CVE-2024-3493 (GCVE-0-2024-3493)

Vulnerability from cvelistv5 – Published: 2024-04-15 21:17 – Updated: 2024-08-12 15:16
VLAI
Title
Rockwell Automation ControlLogix and GaurdLogix Vulnerable to Major Nonrecoverable Fault Due to Invalid Header Value
Summary
A specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation's ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices.
SSVC
Exploitation: none Automatable: yes Technical Impact: partial
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2024-08-12 15:09 UTC
CWE
  • CWE-20 - Improper Input Validation
Assigner
Rockwell CNA under the icscert root
CNA scorecard C 74/100 over 47 records in the last 180 days details
Impacted products
Vendor Product Version CPE status
Rockwell Automation ControlLogix 5580 Affected: v35.011
guessed Create a notification for this product.
Rockwell Automation GuardLogix 5580 Affected: v35.011
guessed Create a notification for this product.
Rockwell Automation CompactLogix 5380 Affected: v5.001
guessed Create a notification for this product.
Rockwell Automation 1756-EN4TR Affected: v5.001
guessed Create a notification for this product.
rockwellautomation guardlogix_5580_firmware Affected: 35.011
    cpe:2.3:o:rockwellautomation:guardlogix_5580_firmware:35.011:*:*:*:*:*:*:*
Create a notification for this product.
rockwellautomation compactlogix_5380_firmware Affected: 35.011
    cpe:2.3:o:rockwellautomation:compactlogix_5380_firmware:5.001:*:*:*:*:*:*:*
Create a notification for this product.
rockwellautomation 1756-en4tr_firmware Affected: 5.001
    cpe:2.3:o:rockwellautomation:1756-en4tr_firmware:5.001:*:*:*:*:*:*:*
Create a notification for this product.
Date Public
2024-04-12 01:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-01T20:12:07.675Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html"
          }
        ],
        "title": "CVE Program Container"
      },
      {
        "affected": [
          {
            "cpes": [
              "cpe:2.3:o:rockwellautomation:guardlogix_5580_firmware:35.011:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "guardlogix_5580_firmware",
            "vendor": "rockwellautomation",
            "versions": [
              {
                "status": "affected",
                "version": "35.011"
              }
            ]
          },
          {
            "cpes": [
              "cpe:2.3:o:rockwellautomation:compactlogix_5380_firmware:5.001:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "compactlogix_5380_firmware",
            "vendor": "rockwellautomation",
            "versions": [
              {
                "status": "affected",
                "version": "35.011"
              }
            ]
          },
          {
            "cpes": [
              "cpe:2.3:o:rockwellautomation:1756-en4tr_firmware:5.001:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "1756-en4tr_firmware",
            "vendor": "rockwellautomation",
            "versions": [
              {
                "status": "affected",
                "version": "5.001"
              }
            ]
          },
          {
            "cpes": [
              "cpe:2.3:o:rockwellautomation:1756-en4tr_firmware:5.001:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "1756-en4tr_firmware",
            "vendor": "rockwellautomation",
            "versions": [
              {
                "status": "affected",
                "version": "5.001"
              }
            ]
          }
        ],
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-3493",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-08-12T15:09:28.736089Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-08-12T15:16:08.155Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "ControlLogix 5580",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v35.011"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GuardLogix 5580",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v35.011"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "CompactLogix 5380",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v5.001"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "1756-EN4TR",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v5.001"
            }
          ]
        }
      ],
      "datePublic": "2024-04-12T01:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\n\n\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eA specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation\u0027s ControlLogix 5580, Guard Logix\u0026nbsp;5580,\u0026nbsp;CompactLogix 5380,\u0026nbsp;and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices. \u003c/span\u003e\n\n"
            }
          ],
          "value": "\nA specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation\u0027s ControlLogix 5580, Guard Logix\u00a05580,\u00a0CompactLogix 5380,\u00a0and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices. \n\n"
        }
      ],
      "impacts": [
        {
          "capecId": "CAPEC-137",
          "descriptions": [
            {
              "lang": "en",
              "value": "CAPEC-137 Parameter Injection"
            }
          ]
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 8.6,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "CHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-20",
              "description": "CWE-20 Improper Input Validation",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-04-15T21:29:33.269Z",
        "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "shortName": "Rockwell"
      },
      "references": [
        {
          "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\n\n\u003cp\u003e\n\n\u003c/p\u003e\u003ctable\u003e\u003ctbody\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u003cbr\u003eAffected Product\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eFirst Known in Firmware Revision\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eCorrected in Firmware Revision\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eControlLogix\u00ae 5580\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.013, V36.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eGuardLogix 5580\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.013, V36.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eCompactLogix 5380\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.013, V36.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e1756-EN4TR\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV5.001\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV6.001\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003c/tbody\u003e\u003c/table\u003e\n\n\u003cbr\u003e\u003cbr\u003e\u003cp\u003e\u003c/p\u003e\u003cp\u003eUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.\u202f\u202f\u003c/p\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\"\u003eSecurity Best Practices\u003c/a\u003e\u0026nbsp;\u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\n\n\u003cbr\u003e"
            }
          ],
          "value": "\nAffected Product\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nFirst Known in Firmware Revision\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nCorrected in Firmware Revision\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nControlLogix\u00ae 5580\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nGuardLogix 5580\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nCompactLogix 5380\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n1756-EN4TR\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV5.001\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV6.001\n\n\u00a0\n\n\u00a0\n\nUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.\u202f\u202f\n\n  *   Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight \u00a0\n\n"
        }
      ],
      "source": {
        "discovery": "INTERNAL"
      },
      "title": "Rockwell Automation ControlLogix and GaurdLogix Vulnerable to Major Nonrecoverable Fault Due to Invalid Header Value",
      "x_generator": {
        "engine": "Vulnogram 0.1.0-dev"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
    "assignerShortName": "Rockwell",
    "cveId": "CVE-2024-3493",
    "datePublished": "2024-04-15T21:17:36.077Z",
    "dateReserved": "2024-04-08T21:46:38.867Z",
    "dateUpdated": "2024-08-12T15:16:08.155Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1",
  "vulnerability-lookup:meta": {
    "epss": {
      "cve": "CVE-2024-3493",
      "date": "2026-11-16",
      "epss": "0.00637",
      "percentile": "0.51135"
    },
    "nvd": {
      "cve": {
        "affected": [
          {
            "affectedData": [
              {
                "defaultStatus": "unaffected",
                "product": "ControlLogix 5580",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "v35.011"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "GuardLogix 5580",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "v35.011"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "CompactLogix 5380",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "v5.001"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "1756-EN4TR",
                "vendor": "Rockwell Automation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "v5.001"
                  }
                ]
              }
            ],
            "source": "PSIRT@rockwellautomation.com"
          },
          {
            "affectedData": [
              {
                "cpes": [
                  "cpe:2.3:o:rockwellautomation:guardlogix_5580_firmware:35.011:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "guardlogix_5580_firmware",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "35.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:o:rockwellautomation:compactlogix_5380_firmware:5.001:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "compactlogix_5380_firmware",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "35.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:o:rockwellautomation:1756-en4tr_firmware:5.001:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "1756-en4tr_firmware",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "5.001"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:o:rockwellautomation:1756-en4tr_firmware:5.001:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "1756-en4tr_firmware",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "5.001"
                  }
                ]
              }
            ],
            "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0"
          }
        ],
        "configurations": [
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:rockwellautomation:controllogix_5580_firmware:35.011:*:*:*:*:*:*:*",
                    "matchCriteriaId": "A29D3775-CAB3-45CF-96CE-71D0672C7E37",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:rockwellautomation:controllogix_5580:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "51BB883B-B863-4D57-B1C0-FC7B3EBD1EA0",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:rockwellautomation:guardlogix_5580_firmware:35.011:*:*:*:*:*:*:*",
                    "matchCriteriaId": "64CAC9B1-19E5-44BB-B814-DDA98B7290E4",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:rockwellautomation:guardlogix_5580:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "006B7683-9FDF-4748-BA28-2EA22613E092",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:rockwellautomation:compactlogix_5380_firmware:35.011:*:*:*:*:*:*:*",
                    "matchCriteriaId": "305CDBFF-404A-45F5-A391-1B18F446D1B8",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:rockwellautomation:compactlogix_5380:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "EDD040ED-B44C-47D0-B4D4-729C378C4F68",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:rockwellautomation:compact_guardlogix_5380_firmware:35.011:*:*:*:*:*:*:*",
                    "matchCriteriaId": "9232043F-8A87-446C-8B7E-F8E400AA6F68",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:rockwellautomation:compact_guardlogix_5380:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "62414E65-73C7-4172-B7BF-F40A66AFBB90",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:rockwellautomation:1756-en4tr_firmware:5.001:*:*:*:*:*:*:*",
                    "matchCriteriaId": "91162BBB-AD61-4191-B00A-FDE767268F13",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:rockwellautomation:1756-en4tr:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "898EE953-E0EF-4B52-8EA0-41AAD8B5CCF3",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:rockwellautomation:controllogix_5580_process_firmware:35.011:*:*:*:*:*:*:*",
                    "matchCriteriaId": "4A1541AE-A429-455E-94C4-3420183CE7CF",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:rockwellautomation:controllogix_5580_process:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "AFEDADD8-01DE-4AE5-A0D7-532347FA7DB2",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:rockwellautomation:compactlogix_5380_process_firmware:35.011:*:*:*:*:*:*:*",
                    "matchCriteriaId": "DF838222-B4B6-4A66-B3CE-55E643368754",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:rockwellautomation:compactlogix_5380_process:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "77BCC249-D601-4A82-9247-C0981BF990FC",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:rockwellautomation:compactlogix_5480_firmware:35.011:*:*:*:*:*:*:*",
                    "matchCriteriaId": "61F8EA3B-C51C-4CB1-9BB3-017577DC6684",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:rockwellautomation:compactlogix_5480:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "80F4F5BE-07DF-402A-BF98-34FBA6A11968",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          }
        ],
        "cveTags": [],
        "descriptions": [
          {
            "lang": "en",
            "value": "\nA specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation\u0027s ControlLogix 5580, Guard Logix\u00a05580,\u00a0CompactLogix 5380,\u00a0and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices. \n\n"
          },
          {
            "lang": "es",
            "value": "Un tipo de paquete fragmentado con formato incorrecto espec\u00edfico (los dispositivos que env\u00edan grandes cantidades de datos pueden generar paquetes fragmentados autom\u00e1ticamente) puede causar una falla mayor no recuperable (MNRF) en ControlLogix 5580, Guard Logix 5580, CompactLogix 5380 y 1756-EN4TR de Rockwell Automation. Si se explota, el producto afectado dejar\u00e1 de estar disponible y requerir\u00e1 un reinicio manual para recuperarlo. Adem\u00e1s, un MNRF podr\u00eda provocar una p\u00e9rdida de visi\u00f3n y/o control de los dispositivos conectados."
          }
        ],
        "id": "CVE-2024-3493",
        "lastModified": "2026-06-17T07:44:22.820",
        "metrics": {
          "cvssMetricV31": [
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 8.6,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "CHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H",
                "version": "3.1"
              },
              "exploitabilityScore": 3.9,
              "impactScore": 4.0,
              "source": "PSIRT@rockwellautomation.com",
              "type": "Secondary"
            },
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                "version": "3.1"
              },
              "exploitabilityScore": 3.9,
              "impactScore": 3.6,
              "source": "nvd@nist.gov",
              "type": "Primary"
            }
          ],
          "ssvcV203": [
            {
              "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "ssvcData": {
                "id": "CVE-2024-3493",
                "options": [
                  {
                    "exploitation": "none"
                  },
                  {
                    "automatable": "yes"
                  },
                  {
                    "technicalImpact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-08-12T15:09:28.736089Z",
                "version": "2.0.3"
              }
            }
          ]
        },
        "published": "2024-04-15T22:15:09.073",
        "references": [
          {
            "source": "PSIRT@rockwellautomation.com",
            "tags": [
              "Broken Link"
            ],
            "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html"
          },
          {
            "source": "af854a3a-2127-422b-91ae-364da2661108",
            "tags": [
              "Broken Link"
            ],
            "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html"
          }
        ],
        "sourceIdentifier": "PSIRT@rockwellautomation.com",
        "vulnStatus": "Analyzed",
        "weaknesses": [
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-20"
              }
            ],
            "source": "PSIRT@rockwellautomation.com",
            "type": "Secondary"
          },
          {
            "description": [
              {
                "lang": "en",
                "value": "NVD-CWE-noinfo"
              }
            ],
            "source": "nvd@nist.gov",
            "type": "Primary"
          }
        ]
      }
    },
    "redhat_vex": {
      "current_release_date": "2025-05-28T20:35:52+00:00",
      "cve": "CVE-2024-3493",
      "id": "CVE-2024-3493",
      "initial_release_date": "2024-04-12T01:00:00+00:00",
      "product_status:known_not_affected": "1",
      "source": "Red Hat CSAF VEX",
      "status": "final",
      "title": "Rockwell Automation ControlLogix and GaurdLogix Vulnerable to Major Nonrecoverable Fault Due to Invalid Header Value",
      "url": "https://security.access.redhat.com/data/csaf/v2/vex/2024/cve-2024-3493.json",
      "version": "3"
    },
    "vulnrichment": {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-01T20:12:07.675Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_transferred"
                ],
                "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:o:rockwellautomation:guardlogix_5580_firmware:35.011:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "guardlogix_5580_firmware",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "35.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:o:rockwellautomation:compactlogix_5380_firmware:5.001:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "compactlogix_5380_firmware",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "35.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:o:rockwellautomation:1756-en4tr_firmware:5.001:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "1756-en4tr_firmware",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "5.001"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:o:rockwellautomation:1756-en4tr_firmware:5.001:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "1756-en4tr_firmware",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "5.001"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-3493",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-08-12T15:09:28.736089Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-08-12T15:15:42.341Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "ControlLogix 5580",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "v35.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "GuardLogix 5580",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "v35.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "CompactLogix 5380",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "v5.001"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "1756-EN4TR",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "v5.001"
                }
              ]
            }
          ],
          "datePublic": "2024-04-12T01:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\n\n\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eA specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation\u0027s ControlLogix 5580, Guard Logix\u0026nbsp;5580,\u0026nbsp;CompactLogix 5380,\u0026nbsp;and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices. \u003c/span\u003e\n\n"
                }
              ],
              "value": "\nA specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation\u0027s ControlLogix 5580, Guard Logix\u00a05580,\u00a0CompactLogix 5380,\u00a0and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices. \n\n"
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-137",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-137 Parameter Injection"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 8.6,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "CHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-20",
                  "description": "CWE-20 Improper Input Validation",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-04-15T21:29:33.269Z",
            "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
            "shortName": "Rockwell"
          },
          "references": [
            {
              "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\n\n\u003cp\u003e\n\n\u003c/p\u003e\u003ctable\u003e\u003ctbody\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u003cbr\u003eAffected Product\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eFirst Known in Firmware Revision\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eCorrected in Firmware Revision\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eControlLogix\u00ae 5580\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.013, V36.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eGuardLogix 5580\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.013, V36.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eCompactLogix 5380\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV35.013, V36.011\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e1756-EN4TR\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV5.001\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003eV6.001\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003cp\u003e\u0026nbsp;\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003c/tbody\u003e\u003c/table\u003e\n\n\u003cbr\u003e\u003cbr\u003e\u003cp\u003e\u003c/p\u003e\u003cp\u003eUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.\u202f\u202f\u003c/p\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\"\u003eSecurity Best Practices\u003c/a\u003e\u0026nbsp;\u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\n\n\u003cbr\u003e"
                }
              ],
              "value": "\nAffected Product\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nFirst Known in Firmware Revision\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nCorrected in Firmware Revision\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nControlLogix\u00ae 5580\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nGuardLogix 5580\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nCompactLogix 5380\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n1756-EN4TR\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV5.001\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV6.001\n\n\u00a0\n\n\u00a0\n\nUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.\u202f\u202f\n\n  *   Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight \u00a0\n\n"
            }
          ],
          "source": {
            "discovery": "INTERNAL"
          },
          "title": "Rockwell Automation ControlLogix and GaurdLogix Vulnerable to Major Nonrecoverable Fault Due to Invalid Header Value",
          "x_generator": {
            "engine": "Vulnogram 0.1.0-dev"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "assignerShortName": "Rockwell",
        "cveId": "CVE-2024-3493",
        "datePublished": "2024-04-15T21:17:36.077Z",
        "dateReserved": "2024-04-08T21:46:38.867Z",
        "dateUpdated": "2024-08-12T15:16:08.155Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }
  }
}


