Search

Find a vulnerability

Search criteria

    10 vulnerabilities found for rslogix_500 by rockwellautomation

    CVE-2024-7847 (GCVE-0-2024-7847)

    Vulnerability from nvd – Published: 2024-10-14 13:47 – Updated: 2024-10-15 14:05
    VLAI
    Title
    RSLogix™ 5 and RSLogix 500® Remote Code Execution Via VBA Embedded Script
    Summary
    VULNERABILITY DETAILS Rockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. A feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention. This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability.
    SSVC
    Exploitation: none Automatable: no Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-345 - Insufficient Verification of Data Authenticity
    Assigner
    Impacted products
    Vendor Product Version
    Rockwell Automation RSLogix 500® Affected: All
    Create a notification for this product.
    Rockwell Automation RSLogix™ Micro Developer and Starter Affected: All
    Create a notification for this product.
    Rockwell Automation RSLogix™ 5 Affected: All
    Create a notification for this product.
    rockwellautomation rslogix_500 Affected: 0 , < * (custom)
        cpe:2.3:a:rockwellautomation:rslogix_500:*:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation rslogix_micro_developer Affected: 0 , < * (custom)
        cpe:2.3:a:rockwellautomation:rslogix_micro_developer:*:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation rslogix_micro_starter Affected: 0 , < * (custom)
        cpe:2.3:a:rockwellautomation:rslogix_micro_starter:*:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation rslogix_5 Affected: 0 , < * (custom)
        cpe:2.3:a:rockwellautomation:rslogix_5:*:*:*:*:*:*:*:*
    Create a notification for this product.
    Date Public
    2024-09-19 13:00
    Credits
    Sharon Brizinov of Claroty Research - Team82
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:rslogix_500:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "rslogix_500",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "lessThan": "*",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:rslogix_micro_developer:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "rslogix_micro_developer",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "lessThan": "*",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:rslogix_micro_starter:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "rslogix_micro_starter",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "lessThan": "*",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:rslogix_5:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "rslogix_5",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "lessThan": "*",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-7847",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-10-14T15:18:18.670939Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-10-15T14:05:45.670Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "RSLogix 500\u00ae",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "All"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "RSLogix\u2122 Micro Developer and Starter",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "All"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "RSLogix\u2122 5",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "All"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "reporter",
              "value": "Sharon Brizinov of Claroty Research - Team82"
            }
          ],
          "datePublic": "2024-09-19T13:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cp\u003e\u003cb\u003eVULNERABILITY DETAILS\u003c/b\u003e\u003c/p\u003e\u003cp\u003eRockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. \u003c/p\u003e\u003cp\u003eA feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention.  This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability.\u003c/p\u003e"
                }
              ],
              "value": "VULNERABILITY DETAILS\n\nRockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. \n\nA feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention.  This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-19",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-19 Embedding Scripts within Scripts"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "HIGH",
                "attackRequirements": "NONE",
                "attackVector": "LOCAL",
                "baseScore": 8.8,
                "baseSeverity": "HIGH",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "HIGH",
                "subConfidentialityImpact": "HIGH",
                "subIntegrityImpact": "HIGH",
                "userInteraction": "PASSIVE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            },
            {
              "cvssV3_1": {
                "attackComplexity": "HIGH",
                "attackVector": "LOCAL",
                "availabilityImpact": "HIGH",
                "baseScore": 7.7,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "HIGH",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "CHANGED",
                "userInteraction": "REQUIRED",
                "vectorString": "CVSS:3.1/AV:L/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-345",
                  "description": "CWE-345 Insufficient Verification of Data Authenticity",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-10-14T13:47:14.540Z",
            "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
            "shortName": "Rockwell"
          },
          "references": [
            {
              "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1701.html"
            }
          ],
          "source": {
            "discovery": "EXTERNAL"
          },
          "title": "RSLogix\u2122 5 and RSLogix 500\u00ae Remote Code Execution Via VBA Embedded Script",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cp\u003e\u003cb\u003eMitigations and Workarounds \u003c/b\u003e\u003c/p\u003e\u003cp\u003eUsers using the affected software are encouraged to apply the following mitigations and security best practices, where possible. \u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Deny the execution feature in FactoryTalk\u00ae Administration Console, when not needed, by navigating to \u201cPolicies\u201d, selecting \u2018\u201dEnable/Disable VBA\u201d, and then checking the \u201cDeny\u201d box to block VBA code execution.\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Save project files in a Trusted\u00ae location where only administrators can modify it and verify file integrity.\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Utilize the VBA editor protection feature, which locks the VBA code from viewing and editing by setting a password.\u003c/p\u003e"
                }
              ],
              "value": "Mitigations and Workarounds \n\nUsers using the affected software are encouraged to apply the following mitigations and security best practices, where possible. \n\n\u00b7 \u00a0 \u00a0 \u00a0 Deny the execution feature in FactoryTalk\u00ae Administration Console, when not needed, by navigating to \u201cPolicies\u201d, selecting \u2018\u201dEnable/Disable VBA\u201d, and then checking the \u201cDeny\u201d box to block VBA code execution.\n\n\u00b7 \u00a0 \u00a0 \u00a0 Save project files in a Trusted\u00ae location where only administrators can modify it and verify file integrity.\n\n\u00b7 \u00a0 \u00a0 \u00a0 Utilize the VBA editor protection feature, which locks the VBA code from viewing and editing by setting a password."
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "assignerShortName": "Rockwell",
        "cveId": "CVE-2024-7847",
        "datePublished": "2024-10-14T13:47:14.540Z",
        "dateReserved": "2024-08-15T15:51:22.233Z",
        "dateUpdated": "2024-10-15T14:05:45.670Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2020-6990 (GCVE-0-2020-6990)

    Vulnerability from nvd – Published: 2020-03-16 15:39 – Updated: 2026-06-03 13:26
    VLAI
    Summary
    Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-321 - USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321
    Assigner
    References
    Impacted products
    Vendor Product Version
    n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Affected: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T09:18:02.522Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "cvssV3_1": {
                  "attackComplexity": "LOW",
                  "attackVector": "NETWORK",
                  "availabilityImpact": "HIGH",
                  "baseScore": 9.8,
                  "baseSeverity": "CRITICAL",
                  "confidentialityImpact": "HIGH",
                  "integrityImpact": "HIGH",
                  "privilegesRequired": "NONE",
                  "scope": "UNCHANGED",
                  "userInteraction": "NONE",
                  "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
                  "version": "3.1"
                }
              },
              {
                "other": {
                  "content": {
                    "id": "CVE-2020-6990",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-03T13:26:22.690361Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-03T13:26:25.620Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-321",
                  "description": "USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2020-03-16T15:39:45.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2020-6990",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
                  "refsource": "MISC",
                  "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2020-6990",
        "datePublished": "2020-03-16T15:39:45.000Z",
        "dateReserved": "2020-01-14T00:00:00.000Z",
        "dateUpdated": "2026-06-03T13:26:25.620Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2020-6988 (GCVE-0-2020-6988)

    Vulnerability from nvd – Published: 2020-03-16 15:38 – Updated: 2026-06-03 13:21
    VLAI
    Summary
    Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: partial
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-603 - USE OF CLIENT-SIDE AUTHENTICATION CWE-603
    Assigner
    References
    Impacted products
    Vendor Product Version
    n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Affected: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T09:18:02.514Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "cvssV3_1": {
                  "attackComplexity": "LOW",
                  "attackVector": "NETWORK",
                  "availabilityImpact": "NONE",
                  "baseScore": 7.5,
                  "baseSeverity": "HIGH",
                  "confidentialityImpact": "HIGH",
                  "integrityImpact": "NONE",
                  "privilegesRequired": "NONE",
                  "scope": "UNCHANGED",
                  "userInteraction": "NONE",
                  "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
                  "version": "3.1"
                }
              },
              {
                "other": {
                  "content": {
                    "id": "CVE-2020-6988",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-03T13:21:18.328497Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-03T13:21:33.239Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim\u2019s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-603",
                  "description": "USE OF CLIENT-SIDE AUTHENTICATION CWE-603",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2020-03-16T15:38:36.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2020-6988",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim\u2019s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "USE OF CLIENT-SIDE AUTHENTICATION CWE-603"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
                  "refsource": "MISC",
                  "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2020-6988",
        "datePublished": "2020-03-16T15:38:36.000Z",
        "dateReserved": "2020-01-14T00:00:00.000Z",
        "dateUpdated": "2026-06-03T13:21:33.239Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2020-6984 (GCVE-0-2020-6984)

