FKIE_CVE-2019-5181
Vulnerability from fkie_nvd - Published: 2020-03-12 00:15 - Updated: 2026-06-17 02:37| URL | Tags | ||
|---|---|---|---|
| talos-cna@cisco.com | https://talosintelligence.com/vulnerability_reports/TALOS-2019-0963 | Exploit, Technical Description, Third Party Advisory | |
| af854a3a-2127-422b-91ae-364da2661108 | https://talosintelligence.com/vulnerability_reports/TALOS-2019-0963 | Exploit, Technical Description, Third Party Advisory |
| Vendor | Product | Version | |
|---|---|---|---|
| wago | pfc200_firmware | 03.02.02\(14\) | |
| wago | pfc200 | - |
{
"affected": [
{
"affectedData": [
{
"product": "WAGO PFC200",
"vendor": "Wago",
"versions": [
{
"status": "affected",
"version": "Firmware version 03.02.02(14)"
}
]
}
],
"source": "talos-cna@cisco.com"
}
],
"configurations": [
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:pfc200_firmware:03.02.02\\(14\\):*:*:*:*:*:*:*",
"matchCriteriaId": "6274B67D-C65B-4834-9DB5-6FB3D0ADD3A9",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:pfc200:-:*:*:*:*:*:*:*",
"matchCriteriaId": "688A3248-7EAA-499D-A47C-A4D4900CDBD1",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
}
],
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service \u2018I/O-Check\u2019 functionality of WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can cause a stack buffer overflow, resulting in code execution. An attacker can send a specially crafted packet to trigger the parsing of this cache file. The destination buffer sp+0x440 is overflowed with the call to sprintf() for any subnetmask values that are greater than 1024-len(\u2018/etc/config-tools/config_interfaces interface=X1 state=enabled subnet-mask=\u2018) in length. A subnetmask value of length 0x3d9 will cause the service to crash."
},
{
"lang": "es",
"value": "Se presenta una vulnerabilidad de desbordamiento del b\u00fafer de la pila explotable en la funcionalidad \"I-O-Check\" del servicio iocheckd de WAGO PFC 200, versiones de Firmware 03.02.02(14). Un archivo cache XML especialmente dise\u00f1ado escrito en una ubicaci\u00f3n espec\u00edfica en el dispositivo puede causar un desbordamiento del b\u00fafer de la pila, resultando en una ejecuci\u00f3n de c\u00f3digo. Un atacante puede enviar un paquete especialmente dise\u00f1ado para activar el an\u00e1lisis de este archivo cache. El b\u00fafer destino p+0x440 es desbordado con la llamada a la funci\u00f3n sprintf() para cualquier valor de mascara de subred que sea mayor que 11024-len(\u2018/etc/config-tools/config_interfaces interface=X1 state=enabled subnet-mask=\u2018) en longitud. Un valor de mascara de subred de longitud 0x3d9 causar\u00e1 que el servicio se bloquee."
}
],
"id": "CVE-2019-5181",
"lastModified": "2026-06-17T02:37:16.350",
"metrics": {
"cvssMetricV2": [
{
"acInsufInfo": false,
"baseSeverity": "MEDIUM",
"cvssData": {
"accessComplexity": "LOW",
"accessVector": "LOCAL",
"authentication": "NONE",
"availabilityImpact": "PARTIAL",
"baseScore": 4.6,
"confidentialityImpact": "PARTIAL",
"integrityImpact": "PARTIAL",
"vectorString": "AV:L/AC:L/Au:N/C:P/I:P/A:P",
"version": "2.0"
},
"exploitabilityScore": 3.9,
"impactScore": 6.4,
"obtainAllPrivilege": false,
"obtainOtherPrivilege": false,
"obtainUserPrivilege": false,
"source": "nvd@nist.gov",
"type": "Primary",
"userInteractionRequired": false
}
],
"cvssMetricV31": [
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"exploitabilityScore": 1.8,
"impactScore": 5.9,
"source": "nvd@nist.gov",
"type": "Primary"
}
]
},
"published": "2020-03-12T00:15:18.493",
"references": [
{
"source": "talos-cna@cisco.com",
"tags": [
"Exploit",
"Technical Description",
"Third Party Advisory"
],
"url": "https://talosintelligence.com/vulnerability_reports/TALOS-2019-0963"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Exploit",
"Technical Description",
"Third Party Advisory"
],
"url": "https://talosintelligence.com/vulnerability_reports/TALOS-2019-0963"
}
],
"sourceIdentifier": "talos-cna@cisco.com",
"vulnStatus": "Modified",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-787"
}
],
"source": "nvd@nist.gov",
"type": "Primary"
}
]
}
Drag nodes to arrange them. Double-click a related vulnerability to open it, or a source to visit its link. The Physics button on the left tunes the layout and the simulation; the legend at the bottom left hides or shows nodes by kind and by sighting type.
Sightings
| Author | Source | Type | Date | Other |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Vulnerability timeline
Sightings and recorded dates, grouped by day · UTC
How durations are calculated
Following the VTEM framework (Black Hat USA 2015), time to patch starts when the vendor or a coordinator was informed, total time to patch at discovery, and disclosure to patch at public disclosure; vendor response time runs from the report to its acknowledgement. Time to exploit and time unpatched start at the earliest discovery or report, falling back to public disclosure. Unpatched time ends at the first recorded patch, or the calculation time when no patch is recorded. Exploitation to patch shows the interval between those two events; a published proof of concept is a public exploit, not exploitation.
Each result shows its source dates. A negative interval means the end event came first; when date-only inputs leave the order open, the result says so. Date-only inputs are approximate. The earliest evidence wins: KEV report dates and sightings are labelled as such. Records describing another vulnerability are listed but never calculated from, and a PoC alone does not establish exploitation. Missing patch evidence does not prove that no patch exists. Filters below change the event list only.
Loading timeline…
The approach is described in our paper Mapping CVEs to MITRE ATT&CK Techniques: A Curated Gold-Set Classifier and the Limits of LLM-Assisted Label Expansion.
Browse all ATT&CK techniques and the vulnerabilities related to each.
Related by attack behaviour
Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.