Search

Find a vulnerability

Search criteria

    4 vulnerabilities found for dvp-12se by deltaww

    CVE-2026-12819 (GCVE-0-2026-12819)

    Vulnerability from nvd – Published: 2026-06-30 06:28 – Updated: 2026-06-30 12:50
    VLAI
    Title
    DVP-12SE Missing Authentication and Unauthorized Write access Vulnerability
    Summary
    Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-306 - Missing Authentication for Critical Function
    Assigner
    Impacted products
    Date Public
    2026-06-30 05:29
    Credits
    CISA Adm Bin Harbi (0xnoag) - Corvo Security
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2026-12819",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-30T12:50:51.923347Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-30T12:50:59.070Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "DVP-12SE",
              "vendor": "deltaww",
              "versions": [
                {
                  "status": "affected",
                  "version": "*"
                }
              ]
            }
          ],
          "cpeApplicability": [
            {
              "nodes": [
                {
                  "cpeMatch": [
                    {
                      "criteria": "cpe:2.3:a:deltaww:dvp-12se:*:*:*:*:*:*:*:*",
                      "vulnerable": true
                    }
                  ],
                  "negate": false,
                  "operator": "OR"
                }
              ],
              "operator": "OR"
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "coordinator",
              "value": "CISA"
            },
            {
              "lang": "en",
              "type": "reporter",
              "value": "Adm Bin Harbi (0xnoag) - Corvo Security"
            }
          ],
          "datePublic": "2026-06-30T05:29:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions."
                }
              ],
              "value": "Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-115",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-115: Authentication Bypass"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 9.3,
                "baseSeverity": "CRITICAL",
                "exploitMaturity": "NOT_DEFINED",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-306",
                  "description": "CWE-306 Missing Authentication for Critical Function",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2026-06-30T06:28:51.514Z",
            "orgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
            "shortName": "Deltaww"
          },
          "references": [
            {
              "url": "https://filecenter.deltaww.com/news/download/doc/Delta-PCSA-2026-00011_DVP12SE%20Multiple%20Vulnerabilities%20(CVE-2026-12818,%20CVE-2026-12819)_v1.0.pdf"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "DVP-12SE Missing Authentication and Unauthorized Write access Vulnerability",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Users are recommended to take the following mitigation measures:\n\u003cbr\u003e\u003cul\u003e\u003cli\u003eEnable the IP Filter feature: Configure and enable the PLC\u0027s built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\u003c/li\u003e\u003cli\u003eSet up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device\u0027s core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\u003c/li\u003e\u003cli\u003eImplement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.\u0026nbsp;\u003c/li\u003e\u003c/ul\u003e"
                }
              ],
              "value": "Users are recommended to take the following mitigation measures:\n\n  *  Enable the IP Filter feature: Configure and enable the PLC\u0027s built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\n  *  Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device\u0027s core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\n  *  Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel."
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 1.0.2"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
        "assignerShortName": "Deltaww",
        "cveId": "CVE-2026-12819",
        "datePublished": "2026-06-30T06:28:51.514Z",
        "dateReserved": "2026-06-21T10:18:28.804Z",
        "dateUpdated": "2026-06-30T12:50:59.070Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2026-12818 (GCVE-0-2026-12818)

