FSA-202203

Vulnerability from csaf_festosecokg - Published: 2022-07-18 10:00 - Updated: 2025-07-10 10:00
Summary
Festo: Controller CECC-S,LK,D family firmware 2.4.2.0 - multiple vulnerabilities in CODESYS V3 runtime system
Notes
Summary: The Festo controller CECC product family in firmware version 2.4.2.0 is affected by multiple vulnerabilities in the CODESYS V3 runtime.
Impact: By using the listed vulnerabilities an unauthorized remote attacker may gain full access to the devices or make them unavailable.
Remediation: No fix planned. This issue will be handled with next hardware generation release.
General recommendations: Festo strongly recommends to minimize and protect network access to connected devices with state of the art techniques and processes. Festo also highly recommends to apply available firmware updates containing security related changes as soon as possible. For a secure operation follow the recommendations in the product manuals. Until Festo provides a firmware-update with CODESYS runtime patching the vulnerabilities general recommendation is to: 1. Do not use the Codesys Web server of the Web-visualization. 2. The access to a PLC with an active webserver should be restricted on network level to participants for whom it is strictly necessary. Also, the PLC should never be exposed to the internet. Assist IT staff to block access (from outside of company network or from outside of virtual network assigned to machines) to PLC through existing network equipment (routers, firewalls etc) by blocking specific ports and protocols (UDP, TCP). 3. PLC with WEB server active shall only include visualization screens in the application that are intended for being accessed by operators of the CODESYS WebVisu and the CODESYS Remote TargetVisu. 4. Activation of the Codesys device user management and visualization user management if Web visualization is used. - With the activation of the user management on the device any online service requires an appropriate authentication. It is highly recommended to setup at least one administrator user. Moreover, a set of users belonging to the appropriate groups allow maintaining leveled access rights. - Use the protection of the user management in the CODESYS visualization not only for the navigation elements but also for all elements that should be restricted to certain operators only. As part of a security strategy, Festo supports the CODESYS GmbH recommended following general defense measures to reduce the risk of exploits: - Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside - Use firewalls to protect and separate the control system network from other networks - Use VPN (Virtual Private Networks) tunnels if remote access is required - Activate and apply user management and password features - Use encrypted communication links - Limit the access to both development and control system by physical means, operating system features, etc. - Protect both development and control system by using up to date virus detecting solutions For more information and general recommendations for protecting machines and plants, see also the CODESYS Security Whitepaper: [https://customers.codesys.com/fileadmin/data/customers/security/CODESYS-Security-Whitepaper.pdf](https://customers.codesys.com/fileadmin/data/customers/security/CODESYS-Security-Whitepaper.pdf)
Disclaimer: Festo assumes no liability whatsoever for indirect, collateral, accidental or consequential losses that occur by the distribution and/or use of this document or any losses in connection with the distribution and/or use of this document. All information published in this document is provided free of charge and on good faith by Festo. Insofar as permissible by law, however, none of this information shall establish any warranty, guarantee, commitment, or liability on the part of Festo. Note: In no case does this information release the operator or responsible person from the obligation to check the effect on his system or installation before using the information and, in the event of negative consequences, not to use the information. In addition, the actual general terms, and conditions for delivery, payment and software use of Festo, available under http://www.festo.com and the special provisions for the use of Festo Security Advisory available at https://www.festo.com/psirt shall apply.

An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).

CWE-787 - Out-of-bounds Write
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

CODESYS Gateway 3 before 3.5.16.70 has a NULL pointer dereference that may result in a denial of service (DoS).

CWE-476 - NULL Pointer Dereference
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Attackers can send crafted communication packets to change the router's addressing scheme and may re-route, add, remove or change low level communication packages.

CWE-20 - Improper Input Validation
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

A remote, unauthenticated attacker can send a specific crafted HTTP or HTTPS requests causing a buffer over-read resulting in a crash of the webserver of the CODESYS Control runtime system.

CWE-126 - Buffer Over-read
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

An unauthenticated, remote attacker can disrupt existing communication channels between CODESYS products by guessing a valid channel ID and injecting packets. This results in the communication channel to be closed.

CWE-330 - Use of Insufficiently Random Values
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

A remote, authenticated attacker could utilize the control program of the CODESYS Control runtime system to use the vulnerability in order to read and modify the configuration file(s) of the affected products.

CWE-668 - Exposure of Resource to Wrong Sphere
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

An authenticated, remote attacker can gain access to a dereferenced pointer contained in a request. The accesses can subsequently lead to local overwriting of memory in the CmpTraceMgr, whereby the attacker can neither gain the values read internally nor control the values to be written. If invalid memory is accessed, this results in a crash.

CWE-822 - Untrusted Pointer Dereference
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

An authenticated remote attacker can cause a null pointer dereference in the CmpSettings component of the affected CODESYS products which leads to a crash.

CWE-476 - NULL Pointer Dereference
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

In CODESYS V3 web server before 3.5.17.10, files or directories are accessible to External Parties.

CWE-552 - Files or Directories Accessible to External Parties
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

CODESYS Control Runtime system before 3.5.17.10 has a Heap-based Buffer Overflow.

CWE-787 - Out-of-bounds Write
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

An issue was discovered in CODESYS Development System before 3.5.16.0. CODESYS WebVisu and CODESYS Remote TargetVisu are susceptible to privilege escalation.

No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

CODESYS V3 web server before 3.5.15.40, as used in CODESYS Control runtime systems, has a buffer overflow.

CWE-787 - Out-of-bounds Write
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

CODESYS Control runtime system before 3.5.16.10 allows Uncontrolled Memory Allocation.

CWE-401 - Missing Release of Memory after Effective Lifetime
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), an attacker can identify valid usernames.

CWE-668 - Exposure of Resource to Wrong Sphere
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.

CWE-327 - Use of a Broken or Risky Cryptographic Algorithm
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), a user's password may be changed by an attacker without knowledge of the current password.

CWE-640 - Weak Password Recovery Mechanism for Forgotten Password
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.

CWE-916 - Use of Password Hash With Insufficient Computational Effort
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.

In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.

CWE-476 - NULL Pointer Dereference
No Fix Planned No fix planned. This issue will be handled with next hardware generation release.
Acknowledgments

