CVE-2023-6711 (GCVE-0-2023-6711)
Vulnerability from cvelistv5 – Published: 2023-12-19 14:53 – Updated: 2024-09-25 08:43- CWE-120 - Buffer Copy without Checking Size of Input ('Classic Buffer Overflow')
| URL | Tags |
|---|---|
| https://publisher.hitachienergy.com/preview?Docum… | vendor-advisory |
| Vendor | Product | Version | |
|---|---|---|---|
| Hitachi Energy | RTU500 series CMU Firmware |
Affected:
12.0.1 , ≤ 12.0.14
(custom)
Affected: 12.2.1 , ≤ 12.2.11 (custom) Affected: 12.4.1 , ≤ 12.4.11 (custom) Affected: 12.6.1 , ≤ 12.6.9 (custom) Affected: 12.7.1 , ≤ 12.7.6 (custom) Affected: 13.2.1 , ≤ 13.2.6 (custom) Affected: 13.4.1 , ≤ 13.4.3 (custom) Affected: 13.5.1 |
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-02T08:35:14.886Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"vendor-advisory",
"x_transferred"
],
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "RTU500 series CMU Firmware",
"vendor": "Hitachi Energy",
"versions": [
{
"lessThanOrEqual": "12.0.14",
"status": "affected",
"version": "12.0.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "12.2.11",
"status": "affected",
"version": "12.2.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "12.4.11",
"status": "affected",
"version": "12.4.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "12.6.9",
"status": "affected",
"version": "12.6.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "12.7.6",
"status": "affected",
"version": "12.7.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "13.2.6",
"status": "affected",
"version": "13.2.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "13.4.3",
"status": "affected",
"version": "13.4.1",
"versionType": "custom"
},
{
"status": "affected",
"version": "13.5.1"
}
]
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU."
}
],
"value": "Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU."
}
],
"impacts": [
{
"capecId": "CAPEC-100",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-100 Overflow Buffers"
}
]
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-120",
"description": "CWE-120 Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2024-09-25T08:43:52.208Z",
"orgId": "e383dce4-0c27-4495-91c4-0db157728d17",
"shortName": "Hitachi Energy"
},
"references": [
{
"tags": [
"vendor-advisory"
],
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true"
}
],
"source": {
"discovery": "UNKNOWN"
},
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "e383dce4-0c27-4495-91c4-0db157728d17",
"assignerShortName": "Hitachi Energy",
"cveId": "CVE-2023-6711",
"datePublished": "2023-12-19T14:53:44.658Z",
"dateReserved": "2023-12-12T06:25:59.268Z",
"dateUpdated": "2024-09-25T08:43:52.208Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1",
"vulnerability-lookup:meta": {
"epss": {
"cve": "CVE-2023-6711",
"date": "2026-06-30",
"epss": "0.00669",
"percentile": "0.47281"
},
"nvd": "{\"cve\":{\"id\":\"CVE-2023-6711\",\"sourceIdentifier\":\"cybersecurity@hitachienergy.com\",\"published\":\"2023-12-19T15:15:09.257\",\"lastModified\":\"2026-06-17T06:51:17.293\",\"vulnStatus\":\"Modified\",\"cveTags\":[],\"descriptions\":[{\"lang\":\"en\",\"value\":\"Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU.\"},{\"lang\":\"es\",\"value\":\"Existe una vulnerabilidad en SCI IEC 60870-5-104 y HCI IEC 60870-5-104 que afecta a las versiones de productos de RTU500 series que se enumeran a continuaci\u00f3n. Los mensajes especialmente manipulados enviados a los componentes mencionados no se validan correctamente y pueden provocar un desbordamiento de b\u00fafer y, como consecuencia final, un reinicio de una CMU RTU500.\"}],\"affected\":[{\"source\":\"cybersecurity@hitachienergy.com\",\"affectedData\":[{\"vendor\":\"Hitachi Energy\",\"product\":\"RTU500 series CMU Firmware\",\"defaultStatus\":\"unaffected\",\"versions\":[{\"version\":\"12.0.1\",\"lessThanOrEqual\":\"12.0.14\",\"versionType\":\"custom\",\"status\":\"affected\"},{\"version\":\"12.2.1\",\"lessThanOrEqual\":\"12.2.11\",\"versionType\":\"custom\",\"status\":\"affected\"},{\"version\":\"12.4.1\",\"lessThanOrEqual\":\"12.4.11\",\"versionType\":\"custom\",\"status\":\"affected\"},{\"version\":\"12.6.1\",\"lessThanOrEqual\":\"12.6.9\",\"versionType\":\"custom\",\"status\":\"affected\"},{\"version\":\"12.7.1\",\"lessThanOrEqual\":\"12.7.6\",\"versionType\":\"custom\",\"status\":\"affected\"},{\"version\":\"13.2.1\",\"lessThanOrEqual\":\"13.2.6\",\"versionType\":\"custom\",\"status\":\"affected\"},{\"version\":\"13.4.1\",\"lessThanOrEqual\":\"13.4.3\",\"versionType\":\"custom\",\"status\":\"affected\"},{\"version\":\"13.5.1\",\"status\":\"affected\"}]}]}],\"metrics\":{\"cvssMetricV31\":[{\"source\":\"cybersecurity@hitachienergy.com\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H\",\"baseScore\":5.9,\"baseSeverity\":\"MEDIUM\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"HIGH\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"NONE\",\"integrityImpact\":\"NONE\",\"availabilityImpact\":\"HIGH\"},\"exploitabilityScore\":2.2,\"impactScore\":3.6},{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H\",\"baseScore\":7.5,\"baseSeverity\":\"HIGH\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"NONE\",\"integrityImpact\":\"NONE\",\"availabilityImpact\":\"HIGH\"},\"exploitabilityScore\":3.9,\"impactScore\":3.6}]},\"weaknesses\":[{\"source\":\"cybersecurity@hitachienergy.com\",\"type\":\"Secondary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-120\"}]},{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-120\"}]}],\"configurations\":[{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*\",\"versionStartIncluding\":\"12.0.1.0\",\"versionEndExcluding\":\"12.0.15.0\",\"matchCriteriaId\":\"E50C1390-D171-43AA-91BB-BCE40AB8B4F5\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*\",\"versionStartIncluding\":\"12.2.1.0\",\"versionEndExcluding\":\"12.2.12.0\",\"matchCriteriaId\":\"99416778-6B10-4C85-BC6A-AA9D77707489\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*\",\"versionStartIncluding\":\"12.4.1.0\",\"versionEndExcluding\":\"12.4.12.0\",\"matchCriteriaId\":\"229DCAE7-8362-4C5F-B708-9B130123DAAC\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*\",\"versionStartIncluding\":\"12.6.1.0\",\"versionEndExcluding\":\"12.6.10.0\",\"matchCriteriaId\":\"6241D442-A026-4F8D-88CA-AF8A3AEB3F57\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*\",\"versionStartIncluding\":\"12.7.1.0\",\"versionEndExcluding\":\"12.7.7.0\",\"matchCriteriaId\":\"71BCAE0B-3CD2-495E-B44B-661656C4BD05\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*\",\"versionStartIncluding\":\"13.2.1.0\",\"versionEndExcluding\":\"13.2.7.0\",\"matchCriteriaId\":\"01D33538-A8C2-4FC3-84B3-5F43E7ABA6E8\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*\",\"versionStartIncluding\":\"13.4.1.0\",\"versionEndExcluding\":\"13.4.4.0\",\"matchCriteriaId\":\"6E7961A7-DA10-498D-B746-A35782A2C4DC\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:hitachienergy:rtu500_firmware:13.5.1.0:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"A3F2C69B-BDFA-42A2-B0DF-50D690CC5024\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"DE94252D-03EE-451B-8322-B4DBC790C6E9\"}]}]}],\"references\":[{\"url\":\"https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true\",\"source\":\"cybersecurity@hitachienergy.com\",\"tags\":[\"Vendor Advisory\"]},{\"url\":\"https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Vendor Advisory\"]}]}}"
}
}
{
"CVSS 2.0": "AV:N/AC:H/Au:N/C:N/I:N/A:C",
"CVSS 3.0": "AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
"CVSS 4.0": null,
"remediation_\u0418\u0434\u0435\u043d\u0442\u0438\u0444\u0438\u043a\u0430\u0442\u043e\u0440": null,
"remediation_\u041d\u0430\u0438\u043c\u0435\u043d\u043e\u0432\u0430\u043d\u0438\u0435": null,
"\u0412\u0435\u043d\u0434\u043e\u0440 \u041f\u041e": "Hitachi, Ltd.",
"\u0412\u0435\u0440\u0441\u0438\u044f \u041f\u041e": "\u043e\u0442 12.2.1.0 \u0434\u043e 12.2.11.0 \u0432\u043a\u043b\u044e\u0447\u0438\u0442\u0435\u043b\u044c\u043d\u043e (RTU500 series CMU), \u043e\u0442 12.4.1.0 \u0434\u043e 12.4.11.0 \u0432\u043a\u043b\u044e\u0447\u0438\u0442\u0435\u043b\u044c\u043d\u043e (RTU500 series CMU), \u043e\u0442 12.0.1.0 \u0434\u043e 12.0.14 \u0432\u043a\u043b\u044e\u0447\u0438\u0442\u0435\u043b\u044c\u043d\u043e (RTU500 series CMU), \u043e\u0442 12.6.1.0 \u0434\u043e 12.6.9.0 \u0432\u043a\u043b\u044e\u0447\u0438\u0442\u0435\u043b\u044c\u043d\u043e (RTU500 series CMU), \u043e\u0442 12.7.1.0 \u0434\u043e 12.7.6.0 \u0432\u043a\u043b\u044e\u0447\u0438\u0442\u0435\u043b\u044c\u043d\u043e (RTU500 series CMU), \u043e\u0442 13.2.1.0 \u0434\u043e 13.2.6.0 \u0432\u043a\u043b\u044e\u0447\u0438\u0442\u0435\u043b\u044c\u043d\u043e (RTU500 series CMU), \u043e\u0442 13.4.1.0 \u0434\u043e 13.4.3.0 \u0432\u043a\u043b\u044e\u0447\u0438\u0442\u0435\u043b\u044c\u043d\u043e (RTU500 series CMU), 13.5.1 (RTU500 series CMU)",
"\u0412\u043e\u0437\u043c\u043e\u0436\u043d\u044b\u0435 \u043c\u0435\u0440\u044b \u043f\u043e \u0443\u0441\u0442\u0440\u0430\u043d\u0435\u043d\u0438\u044e": "\u0418\u0441\u043f\u043e\u043b\u044c\u0437\u043e\u0432\u0430\u043d\u0438\u0435 \u0440\u0435\u043a\u043e\u043c\u0435\u043d\u0434\u0430\u0446\u0438\u0439:\nhttps://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true",
"\u0414\u0430\u0442\u0430 \u0432\u044b\u044f\u0432\u043b\u0435\u043d\u0438\u044f": "19.12.2023",
"\u0414\u0430\u0442\u0430 \u043f\u043e\u0441\u043b\u0435\u0434\u043d\u0435\u0433\u043e \u043e\u0431\u043d\u043e\u0432\u043b\u0435\u043d\u0438\u044f": "22.12.2023",
"\u0414\u0430\u0442\u0430 \u043f\u0443\u0431\u043b\u0438\u043a\u0430\u0446\u0438\u0438": "22.12.2023",
"\u0418\u0434\u0435\u043d\u0442\u0438\u0444\u0438\u043a\u0430\u0442\u043e\u0440": "BDU:2023-09002",
"\u0418\u0434\u0435\u043d\u0442\u0438\u0444\u0438\u043a\u0430\u0442\u043e\u0440\u044b \u0434\u0440\u0443\u0433\u0438\u0445 \u0441\u0438\u0441\u0442\u0435\u043c \u043e\u043f\u0438\u0441\u0430\u043d\u0438\u0439 \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438": "CVE-2023-6711",
"\u0418\u043d\u0444\u043e\u0440\u043c\u0430\u0446\u0438\u044f \u043e\u0431 \u0443\u0441\u0442\u0440\u0430\u043d\u0435\u043d\u0438\u0438": "\u0423\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u044c \u0443\u0441\u0442\u0440\u0430\u043d\u0435\u043d\u0430",
"\u041a\u043b\u0430\u0441\u0441 \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438": "\u0423\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u044c \u043a\u043e\u0434\u0430",
"\u041d\u0430\u0437\u0432\u0430\u043d\u0438\u0435 \u041f\u041e": "RTU500 series CMU",
"\u041d\u0430\u0438\u043c\u0435\u043d\u043e\u0432\u0430\u043d\u0438\u0435 \u041e\u0421 \u0438 \u0442\u0438\u043f \u0430\u043f\u043f\u0430\u0440\u0430\u0442\u043d\u043e\u0439 \u043f\u043b\u0430\u0442\u0444\u043e\u0440\u043c\u044b": null,
"\u041d\u0430\u0438\u043c\u0435\u043d\u043e\u0432\u0430\u043d\u0438\u0435 \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438": "\u0423\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u044c \u0438\u043d\u0442\u0435\u0440\u0444\u0435\u0439\u0441\u043e\u0432 HCI (Host Controller Interface) \u0438 SCI, \u0444\u0443\u043d\u043a\u0446\u0438\u043e\u043d\u0438\u0440\u0443\u044e\u0449\u0438\u0445 \u043f\u043e \u0441\u0442\u0430\u043d\u0434\u0430\u0440\u0442\u0443 IEC 60870-5-104, \u043f\u0440\u043e\u0433\u0440\u0430\u043c\u043c\u0438\u0440\u0443\u0435\u043c\u044b\u0445 \u043b\u043e\u0433\u0438\u0447\u0435\u0441\u043a\u0438\u0445 \u043a\u043e\u043d\u0442\u0440\u043e\u043b\u043b\u0435\u0440\u043e\u0432 Hitachi Energy RTU500 , \u043f\u043e\u0437\u0432\u043e\u043b\u044f\u044e\u0449\u0430\u044f \u043d\u0430\u0440\u0443\u0448\u0438\u0442\u0435\u043b\u044e \u0432\u044b\u0437\u0432\u0430\u0442\u044c \u043e\u0442\u043a\u0430\u0437 \u0432 \u043e\u0431\u0441\u043b\u0443\u0436\u0438\u0432\u0430\u043d\u0438\u0438",
"\u041d\u0430\u043b\u0438\u0447\u0438\u0435 \u044d\u043a\u0441\u043f\u043b\u043e\u0439\u0442\u0430": "\u0414\u0430\u043d\u043d\u044b\u0435 \u0443\u0442\u043e\u0447\u043d\u044f\u044e\u0442\u0441\u044f",
"\u041e\u043f\u0438\u0441\u0430\u043d\u0438\u0435 \u043e\u0448\u0438\u0431\u043a\u0438 CWE": "\u041d\u0435\u0434\u043e\u0441\u0442\u0430\u0442\u043e\u0447\u043d\u0430\u044f \u043f\u0440\u043e\u0432\u0435\u0440\u043a\u0430 \u0432\u0432\u043e\u0434\u0438\u043c\u044b\u0445 \u0434\u0430\u043d\u043d\u044b\u0445 (CWE-20)",
"\u041e\u043f\u0438\u0441\u0430\u043d\u0438\u0435 \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438": "\u0423\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u044c \u0438\u043d\u0442\u0435\u0440\u0444\u0435\u0439\u0441\u043e\u0432 HCI (Host Controller Interface) \u0438 SCI, \u0444\u0443\u043d\u043a\u0446\u0438\u043e\u043d\u0438\u0440\u0443\u044e\u0449\u0438\u0445 \u043f\u043e \u0441\u0442\u0430\u043d\u0434\u0430\u0440\u0442\u0443 IEC 60870-5-104, \u043f\u0440\u043e\u0433\u0440\u0430\u043c\u043c\u0438\u0440\u0443\u0435\u043c\u044b\u0445 \u043b\u043e\u0433\u0438\u0447\u0435\u0441\u043a\u0438\u0445 \u043a\u043e\u043d\u0442\u0440\u043e\u043b\u043b\u0435\u0440\u043e\u0432 Hitachi Energy RTU500 \u0441\u0432\u044f\u0437\u0430\u043d\u0430 \u0441 \u043d\u0435\u0434\u043e\u0441\u0442\u0430\u0442\u043e\u0447\u043d\u043e\u0439 \u043f\u0440\u043e\u0432\u0435\u0440\u043a\u043e\u0439 \u0432\u0445\u043e\u0434\u0435\u044b\u0445 \u0434\u0430\u043d\u043d\u044b\u0445. \u042d\u043a\u0441\u043f\u043b\u0443\u0430\u0442\u0430\u0446\u0438\u044f \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438 \u043c\u043e\u0436\u0435\u0442 \u043f\u043e\u0437\u0432\u043e\u043b\u0438\u0442\u044c \u043d\u0430\u0440\u0443\u0448\u0438\u0442\u0435\u043b\u044e, \u0434\u0435\u0439\u0441\u0442\u0432\u0443\u044e\u0449\u0435\u043c\u0443 \u0443\u0434\u0430\u043b\u0435\u043d\u043d\u043e, \u0432\u044b\u0437\u0432\u0430\u0442\u044c \u043e\u0442\u043a\u0430\u0437 \u0432 \u043e\u0431\u0441\u043b\u0443\u0436\u0438\u0432\u0430\u043d\u0438\u0438",
"\u041f\u043e\u0441\u043b\u0435\u0434\u0441\u0442\u0432\u0438\u044f \u044d\u043a\u0441\u043f\u043b\u0443\u0430\u0442\u0430\u0446\u0438\u0438 \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438": null,
"\u041f\u0440\u043e\u0447\u0430\u044f \u0438\u043d\u0444\u043e\u0440\u043c\u0430\u0446\u0438\u044f": null,
"\u0421\u0432\u044f\u0437\u044c \u0441 \u0438\u043d\u0446\u0438\u0434\u0435\u043d\u0442\u0430\u043c\u0438 \u0418\u0411": "\u0414\u0430\u043d\u043d\u044b\u0435 \u0443\u0442\u043e\u0447\u043d\u044f\u044e\u0442\u0441\u044f",
"\u0421\u043e\u0441\u0442\u043e\u044f\u043d\u0438\u0435 \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438": "\u041e\u043f\u0443\u0431\u043b\u0438\u043a\u043e\u0432\u0430\u043d\u0430",
"\u0421\u043f\u043e\u0441\u043e\u0431 \u0443\u0441\u0442\u0440\u0430\u043d\u0435\u043d\u0438\u044f": "\u041e\u0431\u043d\u043e\u0432\u043b\u0435\u043d\u0438\u0435 \u043f\u0440\u043e\u0433\u0440\u0430\u043c\u043c\u043d\u043e\u0433\u043e \u043e\u0431\u0435\u0441\u043f\u0435\u0447\u0435\u043d\u0438\u044f",
"\u0421\u043f\u043e\u0441\u043e\u0431 \u044d\u043a\u0441\u043f\u043b\u0443\u0430\u0442\u0430\u0446\u0438\u0438": "\u041c\u0430\u043d\u0438\u043f\u0443\u043b\u0438\u0440\u043e\u0432\u0430\u043d\u0438\u0435 \u0440\u0435\u0441\u0443\u0440\u0441\u0430\u043c\u0438",
"\u0421\u0441\u044b\u043b\u043a\u0438 \u043d\u0430 \u0438\u0441\u0442\u043e\u0447\u043d\u0438\u043a\u0438": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true\nhttps://vuldb.com/ru/?id.248412",
"\u0421\u0442\u0430\u0442\u0443\u0441 \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438": "\u041f\u043e\u0434\u0442\u0432\u0435\u0440\u0436\u0434\u0435\u043d\u0430 \u043f\u0440\u043e\u0438\u0437\u0432\u043e\u0434\u0438\u0442\u0435\u043b\u0435\u043c",
"\u0422\u0438\u043f \u041f\u041e": "\u0421\u0440\u0435\u0434\u0441\u0442\u0432\u043e \u0410\u0421\u0423 \u0422\u041f, \u041f\u041e \u043f\u0440\u043e\u0433\u0440\u0430\u043c\u043c\u043d\u043e-\u0430\u043f\u043f\u0430\u0440\u0430\u0442\u043d\u043e\u0433\u043e \u0441\u0440\u0435\u0434\u0441\u0442\u0432\u0430 \u0410\u0421\u0423 \u0422\u041f",
"\u0422\u0438\u043f \u043e\u0448\u0438\u0431\u043a\u0438 CWE": "CWE-20",
"\u0423\u0440\u043e\u0432\u0435\u043d\u044c \u043e\u043f\u0430\u0441\u043d\u043e\u0441\u0442\u0438 \u0443\u044f\u0437\u0432\u0438\u043c\u043e\u0441\u0442\u0438": "\u0421\u0440\u0435\u0434\u043d\u0438\u0439 \u0443\u0440\u043e\u0432\u0435\u043d\u044c \u043e\u043f\u0430\u0441\u043d\u043e\u0441\u0442\u0438 (\u0431\u0430\u0437\u043e\u0432\u0430\u044f \u043e\u0446\u0435\u043d\u043a\u0430 CVSS 2.0 \u0441\u043e\u0441\u0442\u0430\u0432\u043b\u044f\u0435\u0442 5,4)\n\u0421\u0440\u0435\u0434\u043d\u0438\u0439 \u0443\u0440\u043e\u0432\u0435\u043d\u044c \u043e\u043f\u0430\u0441\u043d\u043e\u0441\u0442\u0438 (\u0431\u0430\u0437\u043e\u0432\u0430\u044f \u043e\u0446\u0435\u043d\u043a\u0430 CVSS 3.0 \u0441\u043e\u0441\u0442\u0430\u0432\u043b\u044f\u0435\u0442 5,9)"
}
厂商已发布补丁修复漏洞,请广大用户及时下载更新: https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184&languageCode=en&Preview=true
| Name | ['Hitachi Energy RTU500 series CMU Firmware >=12.2.1,<=12.2.11', 'Hitachi Energy RTU500 series CMU Firmware >=12.4.1,<=12.4.11', 'Hitachi Energy RTU500 series CMU Firmware >=12.6.1,<=12.6.9', 'Hitachi Energy RTU500 series CMU Firmware >=12.7.1,<=12.7.6', 'Hitachi Energy RTU500 series CMU Firmware >=13.2.1,<=13.2.6', 'Hitachi Energy RTU500 series CMU Firmware >=12.0.1,<=12.0.14', 'Hitachi Energy RTU500 series CMU Firmware >=13.4.1,<=13.4.3', 'Hitachi Energy RTU500 series CMU Firmware 13.5.1'] |
|---|
{
"cves": {
"cve": {
"cveNumber": "CVE-2023-6711",
"cveUrl": "https://nvd.nist.gov/vuln/detail/CVE-2023-6711"
}
},
"description": "RTU500\u662f\u65e5\u672c\u65e5\u7acb\u5236\u4f5c\u6240\uff08Hitachi\uff09\u516c\u53f8\u7684\u4e00\u7cfb\u5217\u5de5\u63a7\u7ec4\u4ef6\uff0c\u4e3b\u8981\u7528\u4e8e\u5de5\u4e1a\u63a7\u5236\u7cfb\u7edf\u3002\n\nHitachi Energy RTU500 series CMU Firmware\u5b58\u5728\u8f93\u5165\u9a8c\u8bc1\u9519\u8bef\u6f0f\u6d1e\uff0c\u8be5\u6f0f\u6d1e\u6e90\u4e8e\u53d1\u9001\u5230\u7ec4\u4ef6\u7684\u7279\u5236\u6d88\u606f\u672a\u7ecf\u8fc7\u6b63\u786e\u9a8c\u8bc1\uff0c\u653b\u51fb\u8005\u53ef\u5229\u7528\u6f0f\u6d1e\u5bfc\u81f4\u7f13\u51b2\u533a\u6ea2\u51fa\uff0c\u5e76\u6700\u7ec8\u5bfc\u81f4RTU500 CMU\u91cd\u65b0\u542f\u52a8\u3002",
"formalWay": "\u5382\u5546\u5df2\u53d1\u5e03\u8865\u4e01\u4fee\u590d\u6f0f\u6d1e\uff0c\u8bf7\u5e7f\u5927\u7528\u6237\u53ca\u65f6\u4e0b\u8f7d\u66f4\u65b0\uff1a\r\nhttps://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true",
"isEvent": "\u901a\u7528\u8f6f\u786c\u4ef6\u6f0f\u6d1e",
"number": "CNVD-2025-02737",
"openTime": "2025-02-12",
"patchDescription": "RTU500\u662f\u65e5\u672c\u65e5\u7acb\u5236\u4f5c\u6240\uff08Hitachi\uff09\u516c\u53f8\u7684\u4e00\u7cfb\u5217\u5de5\u63a7\u7ec4\u4ef6\uff0c\u4e3b\u8981\u7528\u4e8e\u5de5\u4e1a\u63a7\u5236\u7cfb\u7edf\u3002\r\n\r\nHitachi Energy RTU500 series CMU Firmware\u5b58\u5728\u8f93\u5165\u9a8c\u8bc1\u9519\u8bef\u6f0f\u6d1e\uff0c\u8be5\u6f0f\u6d1e\u6e90\u4e8e\u53d1\u9001\u5230\u7ec4\u4ef6\u7684\u7279\u5236\u6d88\u606f\u672a\u7ecf\u8fc7\u6b63\u786e\u9a8c\u8bc1\uff0c\u653b\u51fb\u8005\u53ef\u5229\u7528\u6f0f\u6d1e\u5bfc\u81f4\u7f13\u51b2\u533a\u6ea2\u51fa\uff0c\u5e76\u6700\u7ec8\u5bfc\u81f4RTU500 CMU\u91cd\u65b0\u542f\u52a8\u3002\u76ee\u524d\uff0c\u4f9b\u5e94\u5546\u53d1\u5e03\u4e86\u5b89\u5168\u516c\u544a\u53ca\u76f8\u5173\u8865\u4e01\u4fe1\u606f\uff0c\u4fee\u590d\u4e86\u6b64\u6f0f\u6d1e\u3002",
"patchName": "Hitachi Energy RTU500 series CMU Firmware\u8f93\u5165\u9a8c\u8bc1\u9519\u8bef\u6f0f\u6d1e\u7684\u8865\u4e01",
"products": {
"product": [
"Hitachi Energy RTU500 series CMU Firmware \u003e=12.2.1\uff0c\u003c=12.2.11",
"Hitachi Energy RTU500 series CMU Firmware \u003e=12.4.1\uff0c\u003c=12.4.11",
"Hitachi Energy RTU500 series CMU Firmware \u003e=12.6.1\uff0c\u003c=12.6.9",
"Hitachi Energy RTU500 series CMU Firmware \u003e=12.7.1\uff0c\u003c=12.7.6",
"Hitachi Energy RTU500 series CMU Firmware \u003e=13.2.1\uff0c\u003c=13.2.6",
"Hitachi Energy RTU500 series CMU Firmware \u003e=12.0.1\uff0c\u003c=12.0.14",
"Hitachi Energy RTU500 series CMU Firmware \u003e=13.4.1\uff0c\u003c=13.4.3",
"Hitachi Energy RTU500 series CMU Firmware 13.5.1"
]
},
"referenceLink": "https://cxsecurity.com/cveshow/CVE-2023-6711/",
"serverity": "\u4f4e",
"submitTime": "2023-12-21",
"title": "Hitachi Energy RTU500 series CMU Firmware\u8f93\u5165\u9a8c\u8bc1\u9519\u8bef\u6f0f\u6d1e"
}
FKIE_CVE-2023-6711
Vulnerability from fkie_nvd - Published: 2023-12-19 15:15 - Updated: 2026-06-17 06:517.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
| Vendor | Product | Version | |
|---|---|---|---|
| hitachienergy | rtu500_firmware | * | |
| hitachienergy | rtu500_firmware | * | |
| hitachienergy | rtu500_firmware | * | |
| hitachienergy | rtu500_firmware | * | |
| hitachienergy | rtu500_firmware | * | |
| hitachienergy | rtu500_firmware | * | |
| hitachienergy | rtu500_firmware | * | |
| hitachienergy | rtu500_firmware | 13.5.1.0 | |
| hitachienergy | rtu500 | - |
{
"affected": [
{
"affectedData": [
{
"defaultStatus": "unaffected",
"product": "RTU500 series CMU Firmware",
"vendor": "Hitachi Energy",
"versions": [
{
"lessThanOrEqual": "12.0.14",
"status": "affected",
"version": "12.0.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "12.2.11",
"status": "affected",
"version": "12.2.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "12.4.11",
"status": "affected",
"version": "12.4.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "12.6.9",
"status": "affected",
"version": "12.6.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "12.7.6",
"status": "affected",
"version": "12.7.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "13.2.6",
"status": "affected",
"version": "13.2.1",
"versionType": "custom"
},
{
"lessThanOrEqual": "13.4.3",
"status": "affected",
"version": "13.4.1",
"versionType": "custom"
},
{
"status": "affected",
"version": "13.5.1"
}
]
}
],
"source": "cybersecurity@hitachienergy.com"
}
],
"configurations": [
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "E50C1390-D171-43AA-91BB-BCE40AB8B4F5",
"versionEndExcluding": "12.0.15.0",
"versionStartIncluding": "12.0.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "99416778-6B10-4C85-BC6A-AA9D77707489",
"versionEndExcluding": "12.2.12.0",
"versionStartIncluding": "12.2.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "229DCAE7-8362-4C5F-B708-9B130123DAAC",
"versionEndExcluding": "12.4.12.0",
"versionStartIncluding": "12.4.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "6241D442-A026-4F8D-88CA-AF8A3AEB3F57",
"versionEndExcluding": "12.6.10.0",
"versionStartIncluding": "12.6.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "71BCAE0B-3CD2-495E-B44B-661656C4BD05",
"versionEndExcluding": "12.7.7.0",
"versionStartIncluding": "12.7.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "01D33538-A8C2-4FC3-84B3-5F43E7ABA6E8",
"versionEndExcluding": "13.2.7.0",
"versionStartIncluding": "13.2.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "6E7961A7-DA10-498D-B746-A35782A2C4DC",
"versionEndExcluding": "13.4.4.0",
"versionStartIncluding": "13.4.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:13.5.1.0:*:*:*:*:*:*:*",
"matchCriteriaId": "A3F2C69B-BDFA-42A2-B0DF-50D690CC5024",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*",
"matchCriteriaId": "DE94252D-03EE-451B-8322-B4DBC790C6E9",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
}
],
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU."
},
{
"lang": "es",
"value": "Existe una vulnerabilidad en SCI IEC 60870-5-104 y HCI IEC 60870-5-104 que afecta a las versiones de productos de RTU500 series que se enumeran a continuaci\u00f3n. Los mensajes especialmente manipulados enviados a los componentes mencionados no se validan correctamente y pueden provocar un desbordamiento de b\u00fafer y, como consecuencia final, un reinicio de una CMU RTU500."
}
],
"id": "CVE-2023-6711",
"lastModified": "2026-06-17T06:51:17.293",
"metrics": {
"cvssMetricV31": [
{
"cvssData": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 2.2,
"impactScore": 3.6,
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary"
},
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "nvd@nist.gov",
"type": "Primary"
}
]
},
"published": "2023-12-19T15:15:09.257",
"references": [
{
"source": "cybersecurity@hitachienergy.com",
"tags": [
"Vendor Advisory"
],
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Vendor Advisory"
],
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true"
}
],
"sourceIdentifier": "cybersecurity@hitachienergy.com",
"vulnStatus": "Modified",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-120"
}
],
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary"
},
{
"description": [
{
"lang": "en",
"value": "CWE-120"
}
],
"source": "nvd@nist.gov",
"type": "Primary"
}
]
}
GHSA-X25M-G22V-6HGF
Vulnerability from github – Published: 2023-12-19 15:30 – Updated: 2023-12-19 15:30Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU.
{
"affected": [],
"aliases": [
"CVE-2023-6711"
],
"database_specific": {
"cwe_ids": [
"CWE-120",
"CWE-20"
],
"github_reviewed": false,
"github_reviewed_at": null,
"nvd_published_at": "2023-12-19T15:15:09Z",
"severity": "MODERATE"
},
"details": "Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU.",
"id": "GHSA-x25m-g22v-6hgf",
"modified": "2023-12-19T15:30:30Z",
"published": "2023-12-19T15:30:30Z",
"references": [
{
"type": "ADVISORY",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2023-6711"
},
{
"type": "WEB",
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true"
}
],
"schema_version": "1.4.0",
"severity": [
{
"score": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
"type": "CVSS_V3"
}
]
}
GSD-2023-6711
Vulnerability from gsd - Updated: 2023-12-13 01:20{
"gsd": {
"metadata": {
"exploitCode": "unknown",
"remediation": "unknown",
"reportConfidence": "confirmed",
"type": "vulnerability"
},
"osvSchema": {
"aliases": [
"CVE-2023-6711"
],
"details": "Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU.",
"id": "GSD-2023-6711",
"modified": "2023-12-13T01:20:32.744486Z",
"schema_version": "1.4.0"
}
},
"namespaces": {
"cve.org": {
"CVE_data_meta": {
"ASSIGNER": "cybersecurity@hitachienergy.com",
"ID": "CVE-2023-6711",
"STATE": "PUBLIC"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "RTU500 series CMU Firmware",
"version": {
"version_data": [
{
"version_affected": "\u003c=",
"version_name": "12.0.1",
"version_value": "12.0.14"
},
{
"version_affected": "\u003c=",
"version_name": "12.2.1",
"version_value": "12.2.11"
},
{
"version_affected": "\u003c=",
"version_name": "12.4.1",
"version_value": "12.4.11"
},
{
"version_affected": "\u003c=",
"version_name": "12.6.1",
"version_value": "12.6.9"
},
{
"version_affected": "\u003c=",
"version_name": "12.7.1",
"version_value": "12.7.6"
},
{
"version_affected": "\u003c=",
"version_name": "13.2.1",
"version_value": "13.2.6"
},
{
"version_affected": "\u003c=",
"version_name": "13.4.1",
"version_value": "13.4.3"
},
{
"version_affected": "=",
"version_value": "13.5.1"
}
]
}
}
]
},
"vendor_name": "Hitachi Energy"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU."
}
]
},
"generator": {
"engine": "Vulnogram 0.1.0-dev"
},
"impact": {
"cvss": [
{
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"cweId": "CWE-20",
"lang": "eng",
"value": "CWE-20 Improper Input Validation"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true",
"refsource": "MISC",
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true"
}
]
},
"source": {
"discovery": "UNKNOWN"
}
},
"nvd.nist.gov": {
"cve": {
"configurations": [
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "E50C1390-D171-43AA-91BB-BCE40AB8B4F5",
"versionEndExcluding": "12.0.15.0",
"versionStartIncluding": "12.0.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "99416778-6B10-4C85-BC6A-AA9D77707489",
"versionEndExcluding": "12.2.12.0",
"versionStartIncluding": "12.2.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "229DCAE7-8362-4C5F-B708-9B130123DAAC",
"versionEndExcluding": "12.4.12.0",
"versionStartIncluding": "12.4.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "6241D442-A026-4F8D-88CA-AF8A3AEB3F57",
"versionEndExcluding": "12.6.10.0",
"versionStartIncluding": "12.6.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "71BCAE0B-3CD2-495E-B44B-661656C4BD05",
"versionEndExcluding": "12.7.7.0",
"versionStartIncluding": "12.7.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "01D33538-A8C2-4FC3-84B3-5F43E7ABA6E8",
"versionEndExcluding": "13.2.7.0",
"versionStartIncluding": "13.2.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "6E7961A7-DA10-498D-B746-A35782A2C4DC",
"versionEndExcluding": "13.4.4.0",
"versionStartIncluding": "13.4.1.0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:13.5.1.0:*:*:*:*:*:*:*",
"matchCriteriaId": "A3F2C69B-BDFA-42A2-B0DF-50D690CC5024",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*",
"matchCriteriaId": "DE94252D-03EE-451B-8322-B4DBC790C6E9",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
}
],
"descriptions": [
{
"lang": "en",
"value": "Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU."
},
{
"lang": "es",
"value": "Existe una vulnerabilidad en SCI IEC 60870-5-104 y HCI IEC 60870-5-104 que afecta a las versiones de productos de RTU500 series que se enumeran a continuaci\u00f3n. Los mensajes especialmente manipulados enviados a los componentes mencionados no se validan correctamente y pueden provocar un desbordamiento de b\u00fafer y, como consecuencia final, un reinicio de una CMU RTU500."
}
],
"id": "CVE-2023-6711",
"lastModified": "2023-12-28T19:03:00.580",
"metrics": {
"cvssMetricV31": [
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "nvd@nist.gov",
"type": "Primary"
},
{
"cvssData": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 2.2,
"impactScore": 3.6,
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary"
}
]
},
"published": "2023-12-19T15:15:09.257",
"references": [
{
"source": "cybersecurity@hitachienergy.com",
"tags": [
"Vendor Advisory"
],
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true"
}
],
"sourceIdentifier": "cybersecurity@hitachienergy.com",
"vulnStatus": "Analyzed",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-120"
}
],
"source": "nvd@nist.gov",
"type": "Primary"
},
{
"description": [
{
"lang": "en",
"value": "CWE-20"
}
],
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary"
}
]
}
}
}
}
ICSA-24-354-01
Vulnerability from csaf_cisa - Published: 2024-12-19 07:00 - Updated: 2024-12-19 07:00| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
Hitachi Energy RTU500 series CMU Firmware: >=12.0.1|<=12.0.14
Hitachi Energy / RTU500 series CMU Firmware
|
>=12.0.1|<=12.0.14 |
Mitigation
Vendor Fix
Mitigation
Mitigation
Mitigation
fix
Mitigation
fix
|
|
|
Hitachi Energy RTU500 series CMU Firmware: >=12.2.1|<=12.2.11
Hitachi Energy / RTU500 series CMU Firmware
|
>=12.2.1|<=12.2.11 |
Mitigation
Vendor Fix
Mitigation
Mitigation
Mitigation
fix
Mitigation
fix
|
|
|
Hitachi Energy RTU500 series CMU Firmware: >=12.4.1|<=12.4.11
Hitachi Energy / RTU500 series CMU Firmware
|
>=12.4.1|<=12.4.11 |
Mitigation
Vendor Fix
Mitigation
Mitigation
Mitigation
fix
Mitigation
fix
|
|
|
Hitachi Energy RTU500 series CMU Firmware: >=12.6.1|<=12.6.9
Hitachi Energy / RTU500 series CMU Firmware
|
>=12.6.1|<=12.6.9 |
Mitigation
Vendor Fix
Mitigation
Mitigation
Mitigation
fix
Mitigation
fix
|
|
|
Hitachi Energy RTU500 series CMU Firmware: >=12.7.1|<=12.7.6
Hitachi Energy / RTU500 series CMU Firmware
|
>=12.7.1|<=12.7.6 |
Mitigation
Vendor Fix
Mitigation
Mitigation
Mitigation
fix
Mitigation
fix
|
|
|
Hitachi Energy RTU500 series CMU Firmware: >=13.2.1|<=13.2.6
Hitachi Energy / RTU500 series CMU Firmware
|
>=13.2.1|<=13.2.6 |
Mitigation
Vendor Fix
Mitigation
Mitigation
Mitigation
fix
Mitigation
fix
|
|
|
Hitachi Energy RTU500 series CMU Firmware: >=13.4.1|<=13.4.3
Hitachi Energy / RTU500 series CMU Firmware
|
>=13.4.1|<=13.4.3 |
Mitigation
Vendor Fix
Mitigation
Mitigation
Mitigation
fix
Mitigation
fix
|
|
|
Hitachi Energy RTU500 series CMU Firmware: 13.5.1
Hitachi Energy / RTU500 series CMU Firmware
|
13.5.1 |
Mitigation
Vendor Fix
Mitigation
Mitigation
Mitigation
fix
Mitigation
fix
|
{
"document": {
"acknowledgments": [
{
"names": [
"Toralf Gimpel"
],
"organization": "GAI NetConsult GmbH",
"summary": "reporting this vulnerability to Hitachi Energy"
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited",
"tlp": {
"label": "WHITE",
"url": "https://us-cert.cisa.gov/tlp/"
}
},
"lang": "en-US",
"notes": [
{
"category": "legal_disclaimer",
"text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
"title": "Legal Notice"
},
{
"category": "summary",
"text": "Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition.",
"title": "Risk evaluation"
},
{
"category": "other",
"text": "Energy",
"title": "Critical infrastructure sectors"
},
{
"category": "other",
"text": "Worldwide",
"title": "Countries/areas deployed"
},
{
"category": "other",
"text": "Switzerland",
"title": "Company headquarters location"
},
{
"category": "general",
"text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity.",
"title": "Recommended Practices"
}
],
"publisher": {
"category": "coordinator",
"contact_details": "central@cisa.dhs.gov",
"name": "CISA",
"namespace": "https://www.cisa.gov/"
},
"references": [
{
"category": "self",
"summary": "ICS Advisory ICSA-24-354-01 JSON",
"url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2024/icsa-24-354-01.json"
},
{
"category": "self",
"summary": "ICSA Advisory ICSA-24-354-01 - Web Version",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-354-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/topics/industrial-control-systems"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014"
}
],
"title": "Hitachi Energy RTU500 series CMU",
"tracking": {
"current_release_date": "2024-12-19T07:00:00.000000Z",
"generator": {
"engine": {
"name": "CISA CSAF Generator",
"version": "1.0.0"
}
},
"id": "ICSA-24-354-01",
"initial_release_date": "2024-12-19T07:00:00.000000Z",
"revision_history": [
{
"date": "2024-12-19T07:00:00.000000Z",
"legacy_version": "Initial",
"number": "1",
"summary": "Initial Publication"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e=12.0.1|\u003c=12.0.14",
"product": {
"name": "Hitachi Energy RTU500 series CMU Firmware: \u003e=12.0.1|\u003c=12.0.14",
"product_id": "CSAFPID-0001"
}
}
],
"category": "product_name",
"name": "RTU500 series CMU Firmware"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e=12.2.1|\u003c=12.2.11",
"product": {
"name": "Hitachi Energy RTU500 series CMU Firmware: \u003e=12.2.1|\u003c=12.2.11",
"product_id": "CSAFPID-0002"
}
}
],
"category": "product_name",
"name": "RTU500 series CMU Firmware"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e=12.4.1|\u003c=12.4.11",
"product": {
"name": "Hitachi Energy RTU500 series CMU Firmware: \u003e=12.4.1|\u003c=12.4.11",
"product_id": "CSAFPID-0003"
}
}
],
"category": "product_name",
"name": "RTU500 series CMU Firmware"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e=12.6.1|\u003c=12.6.9",
"product": {
"name": "Hitachi Energy RTU500 series CMU Firmware: \u003e=12.6.1|\u003c=12.6.9",
"product_id": "CSAFPID-0004"
}
}
],
"category": "product_name",
"name": "RTU500 series CMU Firmware"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e=12.7.1|\u003c=12.7.6",
"product": {
"name": "Hitachi Energy RTU500 series CMU Firmware: \u003e=12.7.1|\u003c=12.7.6",
"product_id": "CSAFPID-0005"
}
}
],
"category": "product_name",
"name": "RTU500 series CMU Firmware"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e=13.2.1|\u003c=13.2.6",
"product": {
"name": "Hitachi Energy RTU500 series CMU Firmware: \u003e=13.2.1|\u003c=13.2.6",
"product_id": "CSAFPID-0006"
}
}
],
"category": "product_name",