    Vulnerability from nvd – Published: 2020-03-16 15:41 – Updated: 2026-06-03 13:22
    VLAI
    Summary
    Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-327 - USE OF A BROKEN OR RISKY ALGORITHM FOR PASSWORD PROTECTION USE OF CLIENT-SIDE AUTHENTICATION CWE-327
    • CWE-327 - Use of a Broken or Risky Cryptographic Algorithm
    Assigner
    References
    Impacted products
    Vendor Product Version
    n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Affected: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T09:18:02.527Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "cvssV3_1": {
                  "attackComplexity": "LOW",
                  "attackVector": "NETWORK",
                  "availabilityImpact": "HIGH",
                  "baseScore": 9.8,
                  "baseSeverity": "CRITICAL",
                  "confidentialityImpact": "HIGH",
                  "integrityImpact": "HIGH",
                  "privilegesRequired": "NONE",
                  "scope": "UNCHANGED",
                  "userInteraction": "NONE",
                  "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
                  "version": "3.1"
                }
              },
              {
                "other": {
                  "content": {
                    "id": "CVE-2020-6984",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-03T13:22:41.979961Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "problemTypes": [
              {
                "descriptions": [
                  {
                    "cweId": "CWE-327",
                    "description": "CWE-327 Use of a Broken or Risky Cryptographic Algorithm",
                    "lang": "en",
                    "type": "CWE"
                  }
                ]
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-03T13:22:52.674Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-327",
                  "description": "USE OF A BROKEN OR RISKY ALGORITHM FOR PASSWORD PROTECTION USE OF CLIENT-SIDE AUTHENTICATION CWE-327",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2020-03-16T15:41:13.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2020-6984",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "USE OF A BROKEN OR RISKY ALGORITHM FOR PASSWORD PROTECTION USE OF CLIENT-SIDE AUTHENTICATION CWE-327"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
                  "refsource": "MISC",
                  "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2020-6984",
        "datePublished": "2020-03-16T15:41:13.000Z",
        "dateReserved": "2020-01-14T00:00:00.000Z",
        "dateUpdated": "2026-06-03T13:22:52.674Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2020-6980 (GCVE-0-2020-6980)

    Vulnerability from nvd – Published: 2020-03-16 15:36 – Updated: 2024-08-04 09:18
    VLAI
    Summary
    Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim’s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext.
    Severity
    No CVSS data available.
    CWE
    • CWE-312 - CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312
    Assigner
    References
    Impacted products
    Vendor Product Version
    n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Affected: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T09:18:02.979Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim\u2019s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-312",
                  "description": "CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2020-03-16T15:36:51.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2020-6980",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim\u2019s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
                  "refsource": "MISC",
                  "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2020-6980",
        "datePublished": "2020-03-16T15:36:51.000Z",
        "dateReserved": "2020-01-14T00:00:00.000Z",
        "dateUpdated": "2024-08-04T09:18:02.979Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2024-7847 (GCVE-0-2024-7847)