{
  "document": {
    "acknowledgments": [
      {
        "organization": "CERT@VDE",
        "summary": "coordination and support with this publication",
        "urls": [
          "https://certvde.com/"
        ]
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "tlp": {
        "label": "WHITE",
        "url": "https://www.first.org/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "summary",
        "text": "The Festo controller CECC product family in firmware version 2.4.2.0 is affected by multiple vulnerabilities in the\u00a0CODESYS V3 runtime.",
        "title": "Summary"
      },
      {
        "category": "description",
        "text": "By using the listed vulnerabilities an unauthorized remote attacker may gain full access to the devices or make them unavailable.",
        "title": "Impact"
      },
      {
        "category": "description",
        "text": "No fix planned. This issue will be handled with next hardware generation release.",
        "title": "Remediation"
      },
      {
        "category": "general",
        "text": "Festo strongly recommends to minimize and protect network access to connected devices with state of the art techniques and processes.  \nFesto also highly recommends to apply available firmware updates containing security related changes as soon as possible.  \nFor a secure operation follow the recommendations in the product manuals.  \nUntil Festo provides a firmware-update with CODESYS runtime patching the vulnerabilities general recommendation is to:\n\n1. Do not use the Codesys Web server of the Web-visualization.  \n2. The access to a PLC with an active webserver should be restricted on network level to participants for whom it is strictly necessary. Also, the PLC should never be exposed to the internet. Assist IT staff to block access (from outside of company network or from outside of virtual network assigned to machines) to PLC through existing network equipment (routers, firewalls etc) by blocking specific ports and protocols (UDP, TCP).  \n3. PLC with WEB server active shall only include visualization screens in the application that are intended for being accessed by operators of the CODESYS WebVisu and the CODESYS Remote TargetVisu.  \n4. Activation of the Codesys device user management and visualization user management if Web visualization is used.  \n   - With the activation of the user management on the device any online service requires an appropriate authentication. It is highly recommended to setup at least one administrator user. Moreover, a set of users belonging to the appropriate groups allow maintaining leveled access rights.  \n   - Use the protection of the user management in the CODESYS visualization not only for the navigation elements but also for all elements that should be restricted to certain operators only.\n\nAs part of a security strategy, Festo supports the CODESYS GmbH recommended following general defense measures to reduce the risk of exploits:\n\n- Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside  \n- Use firewalls to protect and separate the control system network from other networks - Use VPN (Virtual Private Networks) tunnels if remote access is required  \n- Activate and apply user management and password features  \n- Use encrypted communication links  \n- Limit the access to both development and control system by physical means, operating system features, etc.  \n- Protect both development and control system by using up to date virus detecting solutions  \n\nFor more information and general recommendations for protecting machines and plants, see also the CODESYS Security Whitepaper:  \n[https://customers.codesys.com/fileadmin/data/customers/security/CODESYS-Security-Whitepaper.pdf](https://customers.codesys.com/fileadmin/data/customers/security/CODESYS-Security-Whitepaper.pdf)",
        "title": "General recommendations"
      },
      {
        "category": "legal_disclaimer",
        "text": "Festo assumes no liability whatsoever for indirect, collateral, accidental or consequential losses that occur by the distribution and/or use of this document or any losses in connection with the distribution and/or use of this document. All information published in this document is provided free of charge and on good faith by Festo. Insofar as permissible by law, however, none of this information shall establish any warranty, guarantee, commitment, or liability on the part of Festo.\n\nNote: In no case does this information release the operator or responsible person from the obligation to check the effect on his system or installation before using the information and, in the event of negative consequences, not to use the information.\n\nIn addition, the actual general terms, and conditions for delivery, payment and software use of Festo, available under http://www.festo.com and the special provisions for the use of Festo Security Advisory available at https://www.festo.com/psirt shall apply.",
        "title": "Disclaimer"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "psirt@festo.com",
      "name": "Festo SE \u0026 Co. KG",
      "namespace": "https://festo.com"
    },
    "references": [
      {
        "category": "self",
        "summary": "FSA-202203: Festo: Controller CECC-S,LK,D family firmware 2.4.2.0 - multiple vulnerabilities in CODESYS V3 runtime system - HTML",
        "url": "https://certvde.com/en/advisories/VDE-2022-027/"
      },
      {
        "category": "self",
        "summary": "FSA-202203: Festo: Controller CECC-S,LK,D family firmware 2.4.2.0 - multiple vulnerabilities in CODESYS V3 runtime system - CSAF",
        "url": "https://festo.csaf-tp.certvde.com/.well-known/csaf/white/2022/fsa-202203.json"
      },
      {
        "category": "external",
        "summary": "For further security-related issues in Festo products please contact the Festo Product Security Incident Response Team (PSIRT)",
        "url": "https://festo.com/psirt"
      },
      {
        "category": "external",
        "summary": "CERT@VDE Security Advisories for Festo SE \u0026 Co. KG",
        "url": "https://certvde.com/en/advisories/vendor/festo/"
      }
    ],
    "title": "Festo: Controller CECC-S,LK,D family firmware 2.4.2.0 - multiple vulnerabilities in CODESYS V3 runtime system",
    "tracking": {
      "aliases": [
        "VDE-2022-027"
      ],
      "current_release_date": "2025-07-10T10:00:00.000Z",
      "generator": {
        "date": "2025-08-14T08:36:11.111Z",
        "engine": {
          "name": "Secvisogram",
          "version": "2.5.32"
        }
      },
      "id": "FSA-202203",
      "initial_release_date": "2022-07-18T10:00:00.000Z",
      "revision_history": [
        {
          "date": "2022-07-18T10:00:00.000Z",
          "number": "1.0.0",
          "summary": "Initial version."
        },
        {
          "date": "2024-01-11T10:00:00.000Z",
          "number": "1.0.1",
          "summary": "Adjust link to VDE Advisory, TLP and update some CVE information, where CVSS was not known before."
        },
        {
          "date": "2025-07-10T10:00:00.000Z",
          "number": "1.0.2",
          "summary": "Adjusted to VDE template. Changed document title from \u0027Festo Controller CECC-S,-LK,-D Family Firmware = 2.4.2.0 - Multiple Vulnerabilities in CODESYS V3 Runtime System\u0027 to\u0027 Festo: Controller CECC-S,LK,D family firmware 2.4.2.0 - multiple vulnerabilities in CODESYS V3 runtime system\u0027. Updated legal disclaimer to add references to special provisions."
        }
      ],
      "status": "final",
      "version": "1.0.2"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_name",