    Vulnerability from nvd – Published: 2026-06-30 06:24 – Updated: 2026-06-30 12:55
    VLAI
    Title
    DVP-12SE Exposure of Sensitive Information Vulnerability
    Summary
    Delta Electronics DVP12SE PLCs are susceptible to a resource allocation vulnerability without limits or throttling (CWE-770) within their Modbus TCP service.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-770 - Allocation of resources without limits or throttling
    Assigner
    Impacted products
    Date Public
    2026-06-30 05:29
    Credits
    CISA Adm Bin Harbi (0xnoag) - Corvo Security
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2026-12818",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-30T12:54:54.979527Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-30T12:55:02.858Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "DVP-12SE",
              "vendor": "deltaww",
              "versions": [
                {
                  "status": "affected",
                  "version": "*"
                }
              ]
            }
          ],
          "cpeApplicability": [
            {
              "nodes": [
                {
                  "cpeMatch": [
                    {
                      "criteria": "cpe:2.3:a:deltaww:dvp-12se:*:*:*:*:*:*:*:*",
                      "vulnerable": true
                    }
                  ],
                  "negate": false,
                  "operator": "OR"
                }
              ],
              "operator": "OR"
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "coordinator",
              "value": "CISA"
            },
            {
              "lang": "en",
              "type": "reporter",
              "value": "Adm Bin Harbi (0xnoag) - Corvo Security"
            }
          ],
          "datePublic": "2026-06-30T05:29:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Delta Electronics DVP12SE PLCs are susceptible to a resource allocation vulnerability without limits or throttling (CWE-770) within their Modbus TCP service."
                }
              ],
              "value": "Delta Electronics DVP12SE PLCs are susceptible to a resource allocation vulnerability without limits or throttling (CWE-770) within their Modbus TCP service."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-125",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-125: Flooding"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 9.3,
                "baseSeverity": "CRITICAL",
                "exploitMaturity": "NOT_DEFINED",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-770",
                  "description": "CWE-770 Allocation of resources without limits or throttling",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2026-06-30T06:30:23.413Z",
            "orgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
            "shortName": "Deltaww"
          },
          "references": [
            {
              "url": "https://filecenter.deltaww.com/news/download/doc/Delta-PCSA-2026-00011_DVP12SE%20Multiple%20Vulnerabilities%20(CVE-2026-12818,%20CVE-2026-12819)_v1.0.pdf"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "DVP-12SE Exposure of Sensitive Information Vulnerability",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Users are recommended to take the following mitigation measures:\n\u003cbr\u003e\u003cul\u003e\u003cli\u003eEnable the IP Filter feature: Configure and enable the PLC\u0027s built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\u003c/li\u003e\u003cli\u003eSet up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device\u0027s core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\u003c/li\u003e\u003cli\u003eImplement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.\u0026nbsp;\u003c/li\u003e\u003c/ul\u003e"
                }
              ],
              "value": "Users are recommended to take the following mitigation measures:\n\n  *  Enable the IP Filter feature: Configure and enable the PLC\u0027s built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\n  *  Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device\u0027s core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\n  *  Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel."
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 1.0.2"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
        "assignerShortName": "Deltaww",
        "cveId": "CVE-2026-12818",
        "datePublished": "2026-06-30T06:24:11.495Z",
        "dateReserved": "2026-06-21T10:18:09.710Z",
        "dateUpdated": "2026-06-30T12:55:02.858Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2026-12819 (GCVE-0-2026-12819)

    Vulnerability from cvelistv5 – Published: 2026-06-30 06:28 – Updated: 2026-06-30 12:50
    VLAI
    Title
    DVP-12SE Missing Authentication and Unauthorized Write access Vulnerability
    Summary
    Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-306 - Missing Authentication for Critical Function
    Assigner
    Impacted products
    Date Public
    2026-06-30 05:29
    Credits
    CISA Adm Bin Harbi (0xnoag) - Corvo Security
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2026-12819",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-30T12:50:51.923347Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-30T12:50:59.070Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "DVP-12SE",
              "vendor": "deltaww",
              "versions": [
                {
                  "status": "affected",
                  "version": "*"
                }
              ]
            }
          ],
          "cpeApplicability": [
            {
              "nodes": [
                {
                  "cpeMatch": [
                    {
                      "criteria": "cpe:2.3:a:deltaww:dvp-12se:*:*:*:*:*:*:*:*",
                      "vulnerable": true
                    }
                  ],
                  "negate": false,
                  "operator": "OR"
                }
              ],
              "operator": "OR"
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "coordinator",
              "value": "CISA"
            },
            {
              "lang": "en",
              "type": "reporter",
              "value": "Adm Bin Harbi (0xnoag) - Corvo Security"
            }
          ],
          "datePublic": "2026-06-30T05:29:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions."
                }
              ],
              "value": "Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-115",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-115: Authentication Bypass"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 9.3,
                "baseSeverity": "CRITICAL",
                "exploitMaturity": "NOT_DEFINED",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-306",
                  "description": "CWE-306 Missing Authentication for Critical Function",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2026-06-30T06:28:51.514Z",
            "orgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
            "shortName": "Deltaww"
          },
          "references": [
            {
              "url": "https://filecenter.deltaww.com/news/download/doc/Delta-PCSA-2026-00011_DVP12SE%20Multiple%20Vulnerabilities%20(CVE-2026-12818,%20CVE-2026-12819)_v1.0.pdf"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "DVP-12SE Missing Authentication and Unauthorized Write access Vulnerability",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Users are recommended to take the following mitigation measures:\n\u003cbr\u003e\u003cul\u003e\u003cli\u003eEnable the IP Filter feature: Configure and enable the PLC\u0027s built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\u003c/li\u003e\u003cli\u003eSet up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device\u0027s core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\u003c/li\u003e\u003cli\u003eImplement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.\u0026nbsp;\u003c/li\u003e\u003c/ul\u003e"
                }
              ],
              "value": "Users are recommended to take the following mitigation measures:\n\n  *  Enable the IP Filter feature: Configure and enable the PLC\u0027s built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\n  *  Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device\u0027s core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\n  *  Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel."
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 1.0.2"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
        "assignerShortName": "Deltaww",
        "cveId": "CVE-2026-12819",
        "datePublished": "2026-06-30T06:28:51.514Z",
        "dateReserved": "2026-06-21T10:18:28.804Z",
        "dateUpdated": "2026-06-30T12:50:59.070Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2026-12818 (GCVE-0-2026-12818)

    Vulnerability from cvelistv5 – Published: 2026-06-30 06:24 – Updated: 2026-06-30 12:55
    VLAI
    Title
    DVP-12SE Exposure of Sensitive Information Vulnerability
    Summary
    Delta Electronics DVP12SE PLCs are susceptible to a resource allocation vulnerability without limits or throttling (CWE-770) within their Modbus TCP service.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-770 - Allocation of resources without limits or throttling
    Assigner
    Impacted products
    Date Public
    2026-06-30 05:29
    Credits
    CISA Adm Bin Harbi (0xnoag) - Corvo Security
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2026-12818",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-06-30T12:54:54.979527Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-06-30T12:55:02.858Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "DVP-12SE",
              "vendor": "deltaww",
              "versions": [
                {
                  "status": "affected",
                  "version": "*"
                }
              ]
            }
          ],
          "cpeApplicability": [
            {
              "nodes": [
                {
                  "cpeMatch": [
                    {
                      "criteria": "cpe:2.3:a:deltaww:dvp-12se:*:*:*:*:*:*:*:*",
                      "vulnerable": true
                    }
                  ],
                  "negate": false,
                  "operator": "OR"
                }
              ],
              "operator": "OR"
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "coordinator",
              "value": "CISA"
            },
            {
              "lang": "en",
              "type": "reporter",
              "value": "Adm Bin Harbi (0xnoag) - Corvo Security"
            }
          ],
          "datePublic": "2026-06-30T05:29:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Delta Electronics DVP12SE PLCs are susceptible to a resource allocation vulnerability without limits or throttling (CWE-770) within their Modbus TCP service."
                }
              ],
              "value": "Delta Electronics DVP12SE PLCs are susceptible to a resource allocation vulnerability without limits or throttling (CWE-770) within their Modbus TCP service."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-125",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-125: Flooding"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 9.3,
                "baseSeverity": "CRITICAL",
                "exploitMaturity": "NOT_DEFINED",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-770",
                  "description": "CWE-770 Allocation of resources without limits or throttling",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2026-06-30T06:30:23.413Z",
            "orgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
            "shortName": "Deltaww"
          },
          "references": [
            {
              "url": "https://filecenter.deltaww.com/news/download/doc/Delta-PCSA-2026-00011_DVP12SE%20Multiple%20Vulnerabilities%20(CVE-2026-12818,%20CVE-2026-12819)_v1.0.pdf"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "DVP-12SE Exposure of Sensitive Information Vulnerability",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "Users are recommended to take the following mitigation measures:\n\u003cbr\u003e\u003cul\u003e\u003cli\u003eEnable the IP Filter feature: Configure and enable the PLC\u0027s built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\u003c/li\u003e\u003cli\u003eSet up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device\u0027s core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\u003c/li\u003e\u003cli\u003eImplement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.\u0026nbsp;\u003c/li\u003e\u003c/ul\u003e"
                }
              ],
              "value": "Users are recommended to take the following mitigation measures:\n\n  *  Enable the IP Filter feature: Configure and enable the PLC\u0027s built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\n  *  Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device\u0027s core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\n  *  Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel."
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 1.0.2"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "759f5e80-c8e1-4224-bead-956d7b33c98b",
        "assignerShortName": "Deltaww",
        "cveId": "CVE-2026-12818",
        "datePublished": "2026-06-30T06:24:11.495Z",
        "dateReserved": "2026-06-21T10:18:09.710Z",
        "dateUpdated": "2026-06-30T12:55:02.858Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",