"name": "RTU500 series CMU Firmware"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e=13.4.1|\u003c=13.4.3",
"product": {
"name": "Hitachi Energy RTU500 series CMU Firmware: \u003e=13.4.1|\u003c=13.4.3",
"product_id": "CSAFPID-0007"
}
}
],
"category": "product_name",
"name": "RTU500 series CMU Firmware"
},
{
"branches": [
{
"category": "product_version",
"name": "13.5.1",
"product": {
"name": "Hitachi Energy RTU500 series CMU Firmware: 13.5.1",
"product_id": "CSAFPID-0008"
}
}
],
"category": "product_name",
"name": "RTU500 series CMU Firmware"
}
],
"category": "vendor",
"name": "Hitachi Energy"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2023-6711",
"cwe": {
"id": "CWE-120",
"name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
},
"notes": [
{
"category": "summary",
"text": "A vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU.",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006",
"CSAFPID-0007",
"CSAFPID-0008"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-6711"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Hitachi Energy recommends that users update to the respective series CMU firmware version as below.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006",
"CSAFPID-0007",
"CSAFPID-0008"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy RTU500 series CMU Firmware 12.0.15",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy RTU500 series CMU Firmware 12.2.12",
"product_ids": [
"CSAFPID-0002"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy RTU500 series CMU Firmware 12.4.12",
"product_ids": [
"CSAFPID-0003"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy RTU500 series CMU Firmware 12.6.10",
"product_ids": [
"CSAFPID-0004"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy RTU500 series CMU Firmware 12.7.7",
"product_ids": [
"CSAFPID-0005"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy RTU500 series CMU Firmware 13.2.7",
"product_ids": [
"CSAFPID-0006"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy RTU500 series CMU Firmware 13.4.4",
"product_ids": [
"CSAFPID-0007"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy RTU500 series CMU Firmware 13.5.2",
"product_ids": [
"CSAFPID-0008"
]
},
{
"category": "mitigation",
"details": "Hitachi Energy recommends that customers follow the \"Remote Terminal Units Security Deployment Guideline\", as well as to apply mitigation as described below.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006",
"CSAFPID-0007",
"CSAFPID-0008"
]
},
{
"category": "mitigation",
"details": "Hitachi Energy recommends users use recommended security practices and firewall configurations to help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006",
"CSAFPID-0007",
"CSAFPID-0008"
]
},
{
"category": "mitigation",
"details": "For more information, see Hitachi Energy Cybersecurity Advisory \"DoS Vulnerability in Hitachi Energy\u0027s RTU500 series products\"",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006",
"CSAFPID-0007",
"CSAFPID-0008"
],
"url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000184\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
},
{
"category": "mitigation",
"details": "For additional information and support please contact your product provider or Hitachi Energy service organization. For contact information, see https://www.hitachienergy.com/contact-us/ for Hitachi Energy contact-centers.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006",
"CSAFPID-0007",
"CSAFPID-0008"
],
"url": "https://www.hitachienergy.com/contact-us/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006",
"CSAFPID-0007",
"CSAFPID-0008"
]
}
]
}
]
}
VAR-202312-1753
Vulnerability from variot - Updated: 2025-02-14 23:10Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU. Hitachi Energy of rtu500 Firmware has a classic buffer overflow vulnerability.Service operation interruption (DoS) It may be in a state. RTU500 is a series of industrial control components of Hitachi, Japan, mainly used in industrial control systems. Attackers can exploit the vulnerability to cause a buffer overflow and eventually cause the RTU500 CMU to restart
Show details on source website{
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/VARIoTentry#",
"affected_products": {
"@id": "https://www.variotdbs.pl/ref/affected_products"
},
"credits": {
"@id": "https://www.variotdbs.pl/ref/credits"
},
"cvss": {
"@id": "https://www.variotdbs.pl/ref/cvss/"
},
"description": {
"@id": "https://www.variotdbs.pl/ref/description/"
},
"exploit_availability": {
"@id": "https://www.variotdbs.pl/ref/exploit_availability/"
},
"external_ids": {
"@id": "https://www.variotdbs.pl/ref/external_ids/"
},
"iot": {
"@id": "https://www.variotdbs.pl/ref/iot/"
},
"iot_taxonomy": {
"@id": "https://www.variotdbs.pl/ref/iot_taxonomy/"
},
"patch": {
"@id": "https://www.variotdbs.pl/ref/patch/"
},
"problemtype_data": {
"@id": "https://www.variotdbs.pl/ref/problemtype_data/"
},
"references": {
"@id": "https://www.variotdbs.pl/ref/references/"
},
"sources": {
"@id": "https://www.variotdbs.pl/ref/sources/"
},
"sources_release_date": {
"@id": "https://www.variotdbs.pl/ref/sources_release_date/"
},
"sources_update_date": {
"@id": "https://www.variotdbs.pl/ref/sources_update_date/"
},
"threat_type": {
"@id": "https://www.variotdbs.pl/ref/threat_type/"
},
"title": {
"@id": "https://www.variotdbs.pl/ref/title/"
},
"type": {
"@id": "https://www.variotdbs.pl/ref/type/"
}
},
"@id": "https://www.variotdbs.pl/vuln/VAR-202312-1753",
"affected_products": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/affected_products#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
},
"@id": "https://www.variotdbs.pl/ref/sources"
}
},
"data": [
{
"model": "rtu500",
"scope": "lt",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.2.12.0"
},
{
"model": "rtu500",
"scope": "gte",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.6.1.0"
},
{
"model": "rtu500",
"scope": "lt",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "13.2.7.0"
},
{
"model": "rtu500",
"scope": "gte",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.2.1.0"
},
{
"model": "rtu500",
"scope": "lt",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.0.15.0"
},
{
"model": "rtu500",
"scope": "eq",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "13.5.1.0"
},
{
"model": "rtu500",
"scope": "lt",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "13.4.4.0"
},
{
"model": "rtu500",
"scope": "gte",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "13.2.1.0"
},
{
"model": "rtu500",
"scope": "gte",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.4.1.0"
},
{
"model": "rtu500",
"scope": "gte",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "13.4.1.0"
},
{
"model": "rtu500",
"scope": "gte",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.0.1.0"
},
{
"model": "rtu500",
"scope": "lt",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.7.7.0"
},
{
"model": "rtu500",
"scope": "gte",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.7.1.0"
},
{
"model": "rtu500",
"scope": "lt",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.4.12.0"
},
{
"model": "rtu500",
"scope": "lt",
"trust": 1.0,
"vendor": "hitachienergy",
"version": "12.6.10.0"
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": "rtu500 firmware 13.5.1.0"
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": "rtu500 firmware 12.0.1.0 that\u0027s all 12.0.15.0"
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": null
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": "rtu500 firmware 12.7.1.0 that\u0027s all 12.7.7.0"
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": "rtu500 firmware 12.6.1.0 that\u0027s all 12.6.10.0"
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": "rtu500 firmware 13.2.1.0 that\u0027s all 13.2.7.0"
},
{
"model": "rtu500",
"scope": null,
"trust": 0.8,
"vendor": "hitachi energy",
"version": null
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": "rtu500 firmware 13.4.1.0 that\u0027s all 13.4.4.0"
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": "rtu500 firmware 12.2.1.0 that\u0027s all 12.2.12.0"
},
{
"model": "rtu500",
"scope": "eq",
"trust": 0.8,
"vendor": "hitachi energy",
"version": "rtu500 firmware 12.4.1.0 that\u0027s all 12.4.12.0"
},
{
"model": "energy rtu500 series cmu",
"scope": "gte",
"trust": 0.6,
"vendor": "hitachi",
"version": "12.2.1,\u003c=12.2.11"
},
{
"model": "energy rtu500 series cmu",
"scope": "gte",
"trust": 0.6,
"vendor": "hitachi",
"version": "12.4.1,\u003c=12.4.11"
},
{
"model": "energy rtu500 series cmu",
"scope": "gte",
"trust": 0.6,
"vendor": "hitachi",
"version": "12.6.1,\u003c=12.6.9"
},
{
"model": "energy rtu500 series cmu",
"scope": "gte",
"trust": 0.6,
"vendor": "hitachi",
"version": "12.7.1,\u003c=12.7.6"
},
{
"model": "energy rtu500 series cmu",
"scope": "gte",
"trust": 0.6,
"vendor": "hitachi",
"version": "13.2.1,\u003c=13.2.6"
},
{
"model": "energy rtu500 series cmu",
"scope": "gte",
"trust": 0.6,
"vendor": "hitachi",
"version": "12.0.1,\u003c=12.0.14"
},
{
"model": "energy rtu500 series cmu",
"scope": "gte",
"trust": 0.6,
"vendor": "hitachi",
"version": "13.4.1,\u003c=13.4.3"
},
{
"model": "energy rtu500 series cmu",
"scope": "eq",
"trust": 0.6,
"vendor": "hitachi",
"version": "13.5.1"
}
],
"sources": [
{
"db": "CNVD",
"id": "CNVD-2025-02737"
},
{
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"db": "NVD",
"id": "CVE-2023-6711"
}
]
},
"cve": "CVE-2023-6711",
"cvss": {
"@context": {
"cvssV2": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/cvss/cvssV2#"
},
"@id": "https://www.variotdbs.pl/ref/cvss/cvssV2"
},
"cvssV3": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/cvss/cvssV3#"
},
"@id": "https://www.variotdbs.pl/ref/cvss/cvssV3/"
},
"severity": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/cvss/severity#"
},
"@id": "https://www.variotdbs.pl/ref/cvss/severity"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
},
"@id": "https://www.variotdbs.pl/ref/sources"
}
},
"data": [
{
"cvssV2": [
{
"accessComplexity": "HIGH",
"accessVector": "NETWORK",
"authentication": "NONE",
"author": "CNVD",
"availabilityImpact": "COMPLETE",
"baseScore": 5.4,
"confidentialityImpact": "NONE",
"exploitabilityScore": 4.9,
"id": "CNVD-2025-02737",
"impactScore": 6.9,
"integrityImpact": "NONE",
"severity": "MEDIUM",
"trust": 0.6,
"vectorString": "AV:N/AC:H/Au:N/C:N/I:N/A:C",
"version": "2.0"
}
],
"cvssV3": [
{
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"author": "nvd@nist.gov",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"exploitabilityScore": 3.9,
"id": "CVE-2023-6711",
"impactScore": 3.6,
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"trust": 1.0,
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
{
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"author": "cybersecurity@hitachienergy.com",
"availabilityImpact": "HIGH",
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"exploitabilityScore": 2.2,
"id": "CVE-2023-6711",
"impactScore": 3.6,
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"trust": 1.0,
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
{
"attackComplexity": "Low",
"attackVector": "Network",
"author": "NVD",
"availabilityImpact": "High",
"baseScore": 7.5,
"baseSeverity": "High",
"confidentialityImpact": "None",
"exploitabilityScore": null,
"id": "CVE-2023-6711",
"impactScore": null,
"integrityImpact": "None",
"privilegesRequired": "None",
"scope": "Unchanged",
"trust": 0.8,
"userInteraction": "None",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.0"
}
],
"severity": [
{
"author": "nvd@nist.gov",
"id": "CVE-2023-6711",
"trust": 1.0,
"value": "HIGH"
},
{
"author": "cybersecurity@hitachienergy.com",
"id": "CVE-2023-6711",
"trust": 1.0,
"value": "MEDIUM"
},
{
"author": "NVD",
"id": "CVE-2023-6711",
"trust": 0.8,
"value": "High"
},
{
"author": "CNVD",
"id": "CNVD-2025-02737",
"trust": 0.6,
"value": "MEDIUM"
}
]
}
],
"sources": [
{
"db": "CNVD",
"id": "CNVD-2025-02737"
},
{
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"db": "NVD",
"id": "CVE-2023-6711"
},
{
"db": "NVD",
"id": "CVE-2023-6711"
}
]
},
"description": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/description#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": "Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU. Hitachi Energy of rtu500 Firmware has a classic buffer overflow vulnerability.Service operation interruption (DoS) It may be in a state. RTU500 is a series of industrial control components of Hitachi, Japan, mainly used in industrial control systems. Attackers can exploit the vulnerability to cause a buffer overflow and eventually cause the RTU500 CMU to restart",
"sources": [
{
"db": "NVD",
"id": "CVE-2023-6711"
},
{
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"db": "CNVD",
"id": "CNVD-2025-02737"
}
],
"trust": 2.16
},
"external_ids": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/external_ids#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"db": "NVD",
"id": "CVE-2023-6711",
"trust": 3.2
},
{
"db": "JVN",
"id": "JVNVU98968158",
"trust": 0.8
},
{
"db": "ICS CERT",
"id": "ICSA-24-354-01",
"trust": 0.8
},
{
"db": "JVNDB",
"id": "JVNDB-2023-023919",
"trust": 0.8
},
{
"db": "CNVD",
"id": "CNVD-2025-02737",
"trust": 0.6
}
],
"sources": [
{
"db": "CNVD",
"id": "CNVD-2025-02737"
},
{
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"db": "NVD",
"id": "CVE-2023-6711"
}
]
},
"id": "VAR-202312-1753",
"iot": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/iot#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": true,
"sources": [
{
"db": "CNVD",
"id": "CNVD-2025-02737"
}
],
"trust": 0.06
},
"iot_taxonomy": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/iot_taxonomy#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"category": [
"ICS"
],
"sub_category": null,
"trust": 0.6
}
],
"sources": [
{
"db": "CNVD",
"id": "CNVD-2025-02737"
}
]
},
"last_update_date": "2025-02-14T23:10:23.887000Z",
"patch": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/patch#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"title": "Patch for Hitachi Energy RTU500 series CMU Firmware Input Validation Error Vulnerability",
"trust": 0.6,
"url": "https://www.cnvd.org.cn/patchInfo/show/654811"
}
],
"sources": [
{
"db": "CNVD",
"id": "CNVD-2025-02737"
}
]
},
"problemtype_data": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/problemtype_data#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"problemtype": "CWE-120",
"trust": 1.0
},
{
"problemtype": "Classic buffer overflow (CWE-120) [NVD evaluation ]",
"trust": 0.8
}
],
"sources": [
{
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"db": "NVD",
"id": "CVE-2023-6711"
}
]
},
"references": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/references#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"trust": 1.8,
"url": "https://publisher.hitachienergy.com/preview?documentid=8dbd000184\u0026languagecode=en\u0026preview=true"
},
{
"trust": 0.8,
"url": "https://jvn.jp/vu/jvnvu98968158/index.html"
},
{
"trust": 0.8,
"url": "https://nvd.nist.gov/vuln/detail/cve-2023-6711"
},
{
"trust": 0.8,
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-354-01"
},
{
"trust": 0.6,
"url": "https://cxsecurity.com/cveshow/cve-2023-6711/"
}
],
"sources": [
{
"db": "CNVD",
"id": "CNVD-2025-02737"
},
{
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"db": "NVD",
"id": "CVE-2023-6711"
}
]
},
"sources": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#",
"data": {
"@container": "@list"
}
},
"data": [
{
"db": "CNVD",
"id": "CNVD-2025-02737"
},
{
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"db": "NVD",
"id": "CVE-2023-6711"
}
]
},
"sources_release_date": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources_release_date#",
"data": {
"@container": "@list"
}
},
"data": [
{
"date": "2025-02-12T00:00:00",
"db": "CNVD",
"id": "CNVD-2025-02737"
},
{
"date": "2024-01-30T00:00:00",
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"date": "2023-12-19T15:15:09.257000",
"db": "NVD",
"id": "CVE-2023-6711"
}
]
},
"sources_update_date": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources_update_date#",
"data": {
"@container": "@list"
}
},
"data": [
{
"date": "2025-02-12T00:00:00",
"db": "CNVD",
"id": "CNVD-2025-02737"
},
{
"date": "2024-12-23T03:23:00",
"db": "JVNDB",
"id": "JVNDB-2023-023919"
},
{
"date": "2024-09-25T09:15:02.930000",
"db": "NVD",
"id": "CVE-2023-6711"
}
]
},
"title": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/title#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": "Hitachi\u00a0Energy\u00a0 of \u00a0rtu500\u00a0 Classic buffer overflow vulnerability in firmware",
"sources": [
{
"db": "JVNDB",
"id": "JVNDB-2023-023919"
}
],
"trust": 0.8
}
}
WID-SEC-W-2023-3187
Vulnerability from csaf_certbund - Published: 2023-12-19 23:00 - Updated: 2023-12-19 23:00Es existiert eine Schwachstelle in Hitachi Energy RTU500. Das Problem besteht in der Komponente "Scripting-Schnittstelle". Der Client validiert die Parameter des vorgelegten Zertifikats nicht ordnungsgemäß, so dass nicht überprüft werden kann, ob der Remote-Dienst vertrauenswürdig ist. Ein Angreifer kann diese Schwachstelle ausnutzen, um die Identität des Dienstes fälschen und in der Folge über die RTU500 Scripting-Schnittstelle initiierte Nachrichten abfangen.