    Vulnerability from cvelistv5 – Published: 2024-10-14 13:47 – Updated: 2024-10-15 14:05
    VLAI
    Title
    RSLogix™ 5 and RSLogix 500® Remote Code Execution Via VBA Embedded Script
    Summary
    VULNERABILITY DETAILS Rockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. A feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention. This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability.
    SSVC
    Exploitation: none Automatable: no Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-345 - Insufficient Verification of Data Authenticity
    Assigner
    Impacted products
    Vendor Product Version
    Rockwell Automation RSLogix 500® Affected: All
    Create a notification for this product.
    Rockwell Automation RSLogix™ Micro Developer and Starter Affected: All
    Create a notification for this product.
    Rockwell Automation RSLogix™ 5 Affected: All
    Create a notification for this product.
    rockwellautomation rslogix_500 Affected: 0 , < * (custom)
        cpe:2.3:a:rockwellautomation:rslogix_500:*:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation rslogix_micro_developer Affected: 0 , < * (custom)
        cpe:2.3:a:rockwellautomation:rslogix_micro_developer:*:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation rslogix_micro_starter Affected: 0 , < * (custom)
        cpe:2.3:a:rockwellautomation:rslogix_micro_starter:*:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation rslogix_5 Affected: 0 , < * (custom)
        cpe:2.3:a:rockwellautomation:rslogix_5:*:*:*:*:*:*:*:*
    Create a notification for this product.
    Date Public
    2024-09-19 13:00
    Credits
    Sharon Brizinov of Claroty Research - Team82
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:rslogix_500:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "rslogix_500",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "lessThan": "*",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:rslogix_micro_developer:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "rslogix_micro_developer",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "lessThan": "*",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:rslogix_micro_starter:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "rslogix_micro_starter",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "lessThan": "*",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:rslogix_5:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "rslogix_5",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "lessThan": "*",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-7847",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-10-14T15:18:18.670939Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-10-15T14:05:45.670Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "RSLogix 500\u00ae",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "All"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "RSLogix\u2122 Micro Developer and Starter",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "All"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "RSLogix\u2122 5",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "All"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "reporter",
              "value": "Sharon Brizinov of Claroty Research - Team82"
            }
          ],
          "datePublic": "2024-09-19T13:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cp\u003e\u003cb\u003eVULNERABILITY DETAILS\u003c/b\u003e\u003c/p\u003e\u003cp\u003eRockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. \u003c/p\u003e\u003cp\u003eA feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention.  This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability.\u003c/p\u003e"
                }
              ],
              "value": "VULNERABILITY DETAILS\n\nRockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. \n\nA feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention.  This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-19",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-19 Embedding Scripts within Scripts"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "HIGH",
                "attackRequirements": "NONE",
                "attackVector": "LOCAL",
                "baseScore": 8.8,
                "baseSeverity": "HIGH",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "HIGH",
                "subConfidentialityImpact": "HIGH",
                "subIntegrityImpact": "HIGH",
                "userInteraction": "PASSIVE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            },
            {
              "cvssV3_1": {
                "attackComplexity": "HIGH",
                "attackVector": "LOCAL",
                "availabilityImpact": "HIGH",
                "baseScore": 7.7,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "HIGH",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "CHANGED",
                "userInteraction": "REQUIRED",
                "vectorString": "CVSS:3.1/AV:L/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-345",
                  "description": "CWE-345 Insufficient Verification of Data Authenticity",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-10-14T13:47:14.540Z",
            "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
            "shortName": "Rockwell"
          },
          "references": [
            {
              "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1701.html"
            }
          ],
          "source": {
            "discovery": "EXTERNAL"
          },
          "title": "RSLogix\u2122 5 and RSLogix 500\u00ae Remote Code Execution Via VBA Embedded Script",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cp\u003e\u003cb\u003eMitigations and Workarounds \u003c/b\u003e\u003c/p\u003e\u003cp\u003eUsers using the affected software are encouraged to apply the following mitigations and security best practices, where possible. \u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Deny the execution feature in FactoryTalk\u00ae Administration Console, when not needed, by navigating to \u201cPolicies\u201d, selecting \u2018\u201dEnable/Disable VBA\u201d, and then checking the \u201cDeny\u201d box to block VBA code execution.\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Save project files in a Trusted\u00ae location where only administrators can modify it and verify file integrity.\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Utilize the VBA editor protection feature, which locks the VBA code from viewing and editing by setting a password.\u003c/p\u003e"
                }
              ],
              "value": "Mitigations and Workarounds \n\nUsers using the affected software are encouraged to apply the following mitigations and security best practices, where possible. \n\n\u00b7 \u00a0 \u00a0 \u00a0 Deny the execution feature in FactoryTalk\u00ae Administration Console, when not needed, by navigating to \u201cPolicies\u201d, selecting \u2018\u201dEnable/Disable VBA\u201d, and then checking the \u201cDeny\u201d box to block VBA code execution.\n\n\u00b7 \u00a0 \u00a0 \u00a0 Save project files in a Trusted\u00ae location where only administrators can modify it and verify file integrity.\n\n\u00b7 \u00a0 \u00a0 \u00a0 Utilize the VBA editor protection feature, which locks the VBA code from viewing and editing by setting a password."
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "assignerShortName": "Rockwell",
        "cveId": "CVE-2024-7847",
        "datePublished": "2024-10-14T13:47:14.540Z",
        "dateReserved": "2024-08-15T15:51:22.233Z",
        "dateUpdated": "2024-10-15T14:05:45.670Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2020-6984 (GCVE-0-2020-6984)

    Vulnerability from cvelistv5 – Published: 2020-03-16 15:41 – Updated: 2026-06-03 13:22
    VLAI
    Summary
    Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-327 - USE OF A BROKEN OR RISKY ALGORITHM FOR PASSWORD PROTECTION USE OF CLIENT-SIDE AUTHENTICATION CWE-327
    • CWE-327 - Use of a Broken or Risky Cryptographic Algorithm
    Assigner
    References
    Impacted products
    Vendor Product Version
    n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Affected: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T09:18:02.527Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "cvssV3_1": {
                  "attackComplexity": "LOW",
                  "attackVector": "NETWORK",
                  "availabilityImpact": "HIGH",
                  "baseScore": 9.8,
                  "baseSeverity": "CRITICAL",
                  "confidentialityImpact": "HIGH",
                  "integrityImpact": "HIGH",
                  "privilegesRequired": "NONE",
                  "scope": "UNCHANGED",
                  "userInteraction": "NONE",
                  "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
                  "version": "3.1"
                }
              },
              {
                "other": {
                  "content": {
                    "id": "CVE-2020-6984",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-03T13:22:41.979961Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "problemTypes": [
              {
                "descriptions": [
                  {
                    "cweId": "CWE-327",
                    "description": "CWE-327 Use of a Broken or Risky Cryptographic Algorithm",
                    "lang": "en",
                    "type": "CWE"
                  }
                ]
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-03T13:22:52.674Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-327",
                  "description": "USE OF A BROKEN OR RISKY ALGORITHM FOR PASSWORD PROTECTION USE OF CLIENT-SIDE AUTHENTICATION CWE-327",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2020-03-16T15:41:13.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2020-6984",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "USE OF A BROKEN OR RISKY ALGORITHM FOR PASSWORD PROTECTION USE OF CLIENT-SIDE AUTHENTICATION CWE-327"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
                  "refsource": "MISC",
                  "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2020-6984",
        "datePublished": "2020-03-16T15:41:13.000Z",
        "dateReserved": "2020-01-14T00:00:00.000Z",
        "dateUpdated": "2026-06-03T13:22:52.674Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2020-6990 (GCVE-0-2020-6990)

