CVE-2024-6242 (GCVE-0-2024-6242)

Vulnerability from cvelistv5 – Published: 2024-08-01 15:15 – Updated: 2025-09-25 13:34
VLAI
Title
Rockwell Automation Chassis Restrictions Bypass Vulnerability in Select Logix Devices
Summary
A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis.
SSVC
Exploitation: none Automatable: no Technical Impact: total
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2025-09-25 13:34 UTC
CWE
  • CWE-420 - Unprotected Alternate Channel
Assigner
Rockwell CNA under the icscert root
CNA scorecard C 74/100 over 47 records in the last 180 days details
Date Public
2024-08-01 13:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-6242",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-09-25T13:34:35.364759Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-09-25T13:34:40.444Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "ControlLogix\u00ae 5580 (1756-L8z)",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "V28"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GuardLogix\u00ae 5580  (1756-L8zS)",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "V31"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "1756-EN4TR",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "V2"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "platforms": [
            "Series A/B/C"
          ],
          "product": "1756-EN2T",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v5.007(unsigned)/v5.027(signed)"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "platforms": [
            "Series A/B"
          ],
          "product": "1756-EN2F",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v5.007(unsigned)/v5.027(signed)"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "platforms": [
            "Series A/B"
          ],
          "product": "1756-EN2TR",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v5.007(unsigned)/v5.027(signed)"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "platforms": [
            "Series B"
          ],
          "product": "1756-EN3TR",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v5.007(unsigned)/v5.027(signed)"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "platforms": [
            "Series D"
          ],
          "product": "1756-EN2T",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "1756-EN2T/D: V10.006"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "1756-EN2F",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "1756-EN2F/C: V10.009"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "platforms": [
            "Series C"
          ],
          "product": "1756-EN2TR",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "1756-EN2TR/C: V10.007"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "platforms": [
            "Series B"
          ],
          "product": "1756-EN3TR",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "1756-EN3TR/B: V10.007"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "platforms": [
            "Series A"
          ],
          "product": "1756-EN2TP",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "1756-EN2TP/A: V10.020"
            }
          ]
        }
      ],
      "credits": [
        {
          "lang": "en",
          "type": "finder",
          "value": "Claroty reported this vulnerability."
        }
      ],
      "datePublic": "2024-08-01T13:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eA vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted\u00ae Slot feature in a ControlLogix\u00ae controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis. \u0026nbsp;\u003c/span\u003e"
            }
          ],
          "value": "A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted\u00ae Slot feature in a ControlLogix\u00ae controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis."
        }
      ],
      "impacts": [
        {
          "capecId": "CAPEC-216",
          "descriptions": [
            {
              "lang": "en",
              "value": "CAPEC-216 Communication Channel Manipulation"
            }
          ]
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "PRESENT",
            "attackVector": "NETWORK",
            "baseScore": 7.3,
            "baseSeverity": "HIGH",
            "privilegesRequired": "LOW",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "HIGH",
            "subConfidentialityImpact": "LOW",
            "subIntegrityImpact": "HIGH",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "LOW",
            "vulnIntegrityImpact": "HIGH",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-420",
              "description": "CWE-420: Unprotected Alternate Channel",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-08-01T15:15:32.220Z",
        "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "shortName": "Rockwell"
      },
      "references": [
        {
          "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1682.html"
        }
      ],
      "source": {
        "advisory": "SD1682",
        "discovery": "EXTERNAL"
      },
      "title": "Rockwell Automation Chassis Restrictions Bypass Vulnerability in Select Logix Devices",