Es existiert eine Schwachstelle in Hitachi Energy RTU500. Speziell gestaltete Nachrichten werden nicht sachgemäß validiert, was einen Pufferüberlauf und einen Neustart des Gerätes verursachen kann. Ein entfernter, anonymer Angreifer kann diese Schwachstelle ausnutzen, um einen Denial of Servie zu verursachen.
{
"document": {
"aggregate_severity": {
"text": "mittel"
},
"category": "csaf_base",
"csaf_version": "2.0",
"distribution": {
"tlp": {
"label": "WHITE",
"url": "https://www.first.org/tlp/"
}
},
"lang": "de-DE",
"notes": [
{
"category": "legal_disclaimer",
"text": "Das BSI ist als Anbieter f\u00fcr die eigenen, zur Nutzung bereitgestellten Inhalte nach den allgemeinen Gesetzen verantwortlich. Nutzerinnen und Nutzer sind jedoch daf\u00fcr verantwortlich, die Verwendung und/oder die Umsetzung der mit den Inhalten bereitgestellten Informationen sorgf\u00e4ltig im Einzelfall zu pr\u00fcfen."
},
{
"category": "description",
"text": "Die RTU500-Serie ist eine Produktfamilie von Remote Terminal Units, die Informationen aus dem physikalischen Stromnetz in ein SCADA-System bringt.",
"title": "Produktbeschreibung"
},
{
"category": "summary",
"text": "Ein entfernter, anonymer Angreifer kann mehrere Schwachstellen in Hitachi Energy RTU500 ausnutzen, um die Identit\u00e4t des Dienstes zu f\u00e4lschen oder einen Denial of Servie zu verursachen.",
"title": "Angriff"
},
{
"category": "general",
"text": "- Sonstiges",
"title": "Betroffene Betriebssysteme"
}
],
"publisher": {
"category": "other",
"contact_details": "csaf-provider@cert-bund.de",
"name": "Bundesamt f\u00fcr Sicherheit in der Informationstechnik",
"namespace": "https://www.bsi.bund.de"
},
"references": [
{
"category": "self",
"summary": "WID-SEC-W-2023-3187 - CSAF Version",
"url": "https://wid.cert-bund.de/.well-known/csaf/white/2023/wid-sec-w-2023-3187.json"
},
{
"category": "self",
"summary": "WID-SEC-2023-3187 - Portal Version",
"url": "https://wid.cert-bund.de/portal/wid/securityadvisory?name=WID-SEC-2023-3187"
},
{
"category": "external",
"summary": "Hitachi Cybersecurity Advisory vom 2023-12-19",
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000152\u0026languageCode=en\u0026Preview=true"
},
{
"category": "external",
"summary": "GitHub Advisory Database vom 2023-12-19",
"url": "https://github.com/advisories/GHSA-r8hg-9v6r-2mq2"
},
{
"category": "external",
"summary": "Hitachi Cybersecurity Advisory vom 2023-12-19",
"url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184\u0026languageCode=en\u0026Preview=true"
},
{
"category": "external",
"summary": "GitHub Advisory Database vom 2023-12-19",
"url": "https://github.com/advisories/GHSA-x25m-g22v-6hgf"
}
],
"source_lang": "en-US",
"title": "Hitachi Energy RTU500: Mehrere Schwachstellen",
"tracking": {
"current_release_date": "2023-12-19T23:00:00.000+00:00",
"generator": {
"date": "2024-08-15T18:03:01.382+00:00",
"engine": {
"name": "BSI-WID",
"version": "1.3.5"
}
},
"id": "WID-SEC-W-2023-3187",
"initial_release_date": "2023-12-19T23:00:00.000+00:00",
"revision_history": [
{
"date": "2023-12-19T23:00:00.000+00:00",
"number": "1",
"summary": "Initiale Fassung"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_name",
"name": "Hitachi Energy RTU500 \u003c 12.0.15",
"product": {
"name": "Hitachi Energy RTU500 \u003c 12.0.15",
"product_id": "T031450",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:12.0.15"
}
}
},
{
"category": "product_name",
"name": "Hitachi Energy RTU500 \u003c 12.2.12",
"product": {
"name": "Hitachi Energy RTU500 \u003c 12.2.12",
"product_id": "T031451",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:12.2.12"
}
}
},
{
"category": "product_name",
"name": "Hitachi Energy RTU500 \u003c 12.4.12",
"product": {
"name": "Hitachi Energy RTU500 \u003c 12.4.12",
"product_id": "T031452",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:12.4.12"
}
}
},
{
"category": "product_name",
"name": "Hitachi Energy RTU500 \u003c 12.6.10",
"product": {
"name": "Hitachi Energy RTU500 \u003c 12.6.10",
"product_id": "T031453",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:12.6.10"
}
}
},
{
"category": "product_name",
"name": "Hitachi Energy RTU500 \u003c 12.7.7",
"product": {
"name": "Hitachi Energy RTU500 \u003c 12.7.7",
"product_id": "T031454",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:12.7.7"
}
}
},
{
"category": "product_name",
"name": "Hitachi Energy RTU500 \u003c 13.2.7",
"product": {
"name": "Hitachi Energy RTU500 \u003c 13.2.7",
"product_id": "T031455",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:13.2.7"
}
}
},
{
"category": "product_name",
"name": "Hitachi Energy RTU500 \u003c 13.4.4",
"product": {
"name": "Hitachi Energy RTU500 \u003c 13.4.4",
"product_id": "T031457",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:13.4.4"
}
}
},
{
"category": "product_name",
"name": "Hitachi Energy RTU500 Scripting interface \u003c 1.2.1",
"product": {
"name": "Hitachi Energy RTU500 Scripting interface \u003c 1.2.1",
"product_id": "T031763",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:scripting_interface__1.2.1"
}
}
},
{
"category": "product_name",
"name": "Hitachi Energy RTU500 \u003c 13.5.2",
"product": {
"name": "Hitachi Energy RTU500 \u003c 13.5.2",
"product_id": "T031764",
"product_identification_helper": {
"cpe": "cpe:/h:abb:rtu500:13.5.2"
}
}
}
],
"category": "product_name",
"name": "RTU500"
}
],
"category": "vendor",
"name": "Hitachi Energy"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2023-1514",
"notes": [
{
"category": "description",
"text": "Es existiert eine Schwachstelle in Hitachi Energy RTU500. Das Problem besteht in der Komponente \"Scripting-Schnittstelle\". Der Client validiert die Parameter des vorgelegten Zertifikats nicht ordnungsgem\u00e4\u00df, so dass nicht \u00fcberpr\u00fcft werden kann, ob der Remote-Dienst vertrauensw\u00fcrdig ist. Ein Angreifer kann diese Schwachstelle ausnutzen, um die Identit\u00e4t des Dienstes f\u00e4lschen und in der Folge \u00fcber die RTU500 Scripting-Schnittstelle initiierte Nachrichten abfangen."
}
],
"release_date": "2023-12-19T23:00:00.000+00:00",
"title": "CVE-2023-1514"
},
{
"cve": "CVE-2023-6711",
"notes": [
{
"category": "description",
"text": "Es existiert eine Schwachstelle in Hitachi Energy RTU500. Speziell gestaltete Nachrichten werden nicht sachgem\u00e4\u00df validiert, was einen Puffer\u00fcberlauf und einen Neustart des Ger\u00e4tes verursachen kann. Ein entfernter, anonymer Angreifer kann diese Schwachstelle ausnutzen, um einen Denial of Servie zu verursachen."
}
],
"release_date": "2023-12-19T23:00:00.000+00:00",
"title": "CVE-2023-6711"
}
]
}
Sightings
| Author | Source | Type | Date | Other |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.