    Vulnerability from cvelistv5 – Published: 2020-03-16 15:39 – Updated: 2026-06-03 13:26
    VLAI
    Summary
    Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-321 - USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321
    Assigner
    References
    Impacted products
    Vendor Product Version
    n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Affected: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T09:18:02.522Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "cvssV3_1": {
                  "attackComplexity": "LOW",
                  "attackVector": "NETWORK",
                  "availabilityImpact": "HIGH",
                  "baseScore": 9.8,
                  "baseSeverity": "CRITICAL",
                  "confidentialityImpact": "HIGH",
                  "integrityImpact": "HIGH",
                  "privilegesRequired": "NONE",
                  "scope": "UNCHANGED",
                  "userInteraction": "NONE",
                  "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
                  "version": "3.1"
                }
              },
              {
                "other": {
                  "content": {
                    "id": "CVE-2020-6990",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-03T13:26:22.690361Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-03T13:26:25.620Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-321",
                  "description": "USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2020-03-16T15:39:45.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2020-6990",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
                  "refsource": "MISC",
                  "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2020-6990",
        "datePublished": "2020-03-16T15:39:45.000Z",
        "dateReserved": "2020-01-14T00:00:00.000Z",
        "dateUpdated": "2026-06-03T13:26:25.620Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2020-6988 (GCVE-0-2020-6988)

    Vulnerability from cvelistv5 – Published: 2020-03-16 15:38 – Updated: 2026-06-03 13:21
    VLAI
    Summary
    Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: partial
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-603 - USE OF CLIENT-SIDE AUTHENTICATION CWE-603
    Assigner
    References
    Impacted products
    Vendor Product Version
    n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Affected: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T09:18:02.514Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "cvssV3_1": {
                  "attackComplexity": "LOW",
                  "attackVector": "NETWORK",
                  "availabilityImpact": "NONE",
                  "baseScore": 7.5,
                  "baseSeverity": "HIGH",
                  "confidentialityImpact": "HIGH",
                  "integrityImpact": "NONE",
                  "privilegesRequired": "NONE",
                  "scope": "UNCHANGED",
                  "userInteraction": "NONE",
                  "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
                  "version": "3.1"
                }
              },
              {
                "other": {
                  "content": {
                    "id": "CVE-2020-6988",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-03T13:21:18.328497Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-03T13:21:33.239Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim\u2019s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-603",
                  "description": "USE OF CLIENT-SIDE AUTHENTICATION CWE-603",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2020-03-16T15:38:36.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2020-6988",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim\u2019s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "USE OF CLIENT-SIDE AUTHENTICATION CWE-603"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
                  "refsource": "MISC",
                  "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2020-6988",
        "datePublished": "2020-03-16T15:38:36.000Z",
        "dateReserved": "2020-01-14T00:00:00.000Z",
        "dateUpdated": "2026-06-03T13:21:33.239Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2020-6980 (GCVE-0-2020-6980)

    Vulnerability from cvelistv5 – Published: 2020-03-16 15:36 – Updated: 2024-08-04 09:18
    VLAI
    Summary
    Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim’s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext.
    Severity
    No CVSS data available.
    CWE
    • CWE-312 - CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312
    Assigner
    References
    Impacted products
    Vendor Product Version
    n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Affected: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T09:18:02.979Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim\u2019s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-312",
                  "description": "CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2020-03-16T15:36:51.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2020-6980",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim\u2019s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
                  "refsource": "MISC",
                  "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2020-6980",
        "datePublished": "2020-03-16T15:36:51.000Z",
        "dateReserved": "2020-01-14T00:00:00.000Z",
        "dateUpdated": "2024-08-04T09:18:02.979Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }