-11-12T18:28:58.336Z",
        "engine": {
          "name": "Secvisogram",
          "version": "2.6.16"
        }
      },
      "id": "Advisory2026-13_VDE-2026-145",
      "initial_release_date": "2026-11-17T10:00:00.000Z",
      "revision_history": [
        {
          "date": "2026-11-17T10:00:00.000Z",
          "number": "1.0.0",
          "summary": "Initial revision."
        }
      ],
      "status": "final",
      "version": "1.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "branches": [
                  {
                    "category": "product_version_range",
                    "name": "vers:generic/\u003e=1.0.0.0|\u003c1.40.0.0",
                    "product": {
                      "name": "CODESYS Automation Server Connector 1.0.0.0\u003c1.40.0.0",
                      "product_id": "CSAFPID-51001",
                      "product_identification_helper": {
                        "cpe": "cpe:2.3:a:codesys:codesys_automation_server_connector:*:*:*:*:*:*:*:*"
                      }
                    }
                  },
                  {
                    "category": "product_version",
                    "name": "1.40.0.0",
                    "product": {
                      "name": "CODESYS Automation Server Connector 1.40.0.0",
                      "product_id": "CSAFPID-52001",
                      "product_identification_helper": {
                        "cpe": "cpe:2.3:a:codesys:codesys_automation_server_connector:1.40.0.0:*:*:*:*:*:*:*"
                      }
                    }
                  }
                ],
                "category": "product_name",
                "name": "CODESYS Automation Server Connector"
              },
              {
                "branches": [
                  {
                    "category": "product_version_range",
                    "name": "vers:generic/\u003e=1.0.0.0|\u003c1.40.0.0",
                    "product": {
                      "name": "CODESYS Service Tool 1.0.0.0\u003c1.40.0.0",
                      "product_id": "CSAFPID-51002",
                      "product_identification_helper": {
                        "cpe": "cpe:2.3:a:codesys:codesys_service_tool:*:*:*:*:*:*:*:*"
                      }
                    }
                  },
                  {
                    "category": "product_version",
                    "name": "1.40.0.0",
                    "product": {
                      "name": "CODESYS Service Tool 1.40.0.0",
                      "product_id": "CSAFPID-52002",
                      "product_identification_helper": {
                        "cpe": "cpe:2.3:a:codesys:codesys_service_tool:1.40.0.0:*:*:*:*:*:*:*"
                      }
                    }
                  }
                ],
                "category": "product_name",
                "name": "CODESYS Service Tool"
              }
            ],
            "category": "product_family",
            "name": "Software"
          }
        ],
        "category": "vendor",
        "name": "CODESYS"
      }
    ],
    "product_groups": [
      {
        "group_id": "CSAFGID-1001",
        "product_ids": [
          "CSAFPID-51001",
          "CSAFPID-51002"
        ],
        "summary": "Affected products v1.x."
      },
      {
        "group_id": "CSAFGID-2001",
        "product_ids": [
          "CSAFPID-52001",
          "CSAFPID-52002"
        ],
        "summary": "Fixed products v1.x."
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2026-118496",
      "cwe": {
        "id": "CWE-706",
        "name": "Use of Incorrectly-Resolved Name or Reference"
      },
      "notes": [
        {
          "audience": "all",
          "category": "description",
          "text": "The affected products process a server-supplied URL without sufficient validation. An unauthenticated remote attacker controlling a malicious Automation Server and tricking a user to trust it or performing a man-in-the-middle attack, can exploit this vulnerability by causing the affected product to process unintended content. Successful exploitation may result in arbitrary code execution with the privileges of the user running the affected product.",
          "title": "CVE description"
        }
      ],
      "product_status": {
        "fixed": [
          "CSAFPID-52001",
          "CSAFPID-52002"
        ],
        "known_affected": [
          "CSAFPID-51001",
          "CSAFPID-51002"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N - 7.5 / High",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update the following products to version 1.40.0.0.\n* CODESYS Automation Server Connector\n* CODESYS Service Tool\n\nThe CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.",
          "group_ids": [
            "CSAFGID-1001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "REQUIRED",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-51001",
            "CSAFPID-51002"
          ]
        }
      ],
      "title": "Use of Incorrectly-Resolved Name or Reference in CODESYS Automation Server Connector and CODESYS Service Tool"
    },
    {
      "cve": "CVE-2026-118497",
      "cwe": {
        "id": "CWE-295",
        "name": "Improper Certificate Validation"
      },
      "notes": [
        {
          "audience": "all",
          "category": "description",
          "text": "The affected products do not sufficiently validate CODESYS Automation Server TLS certificates when a user starts the certificate enrollment. An unauthenticated remote attacker performing a man-in-the-middle attack can exploit this vulnerability by supplying an untrusted certificate that is accepted as trusted. Successful exploitation may allow an attacker to intercept and manipulate communications between the CODESYS Automation Server and the PLC network.",
          "title": "CVE description"
        }
      ],
      "product_status": {
        "fixed": [
          "CSAFPID-52001",
          "CSAFPID-52002"
        ],
        "known_affected": [
          "CSAFPID-51001",
          "CSAFPID-51002"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:A/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N - 7.4 / High",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:A/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update the following products to version 1.40.0.0.\n* CODESYS Automation Server Connector\n* CODESYS Service Tool\n\nThe CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.",
          "group_ids": [
            "CSAFGID-1001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 6.8,
            "environmentalSeverity": "MEDIUM",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 6.8,
            "temporalSeverity": "MEDIUM",
            "userInteraction": "REQUIRED",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-51001",
            "CSAFPID-51002"
          ]
        }
      ],
      "title": "Improper Certificate Validation in CODESYS Automation Server Connector and CODESYS Service Tool"
    }
  ]
}



Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Drag nodes to arrange them. Double-click a related vulnerability to open it, or a source to visit its link. The Physics button on the left tunes the layout and the simulation; the legend at the bottom left hides or shows nodes by kind and by sighting type.

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Vulnerability timeline

Sightings and recorded dates, grouped by day · UTC

JSON
How durations are calculated

Following the VTEM framework (Black Hat USA 2015), time to patch starts when the vendor or a coordinator was informed, total time to patch at discovery, and disclosure to patch at public disclosure; vendor response time runs from the report to its acknowledgement. Time to exploit and time unpatched start at the earliest discovery or report, falling back to public disclosure. Unpatched time ends at the first recorded patch, or the calculation time when no patch is recorded. Exploitation to patch shows the interval between those two events; a published proof of concept is a public exploit, not exploitation.

Each result shows its source dates. A negative interval means the end event came first; when date-only inputs leave the order open, the result says so. Date-only inputs are approximate. The earliest evidence wins: KEV report dates and sightings are labelled as such. Records describing another vulnerability are listed but never calculated from, and a PoC alone does not establish exploitation. Missing patch evidence does not prove that no patch exists. Filters below change the event list only.

Events included in the timeline

Loading timeline…


    Loading…

    Loading…

    Loading…

    Related by attack behaviour