Solutions

CNA · Rockwell
Affected Product         First Known in Firmware Revision         Corrected in Firmware Revision         ControlLogix® 5580         V35.011         V35.013, V36.011         GuardLogix 5580         V35.011         V35.013, V36.011         CompactLogix 5380         V35.011         V35.013, V36.011         1756-EN4TR         V5.001         V6.001     Users using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.   * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight

Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Drag nodes to arrange them. Double-click a related vulnerability to open it, or a source to visit its link. The Physics button on the left tunes the layout and the simulation; the legend at the bottom left hides or shows nodes by kind and by sighting type.

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Vulnerability timeline

Sightings and recorded dates, grouped by day · UTC

JSON
How durations are calculated

Following the VTEM framework (Black Hat USA 2015), time to patch starts when the vendor or a coordinator was informed, total time to patch at discovery, and disclosure to patch at public disclosure; vendor response time runs from the report to its acknowledgement. Time to exploit and time unpatched start at the earliest discovery or report, falling back to public disclosure. Unpatched time ends at the first recorded patch, or the calculation time when no patch is recorded. Exploitation to patch shows the interval between those two events; a published proof of concept is a public exploit, not exploitation.

Each result shows its source dates. A negative interval means the end event came first; when date-only inputs leave the order open, the result says so. Date-only inputs are approximate. The earliest evidence wins: KEV report dates and sightings are labelled as such. Records describing another vulnerability are listed but never calculated from, and a PoC alone does not establish exploitation. Missing patch evidence does not prove that no patch exists. Filters below change the event list only.

Events included in the timeline

Loading timeline…


    Loading…

    Loading…

    Loading…

    Related by attack behaviour

    Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.