      "workarounds": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cp\u003e\n\n\u003c/p\u003e\u003ctable\u003e\u003ctbody\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eAffected Product \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eFirst Known in Firmware Revision \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eCorrected in Firmware Revision \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eControlLogix\u00ae 5580 (1756-L8z) \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV28 \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV32.016, V33.015, V34.014, \u0026nbsp;\u003cbr\u003eV35.011 and later \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eGuardLogix\u00ae 5580 (1756-L8zS) \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV31 \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV32.016, V33.015, V34.014, \u0026nbsp;\u003cbr\u003eV35.011 and later \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e1756-EN4TR \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV2 \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV5.001 and later \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2T, Series A/B/C \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2F, Series A/B \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TR, Series A/B \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN3TR, Series B \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003ev5.007(unsigned)/v5.027(signed) \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eNo fix is available for Series A/B/C. Users can upgrade to Series D to remediate this vulnerability \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2T, Series D \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2F, Series C \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TR, Series C \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN3TR, Series B \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TP, Series A \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2T/D: V10.006 \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2F/C: V10.009 \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TR/C: V10.007 \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN3TR/B: V10.007 \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TP/A: V10.020 \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV12.001 and later \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003c/tbody\u003e\u003c/table\u003e\n\n\u003cbr\u003e\u003cp\u003e\u003c/p\u003e\u003cp\u003e\n\n\u003c/p\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eUsers using the affected firmware and who are not able to upgrade to one of the corrected versions are encouraged to apply the following mitigation and security best practices, where possible.\u202f\u003c/span\u003e\u202f\u0026nbsp;\u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003eLimit the allowed CIP commands on controllers by setting the mode switch to the RUN position. \u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\u003c/div\u003e\u003c/div\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\"\u003eSecurity Best Practices\u003c/a\u003e\u0026nbsp;\u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\u003c/div\u003e\u003c/div\u003e\u003cp\u003e\u003c/p\u003e"
            }
          ],
          "value": "Affected Product \n\n\n\n\n\nFirst Known in Firmware Revision \n\n\n\n\n\nCorrected in Firmware Revision \n\n\n\n\n\nControlLogix\u00ae 5580 (1756-L8z) \n\n\n\n\n\nV28 \n\n\n\n\n\nV32.016, V33.015, V34.014, \u00a0\nV35.011 and later \n\n\n\n\u00a0\n\n\n\n\n\nGuardLogix\u00ae 5580 (1756-L8zS) \n\n\n\n\n\nV31 \n\n\n\n\n\nV32.016, V33.015, V34.014, \u00a0\nV35.011 and later \n\n\n\n\n\n1756-EN4TR \n\n\n\n\n\nV2 \n\n\n\n\n\nV5.001 and later \n\n\n\n\n\n1756-EN2T, Series A/B/C \n\n\n\n1756-EN2F, Series A/B \n\n\n\n1756-EN2TR, Series A/B \n\n\n\n1756-EN3TR, Series B \n\n\n\n\n\nv5.007(unsigned)/v5.027(signed) \n\n\n\n\n\nNo fix is available for Series A/B/C. Users can upgrade to Series D to remediate this vulnerability \n\n\n\n\n\n1756-EN2T, Series D \n\n\n\n1756-EN2F, Series C \n\n\n\n1756-EN2TR, Series C \n\n\n\n1756-EN3TR, Series B \n\n\n\n1756-EN2TP, Series A \n\n\n\n\n\n1756-EN2T/D: V10.006 \n\n\n\n1756-EN2F/C: V10.009 \n\n\n\n1756-EN2TR/C: V10.007 \n\n\n\n1756-EN3TR/B: V10.007 \n\n\n\n1756-EN2TP/A: V10.020 \n\n\n\n\n\nV12.001 and later \n\n\n\n\n\n\n\n\n\n\n\n\n\n\nUsers using the affected firmware and who are not able to upgrade to one of the corrected versions are encouraged to apply the following mitigation and security best practices, where possible.\u202f\u202f\u00a0\n\n\n\n  *  Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position. \n\n\n\n\n\n\n\n\n  *   Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight"
        }
      ],
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
    "assignerShortName": "Rockwell",
    "cveId": "CVE-2024-6242",
    "datePublished": "2024-08-01T15:15:32.220Z",
    "dateReserved": "2024-06-21T12:21:00.689Z",
    "dateUpdated": "2025-09-25T13:34:40.444Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1",
  "vulnerability-lookup:meta": {
    "epss": {
      "cve": "CVE-2024-6242",
      "date": "2026-11-17",
      "epss": "0.111",
      "percentile": "0.96"
    },
    "nvd": {
      "cve": {
        "affected": [
          {
            "affectedData": [
              {
                "defaultStatus": "unaffected",
                "product": "ControlLogix\u00ae 5580 (1756-L8z)",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "V28"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "GuardLogix\u00ae 5580  (1756-L8zS)",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "V31"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "1756-EN4TR",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "V2"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "platforms": [
                  "Series A/B/C"
                ],
                "product": "1756-EN2T",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "v5.007(unsigned)/v5.027(signed)"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "platforms": [
                  "Series A/B"
                ],
                "product": "1756-EN2F",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "v5.007(unsigned)/v5.027(signed)"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "platforms": [
                  "Series A/B"
                ],
                "product": "1756-EN2TR",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "v5.007(unsigned)/v5.027(signed)"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "platforms": [
                  "Series B"
                ],
                "product": "1756-EN3TR",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "v5.007(unsigned)/v5.027(signed)"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "platforms": [
                  "Series D"
                ],
                "product": "1756-EN2T",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "1756-EN2T/D: V10.006"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "1756-EN2F",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "1756-EN2F/C: V10.009"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "platforms": [
                  "Series C"
                ],
                "product": "1756-EN2TR",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "1756-EN2TR/C: V10.007"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "platforms": [
                  "Series B"
                ],
                "product": "1756-EN3TR",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "1756-EN3TR/B: V10.007"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "platforms": [
                  "Series A"
                ],
                "product": "1756-EN2TP",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "1756-EN2TP/A: V10.020"
                  }
                ]
              }
            ],
            "source": "PSIRT@rockwellautomation.com"
          }
        ],
        "cveTags": [],
        "descriptions": [
          {
            "lang": "en",
            "value": "A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted\u00ae Slot feature in a ControlLogix\u00ae controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis."
          },
          {
            "lang": "es",
            "value": " Existe una vulnerabilidad en los productos afectados de Rockwell Automation que permite a un actor de amenazas eludir la funci\u00f3n Trusted\u00ae Slot en un controlador ControlLogix\u00ae. Si se explota en cualquier m\u00f3dulo afectado en un chasis 1756, un actor de amenazas podr\u00eda potencialmente ejecutar comandos CIP que modifiquen los proyectos de usuario y/o la configuraci\u00f3n del dispositivo en un controlador Logix en el chasis."
          }
        ],
        "id": "CVE-2024-6242",
        "lastModified": "2026-06-17T08:17:36.693",
        "metrics": {
          "cvssMetricV40": [
            {
              "cvssData": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "PRESENT",
                "attackVector": "NETWORK",
                "availabilityRequirement": "NOT_DEFINED",
                "baseScore": 7.3,
                "baseSeverity": "HIGH",
                "confidentialityRequirement": "NOT_DEFINED",
                "exploitMaturity": "NOT_DEFINED",
                "integrityRequirement": "NOT_DEFINED",
                "modifiedAttackComplexity": "NOT_DEFINED",
                "modifiedAttackRequirements": "NOT_DEFINED",
                "modifiedAttackVector": "NOT_DEFINED",
                "modifiedPrivilegesRequired": "NOT_DEFINED",
                "modifiedSubAvailabilityImpact": "NOT_DEFINED",
                "modifiedSubConfidentialityImpact": "NOT_DEFINED",
                "modifiedSubIntegrityImpact": "NOT_DEFINED",
                "modifiedUserInteraction": "NOT_DEFINED",
                "modifiedVulnAvailabilityImpact": "NOT_DEFINED",
                "modifiedVulnConfidentialityImpact": "NOT_DEFINED",
                "modifiedVulnIntegrityImpact": "NOT_DEFINED",
                "privilegesRequired": "LOW",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "HIGH",
                "subConfidentialityImpact": "LOW",
                "subIntegrityImpact": "HIGH",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "LOW",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "source": "PSIRT@rockwellautomation.com",
              "type": "Secondary"
            }
          ],
          "ssvcV203": [
            {
              "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "ssvcData": {
                "id": "CVE-2024-6242",
                "options": [
                  {
                    "exploitation": "none"
                  },
                  {
                    "automatable": "no"
                  },
                  {
                    "technicalImpact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-09-25T13:34:35.364759Z",
                "version": "2.0.3"
              }
            }
          ]
        },
        "published": "2024-08-01T16:15:07.013",
        "references": [
          {
            "source": "PSIRT@rockwellautomation.com",
            "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1682.html"
          }
        ],
        "sourceIdentifier": "PSIRT@rockwellautomation.com",
        "vulnStatus": "Deferred",
        "weaknesses": [
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-420"
              }
            ],
            "source": "PSIRT@rockwellautomation.com",
            "type": "Secondary"
          }
        ]
      }
    },
    "redhat_vex": {
      "current_release_date": "2025-05-28T20:24:42+00:00",
      "cve": "CVE-2024-6242",
      "id": "CVE-2024-6242",
      "initial_release_date": "2024-08-01T13:00:00+00:00",
      "product_status:known_not_affected": "1",
      "source": "Red Hat CSAF VEX",
      "status": "final",
      "title": "Rockwell Automation Chassis Restrictions Bypass Vulnerability in Select Logix Devices",
      "url": "https://security.access.redhat.com/data/csaf/v2/vex/2024/cve-2024-6242.json",
      "version": "3"
    },
    "vulnrichment": {
      "containers": {
        "adp": [
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-6242",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2025-09-25T13:34:35.364759Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-08-01T18:00:57.404Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "ControlLogix\u00ae 5580 (1756-L8z)",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "V28"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "GuardLogix\u00ae 5580  (1756-L8zS)",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "V31"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "1756-EN4TR",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "V2"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "platforms": [
                "Series A/B/C"
              ],
              "product": "1756-EN2T",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "v5.007(unsigned)/v5.027(signed)"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "platforms": [
                "Series A/B"
              ],
              "product": "1756-EN2F",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "v5.007(unsigned)/v5.027(signed)"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "platforms": [
                "Series A/B"
              ],
              "product": "1756-EN2TR",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "v5.007(unsigned)/v5.027(signed)"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "platforms": [
                "Series B"
              ],
              "product": "1756-EN3TR",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "v5.007(unsigned)/v5.027(signed)"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "platforms": [
                "Series D"
              ],
              "product": "1756-EN2T",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "1756-EN2T/D: V10.006"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "1756-EN2F",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "1756-EN2F/C: V10.009"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "platforms": [
                "Series C"
              ],
              "product": "1756-EN2TR",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "1756-EN2TR/C: V10.007"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "platforms": [
                "Series B"
              ],
              "product": "1756-EN3TR",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "1756-EN3TR/B: V10.007"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "platforms": [
                "Series A"
              ],
              "product": "1756-EN2TP",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "1756-EN2TP/A: V10.020"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "finder",
              "value": "Claroty reported this vulnerability."
            }
          ],
          "datePublic": "2024-08-01T13:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eA vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted\u00ae Slot feature in a ControlLogix\u00ae controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis. \u0026nbsp;\u003c/span\u003e"
                }
              ],
              "value": "A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted\u00ae Slot feature in a ControlLogix\u00ae controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-216",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-216 Communication Channel Manipulation"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "PRESENT",
                "attackVector": "NETWORK",
                "baseScore": 7.3,
                "baseSeverity": "HIGH",
                "privilegesRequired": "LOW",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "HIGH",
                "subConfidentialityImpact": "LOW",
                "subIntegrityImpact": "HIGH",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "LOW",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-420",
                  "description": "CWE-420: Unprotected Alternate Channel",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-08-01T15:15:32.220Z",
            "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
            "shortName": "Rockwell"
          },
          "references": [
            {
              "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1682.html"
            }
          ],
          "source": {
            "advisory": "SD1682",
            "discovery": "EXTERNAL"
          },
