Search

Find a vulnerability

Search criteria

    2 vulnerabilities found for AK-SM8xxA by Danfoss

    CVE-2026-129713 (GCVE-0-2026-129713)

    Vulnerability from nvd – Published: 2026-11-20 10:49 – Updated: 2026-11-20 10:49
    VLAI
    Title
    Stack-based buffer overflow in Danfoss AK-SM8xxA unauthenticated CGI handler
    Summary
    A stack-based buffer overflow in an unauthenticated CGI handler of the Danfoss AK-SM 8xxA Series controller allows remote attackers to send specially crafted HTTP/S POST requests, leading to memory corruption, webserver restart and hypothetically potential arbitrary code execution with webserver privileges. Authentication is not required to exploit this vulnerability.
    CWE
    • CWE-121 - Stack-based buffer overflow
    Assigner
    Danfoss CNA under the icscert root
    CNA scorecard – unranked: 3 records in the last 180 days, 10 needed details
    Impacted products
    Vendor Product Version
    Danfoss AK-SM8xxA Affected: 0 , ≤ 5.4.0 (custom)
    Create a notification for this product.
    Show details on NVD website

    {
      "containers": {
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "AK-SM8xxA",
              "vendor": "Danfoss",
              "versions": [
                {
                  "lessThanOrEqual": "5.4.0",
                  "status": "affected",
                  "version": "0",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cp\u003eA stack-based buffer overflow in an unauthenticated CGI handler of the\nDanfoss AK-SM 8xxA Series controller allows remote attackers to send specially\ncrafted HTTP/S POST requests, leading to memory corruption, webserver restart\nand hypothetically potential arbitrary code execution with webserver privileges.\nAuthentication is not required to exploit this vulnerability.\u003c/p\u003e"
                }
              ],
              "value": "A stack-based buffer overflow in an unauthenticated CGI handler of the\nDanfoss AK-SM 8xxA Series controller allows remote attackers to send specially\ncrafted HTTP/S POST requests, leading to memory corruption, webserver restart\nand hypothetically potential arbitrary code execution with webserver privileges.\nAuthentication is not required to exploit this vulnerability."
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 9.3,
                "baseSeverity": "CRITICAL",
                "exploitMaturity": "NOT_DEFINED",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-121",
                  "description": "CWE-121 Stack-based buffer overflow",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2026-11-20T10:49:40.291Z",
            "orgId": "d7ff35af-cf88-454c-bab9-af60602f10f8",
            "shortName": "Danfoss"
          },
          "references": [
            {
              "url": "https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2026-12-01/"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cul\u003e\n \u003cli\u003eThis\n     vulnerability will be addressed in Danfoss AK-SM 8xxA Series upcoming software\n     version 5.5.x.\u003c/li\u003e\n \u003cli\u003eFurther, we will\n     remove the option that customers can disable the product Strict mode.\u003c/li\u003e\n\u003c/ul\u003e"
                }
              ],
              "value": "*  This\n     vulnerability will be addressed in Danfoss AK-SM 8xxA Series upcoming software\n     version 5.5.x.\n\n   *  Further, we will\n     remove the option that customers can disable the product Strict mode."
            }
          ],
          "source": {
            "discovery": "EXTERNAL"
          },
          "title": "Stack-based buffer overflow in Danfoss AK-SM8xxA unauthenticated CGI handler",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cul\u003e\n \u003cli\u003eFollow the\n     instructions provided in the product\u2019s manual, avoiding Internet exposure\n     of all units on public IP\u003c/li\u003e\n \u003cli\u003eMake sure remote\n     access to the units is possible only through a secure VPN or in general\n     over a protected network\u003c/li\u003e\n \u003cli\u003eConfigure the\n     units to Strict mode, which ensures higher security levels on the product\u003c/li\u003e\n \u003cli\u003eRecommend using strong passwords\u003c/li\u003e\n\u003c/ul\u003e"
                }
              ],
              "value": "*  Follow the\n     instructions provided in the product\u2019s manual, avoiding Internet exposure\n     of all units on public IP\n\n   *  Make sure remote\n     access to the units is possible only through a secure VPN or in general\n     over a protected network\n\n   *  Configure the\n     units to Strict mode, which ensures higher security levels on the product\n\n   *  Recommend using strong passwords"
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 1.0.5"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "d7ff35af-cf88-454c-bab9-af60602f10f8",
        "assignerShortName": "Danfoss",
        "cveId": "CVE-2026-129713",
        "datePublished": "2026-11-20T10:49:40.291Z",
        "dateReserved": "2026-11-16T09:00:14.479Z",
        "dateUpdated": "2026-11-20T10:49:40.291Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }

    CVE-2026-129713 (GCVE-0-2026-129713)

    Vulnerability from cvelistv5 – Published: 2026-11-20 10:49 – Updated: 2026-11-20 10:49
    VLAI
    Title
    Stack-based buffer overflow in Danfoss AK-SM8xxA unauthenticated CGI handler
    Summary
    A stack-based buffer overflow in an unauthenticated CGI handler of the Danfoss AK-SM 8xxA Series controller allows remote attackers to send specially crafted HTTP/S POST requests, leading to memory corruption, webserver restart and hypothetically potential arbitrary code execution with webserver privileges. Authentication is not required to exploit this vulnerability.
    CWE
    • CWE-121 - Stack-based buffer overflow
    Assigner
    Danfoss CNA under the icscert root
    CNA scorecard – unranked: 3 records in the last 180 days, 10 needed details
    Impacted products
    Vendor Product Version
    Danfoss AK-SM8xxA Affected: 0 , ≤ 5.4.0 (custom)
    Create a notification for this product.
    Show details on NVD website

    {
      "containers": {
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "AK-SM8xxA",
              "vendor": "Danfoss",
              "versions": [
                {
                  "lessThanOrEqual": "5.4.0",
                  "status": "affected",
                  "version": "0",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cp\u003eA stack-based buffer overflow in an unauthenticated CGI handler of the\nDanfoss AK-SM 8xxA Series controller allows remote attackers to send specially\ncrafted HTTP/S POST requests, leading to memory corruption, webserver restart\nand hypothetically potential arbitrary code execution with webserver privileges.\nAuthentication is not required to exploit this vulnerability.\u003c/p\u003e"
                }
              ],
              "value": "A stack-based buffer overflow in an unauthenticated CGI handler of the\nDanfoss AK-SM 8xxA Series controller allows remote attackers to send specially\ncrafted HTTP/S POST requests, leading to memory corruption, webserver restart\nand hypothetically potential arbitrary code execution with webserver privileges.\nAuthentication is not required to exploit this vulnerability."
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 9.3,
                "baseSeverity": "CRITICAL",
                "exploitMaturity": "NOT_DEFINED",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-121",
                  "description": "CWE-121 Stack-based buffer overflow",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2026-11-20T10:49:40.291Z",
            "orgId": "d7ff35af-cf88-454c-bab9-af60602f10f8",
            "shortName": "Danfoss"
          },
          "references": [
            {
              "url": "https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2026-12-01/"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cul\u003e\n \u003cli\u003eThis\n     vulnerability will be addressed in Danfoss AK-SM 8xxA Series upcoming software\n     version 5.5.x.\u003c/li\u003e\n \u003cli\u003eFurther, we will\n     remove the option that customers can disable the product Strict mode.\u003c/li\u003e\n\u003c/ul\u003e"
                }
              ],
              "value": "*  This\n     vulnerability will be addressed in Danfoss AK-SM 8xxA Series upcoming software\n     version 5.5.x.\n\n   *  Further, we will\n     remove the option that customers can disable the product Strict mode."
            }
          ],
          "source": {
            "discovery": "EXTERNAL"
          },
          "title": "Stack-based buffer overflow in Danfoss AK-SM8xxA unauthenticated CGI handler",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\u003cul\u003e\n \u003cli\u003eFollow the\n     instructions provided in the product\u2019s manual, avoiding Internet exposure\n     of all units on public IP\u003c/li\u003e\n \u003cli\u003eMake sure remote\n     access to the units is possible only through a secure VPN or in general\n     over a protected network\u003c/li\u003e\n \u003cli\u003eConfigure the\n     units to Strict mode, which ensures higher security levels on the product\u003c/li\u003e\n \u003cli\u003eRecommend using strong passwords\u003c/li\u003e\n\u003c/ul\u003e"
                }
              ],
              "value": "*  Follow the\n     instructions provided in the product\u2019s manual, avoiding Internet exposure\n     of all units on public IP\n\n   *  Make sure remote\n     access to the units is possible only through a secure VPN or in general\n     over a protected network\n\n   *  Configure the\n     units to Strict mode, which ensures higher security levels on the product\n\n   *  Recommend using strong passwords"
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 1.0.5"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "d7ff35af-cf88-454c-bab9-af60602f10f8",
        "assignerShortName": "Danfoss",
        "cveId": "CVE-2026-129713",
        "datePublished": "2026-11-20T10:49:40.291Z",
        "dateReserved": "2026-11-16T09:00:14.479Z",
        "dateUpdated": "2026-11-20T10:49:40.291Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }