SSA-766247
Vulnerability from csaf_siemens - Published: 2021-10-12 00:00 - Updated: 2022-01-11 00:00| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
SIMATIC Process Historian 2013 and earlier
Siemens / SIMATIC Process Historian 2013 and earlier
|
vers:all/* |
Mitigation
No Fix Planned
Mitigation
Mitigation
|
|
|
SIMATIC Process Historian 2014
Siemens / SIMATIC Process Historian 2014
|
< SP3 Update 6 |
Vendor Fix
fix
Mitigation
Mitigation
|
|
|
SIMATIC Process Historian 2019
Siemens / SIMATIC Process Historian 2019
|
vers:all/* |
Mitigation
No Fix Planned
Mitigation
Mitigation
|
|
|
SIMATIC Process Historian 2020
Siemens / SIMATIC Process Historian 2020
|
vers:all/* |
Vendor Fix
Vendor Fix
Mitigation
Mitigation
|
{
"document": {
"category": "Siemens Security Advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited.",
"tlp": {
"label": "WHITE"
}
},
"notes": [
{
"category": "summary",
"text": "The latest update for SIMATIC Process Historian (PH) fixes an authentication vulnerability in the configuration interface of redundant PH instances that could enable the execution of admin operations on the database.\n\nThe related vulnerable interface is restricted to local access on recent versions starting from SIMATIC Process Historian 2020.\n\nSiemens has released updates for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not, or not yet available.",
"title": "Summary"
},
{
"category": "general",
"text": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-766247: Authentication Vulnerability in SIMATIC Process Historian - PDF Version",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-766247.pdf"
},
{
"category": "self",
"summary": "SSA-766247: Authentication Vulnerability in SIMATIC Process Historian - TXT Version",
"url": "https://cert-portal.siemens.com/productcert/txt/ssa-766247.txt"
},
{
"category": "self",
"summary": "SSA-766247: Authentication Vulnerability in SIMATIC Process Historian - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-766247.json"
}
],
"title": "SSA-766247: Authentication Vulnerability in SIMATIC Process Historian",
"tracking": {
"current_release_date": "2022-01-11T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-766247",
"initial_release_date": "2021-10-12T00:00:00Z",
"revision_history": [
{
"date": "2021-10-12T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
},
{
"date": "2022-01-11T00:00:00Z",
"legacy_version": "1.1",
"number": "2",
"summary": "Added solution for SIMATIC Process Historian 2020"
}
],
"status": "final",
"version": "2"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "SIMATIC Process Historian 2013 and earlier",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "SIMATIC Process Historian 2013 and earlier"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c SP3 Update 6",
"product": {
"name": "SIMATIC Process Historian 2014",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "SIMATIC Process Historian 2014"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "SIMATIC Process Historian 2019",
"product_id": "3"
}
}
],
"category": "product_name",
"name": "SIMATIC Process Historian 2019"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "SIMATIC Process Historian 2020",
"product_id": "4"
}
}
],
"category": "product_name",
"name": "SIMATIC Process Historian 2020"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2021-27395",
"cwe": {
"id": "CWE-306",
"name": "Missing Authentication for Critical Function"
},
"notes": [
{
"category": "summary",
"text": "An interface in the software that is used for critical functionalities lacks authentication, which could allow a malicious user to maliciously insert, modify or delete data.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1",
"2",
"3",
"4"
]
},
"references": [
{
"summary": "CVE-2021-27395 - SIMATIC Process Historian 2014",
"url": "https://support.industry.siemens.com/cs/ww/en/view/109780528/"
},
{
"summary": "CVE-2021-27395 Mitre 5.0 json",
"url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-27395.json"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Consider upgrading to a newer SIMATIC Process Historian version",
"product_ids": [
"1",
"3"
]
},
{
"category": "no_fix_planned",
"details": "Currently no remediation is planned",
"product_ids": [
"1",
"3"
]
},
{
"category": "vendor_fix",
"details": "Update to SP3 Update 6 or later version",
"product_ids": [
"2"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109780528/"
},
{
"category": "vendor_fix",
"details": "Update to 2020 Update 2 or later version",
"product_ids": [
"4"
]
},
{
"category": "vendor_fix",
"details": "To update, use the Process Historian version as bundled with PCS neo V3.1 Upd1 (https://support.industry.siemens.com/cs/ww/en/view/109804750/) or with PCS 7 V9.1 SP1 (https://support.industry.siemens.com/cs/ww/en/view/109805073/)",
"product_ids": [
"4"
]
},
{
"category": "mitigation",
"details": "Deactivate following incoming rules in the local Windows firewall:\n\n- PH Redundancy Services\n- PH Wcf MessageQueue Service (RedundancyMaintenanceService)\n- PH Wcf MessageQueue Service (SqlMirroringSetup)\n- PH Wcf MessageQueue Service (MaintenanceService)\n- PH SQL-Server Mirroring Port (UDP)\n- PH SQL-Server Mirroring Port (TCP)",
"product_ids": [
"1",
"2",
"3",
"4"
]
},
{
"category": "mitigation",
"details": "In case SIMATIC Process Historian is used as a redundant system, restrict remote IP addresses in the firewall rules to allow only access for the Master, the Standby and the Mirror server",
"product_ids": [
"1",
"2",
"3",
"4"
]
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C",
"version": "3.1"
},
"products": [
"1",
"2",
"3",
"4"
]
}
],
"title": "CVE-2021-27395"
}
]
}
Drag nodes to arrange them. Double-click a related vulnerability to open it, or a source to visit its link. The Physics button on the left tunes the layout and the simulation; the legend at the bottom left hides or shows nodes by kind and by sighting type.
Sightings
| Author | Source | Type | Date | Other |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Vulnerability timeline
Sightings and recorded dates, grouped by day · UTC
How durations are calculated
Following the VTEM framework (Black Hat USA 2015), time to patch starts when the vendor or a coordinator was informed, total time to patch at discovery, and disclosure to patch at public disclosure; vendor response time runs from the report to its acknowledgement. Time to exploit and time unpatched start at the earliest discovery or report, falling back to public disclosure. Unpatched time ends at the first recorded patch, or the calculation time when no patch is recorded. Exploitation to patch shows the interval between those two events; a published proof of concept is a public exploit, not exploitation.
Each result shows its source dates. A negative interval means the end event came first; when date-only inputs leave the order open, the result says so. Date-only inputs are approximate. The earliest evidence wins: KEV report dates and sightings are labelled as such. Records describing another vulnerability are listed but never calculated from, and a PoC alone does not establish exploitation. Missing patch evidence does not prove that no patch exists. Filters below change the event list only.
Loading timeline…
The approach is described in our paper Mapping CVEs to MITRE ATT&CK Techniques: A Curated Gold-Set Classifier and the Limits of LLM-Assisted Label Expansion.
Browse all ATT&CK techniques and the vulnerabilities related to each.
Related by attack behaviour
Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.