          "title": "Rockwell Automation Chassis Restrictions Bypass Vulnerability in Select Logix Devices",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cp\u003e\n\n\u003c/p\u003e\u003ctable\u003e\u003ctbody\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eAffected Product \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eFirst Known in Firmware Revision \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eCorrected in Firmware Revision \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eControlLogix\u00ae 5580 (1756-L8z) \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV28 \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV32.016, V33.015, V34.014, \u0026nbsp;\u003cbr\u003eV35.011 and later \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eGuardLogix\u00ae 5580 (1756-L8zS) \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV31 \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV32.016, V33.015, V34.014, \u0026nbsp;\u003cbr\u003eV35.011 and later \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e1756-EN4TR \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV2 \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV5.001 and later \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2T, Series A/B/C \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2F, Series A/B \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TR, Series A/B \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN3TR, Series B \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003ev5.007(unsigned)/v5.027(signed) \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eNo fix is available for Series A/B/C. Users can upgrade to Series D to remediate this vulnerability \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2T, Series D \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2F, Series C \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TR, Series C \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN3TR, Series B \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TP, Series A \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2T/D: V10.006 \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2F/C: V10.009 \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TR/C: V10.007 \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN3TR/B: V10.007 \u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cp\u003e1756-EN2TP/A: V10.020 \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003ctd\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003eV12.001 and later \u003c/p\u003e\u003c/div\u003e\u003c/div\u003e\u003c/td\u003e\u003c/tr\u003e\u003c/tbody\u003e\u003c/table\u003e\n\n\u003cbr\u003e\u003cp\u003e\u003c/p\u003e\u003cp\u003e\n\n\u003c/p\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cp\u003e\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eUsers using the affected firmware and who are not able to upgrade to one of the corrected versions are encouraged to apply the following mitigation and security best practices, where possible.\u202f\u003c/span\u003e\u202f\u0026nbsp;\u003c/p\u003e\u003c/div\u003e\u003cdiv\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003eLimit the allowed CIP commands on controllers by setting the mode switch to the RUN position. \u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\u003c/div\u003e\u003c/div\u003e\u003cdiv\u003e\u003cdiv\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\"\u003eSecurity Best Practices\u003c/a\u003e\u0026nbsp;\u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\u003c/div\u003e\u003c/div\u003e\u003cp\u003e\u003c/p\u003e"
                }
              ],
              "value": "Affected Product \n\n\n\n\n\nFirst Known in Firmware Revision \n\n\n\n\n\nCorrected in Firmware Revision \n\n\n\n\n\nControlLogix\u00ae 5580 (1756-L8z) \n\n\n\n\n\nV28 \n\n\n\n\n\nV32.016, V33.015, V34.014, \u00a0\nV35.011 and later \n\n\n\n\u00a0\n\n\n\n\n\nGuardLogix\u00ae 5580 (1756-L8zS) \n\n\n\n\n\nV31 \n\n\n\n\n\nV32.016, V33.015, V34.014, \u00a0\nV35.011 and later \n\n\n\n\n\n1756-EN4TR \n\n\n\n\n\nV2 \n\n\n\n\n\nV5.001 and later \n\n\n\n\n\n1756-EN2T, Series A/B/C \n\n\n\n1756-EN2F, Series A/B \n\n\n\n1756-EN2TR, Series A/B \n\n\n\n1756-EN3TR, Series B \n\n\n\n\n\nv5.007(unsigned)/v5.027(signed) \n\n\n\n\n\nNo fix is available for Series A/B/C. Users can upgrade to Series D to remediate this vulnerability \n\n\n\n\n\n1756-EN2T, Series D \n\n\n\n1756-EN2F, Series C \n\n\n\n1756-EN2TR, Series C \n\n\n\n1756-EN3TR, Series B \n\n\n\n1756-EN2TP, Series A \n\n\n\n\n\n1756-EN2T/D: V10.006 \n\n\n\n1756-EN2F/C: V10.009 \n\n\n\n1756-EN2TR/C: V10.007 \n\n\n\n1756-EN3TR/B: V10.007 \n\n\n\n1756-EN2TP/A: V10.020 \n\n\n\n\n\nV12.001 and later \n\n\n\n\n\n\n\n\n\n\n\n\n\n\nUsers using the affected firmware and who are not able to upgrade to one of the corrected versions are encouraged to apply the following mitigation and security best practices, where possible.\u202f\u202f\u00a0\n\n\n\n  *  Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position. \n\n\n\n\n\n\n\n\n  *   Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight"
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "assignerShortName": "Rockwell",
        "cveId": "CVE-2024-6242",
        "datePublished": "2024-08-01T15:15:32.220Z",
        "dateReserved": "2024-06-21T12:21:00.689Z",
        "dateUpdated": "2025-09-25T13:34:40.444Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }
  }
}


Workarounds

CNA · Rockwell
Affected Product First Known in Firmware Revision Corrected in Firmware Revision ControlLogix® 5580 (1756-L8z) V28 V32.016, V33.015, V34.014,   V35.011 and later   GuardLogix® 5580 (1756-L8zS) V31 V32.016, V33.015, V34.014,   V35.011 and later 1756-EN4TR V2 V5.001 and later 1756-EN2T, Series A/B/C 1756-EN2F, Series A/B 1756-EN2TR, Series A/B 1756-EN3TR, Series B v5.007(unsigned)/v5.027(signed) No fix is available for Series A/B/C. Users can upgrade to Series D to remediate this vulnerability 1756-EN2T, Series D 1756-EN2F, Series C 1756-EN2TR, Series C 1756-EN3TR, Series B 1756-EN2TP, Series A 1756-EN2T/D: V10.006 1756-EN2F/C: V10.009 1756-EN2TR/C: V10.007 1756-EN3TR/B: V10.007 1756-EN2TP/A: V10.020 V12.001 and later Users using the affected firmware and who are not able to upgrade to one of the corrected versions are encouraged to apply the following mitigation and security best practices, where possible.    * Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position. * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight

Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Drag nodes to arrange them. Double-click a related vulnerability to open it, or a source to visit its link. The Physics button on the left tunes the layout and the simulation; the legend at the bottom left hides or shows nodes by kind and by sighting type.

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Vulnerability timeline

Sightings and recorded dates, grouped by day · UTC

JSON
How durations are calculated

Following the VTEM framework (Black Hat USA 2015), time to patch starts when the vendor or a coordinator was informed, total time to patch at discovery, and disclosure to patch at public disclosure; vendor response time runs from the report to its acknowledgement. Time to exploit and time unpatched start at the earliest discovery or report, falling back to public disclosure. Unpatched time ends at the first recorded patch, or the calculation time when no patch is recorded. Exploitation to patch shows the interval between those two events; a published proof of concept is a public exploit, not exploitation.

Each result shows its source dates. A negative interval means the end event came first; when date-only inputs leave the order open, the result says so. Date-only inputs are approximate. The earliest evidence wins: KEV report dates and sightings are labelled as such. Records describing another vulnerability are listed but never calculated from, and a PoC alone does not establish exploitation. Missing patch evidence does not prove that no patch exists. Filters below change the event list only.

Events included in the timeline

Loading timeline…


    Loading…

    Loading…

    Loading…

    Related by attack behaviour

    Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.