                "name": "Controller CECC-D",
                "product": {
                  "name": "Controller CECC-D",
                  "product_id": "CSAFPID-11001",
                  "product_identification_helper": {
                    "model_numbers": [
                      "CECC-D Rev4",
                      "CECC-D Rev5",
                      "CECC-D Rev6"
                    ],
                    "skus": [
                      "574415"
                    ],
                    "x_generic_uris": [
                      {
                        "namespace": "Festo:Partnumber",
                        "uri": "Festo:Partnumber:574415"
                      },
                      {
                        "namespace": "Festo:Ordercode",
                        "uri": "Festo:Ordercode:CECC-D"
                      }
                    ]
                  }
                }
              },
              {
                "category": "product_name",
                "name": "Controller CECC-LK",
                "product": {
                  "name": "Controller CECC-LK",
                  "product_id": "CSAFPID-11002",
                  "product_identification_helper": {
                    "model_numbers": [
                      "CECC-LK Rev4",
                      "CECC-LK Rev5",
                      "CECC-LK Rev6"
                    ],
                    "skus": [
                      "574418"
                    ],
                    "x_generic_uris": [
                      {
                        "namespace": "Festo:Partnumber",
                        "uri": "Festo:Partnumber:574418"
                      },
                      {
                        "namespace": "Festo:Ordercode",
                        "uri": "Festo:Ordercode:CECC-LK"
                      }
                    ]
                  }
                }
              },
              {
                "category": "product_name",
                "name": "Controller CECC-S",
                "product": {
                  "name": "Controller CECC-S",
                  "product_id": "CSAFPID-11003",
                  "product_identification_helper": {
                    "model_numbers": [
                      "CECC-S Rev4",
                      "CECC-S Rev5",
                      "CECC-S Rev6"
                    ],
                    "skus": [
                      "574416"
                    ],
                    "x_generic_uris": [
                      {
                        "namespace": "Festo:Partnumber",
                        "uri": "Festo:Partnumber:574416"
                      },
                      {
                        "namespace": "Festo:Ordercode",
                        "uri": "Festo:Ordercode:CECC-S"
                      }
                    ]
                  }
                }
              }
            ],
            "category": "product_family",
            "name": "Hardware"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "R07 (07.06.2021) = 2.4.2.0",
                "product": {
                  "name": "FESTO Firmware R07 (07.06.2021) = 2.4.2.0",
                  "product_id": "CSAFPID-21001"
                }
              }
            ],
            "category": "product_family",
            "name": "Firmware"
          }
        ],
        "category": "vendor",
        "name": "Festo"
      }
    ],
    "product_groups": [
      {
        "group_id": "CSAFGID-0001",
        "product_ids": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ],
        "summary": "Affected products."
      }
    ],
    "relationships": [
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "FESTO Firmware R07 (07.06.2021) = 2.4.2.0 installed on Controller CECC-D",
          "product_id": "CSAFPID-31001"
        },
        "product_reference": "CSAFPID-21001",
        "relates_to_product_reference": "CSAFPID-11001"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "FESTO Firmware R07 (07.06.2021) = 2.4.2.0 installed on Controller CECC-LK",
          "product_id": "CSAFPID-31002"
        },
        "product_reference": "CSAFPID-21001",
        "relates_to_product_reference": "CSAFPID-11002"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "FESTO Firmware R07 (07.06.2021) = 2.4.2.0 installed on Controller CECC-S",
          "product_id": "CSAFPID-31003"
        },
        "product_reference": "CSAFPID-21001",
        "relates_to_product_reference": "CSAFPID-11003"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2019-5105",
      "cwe": {
        "id": "CWE-787",
        "name": "Out-of-bounds Write"
      },
      "notes": [
        {
          "category": "description",
          "text": "An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2019-5105"
    },
    {
      "cve": "CVE-2021-29241",
      "cwe": {
        "id": "CWE-476",
        "name": "NULL Pointer Dereference"
      },
      "notes": [
        {
          "category": "description",
          "text": "CODESYS Gateway 3 before 3.5.16.70 has a NULL pointer dereference that may result in a denial of service (DoS).",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2021-29241"
    },
    {
      "cve": "CVE-2021-29242",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "description",
          "text": "CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Attackers can send crafted communication packets to change the router\u0027s addressing scheme and may re-route, add, remove or change low level communication packages.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "LOW",
            "baseScore": 7.3,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "LOW",
            "environmentalScore": 7.3,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "LOW",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.3,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2021-29242"
    },
    {
      "cve": "CVE-2022-22519",
      "cwe": {
        "id": "CWE-126",
        "name": "Buffer Over-read"
      },
      "notes": [
        {
          "category": "description",
          "text": "A remote, unauthenticated attacker can send a specific crafted HTTP or HTTPS requests causing a buffer over-read resulting in a crash of the webserver of the CODESYS Control runtime system.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2022-22519"
    },
    {
      "cve": "CVE-2022-22517",
      "cwe": {
        "id": "CWE-330",
        "name": "Use of Insufficiently Random Values"
      },
      "notes": [
        {
          "category": "description",
          "text": "An unauthenticated, remote attacker can disrupt existing communication channels between CODESYS products by guessing a valid channel ID and injecting packets. This results in the communication channel to be closed.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2022-22517"
    },
    {
      "cve": "CVE-2022-22515",
      "cwe": {
        "id": "CWE-668",
        "name": "Exposure of Resource to Wrong Sphere"
      },
      "notes": [
        {
          "category": "description",
          "text": "A remote, authenticated attacker could utilize the control program of the CODESYS Control runtime system to use the vulnerability in order to read and modify the configuration file(s) of the affected products.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 8.1,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 8.1,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "temporalScore": 8.1,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2022-22515"
    },
    {
      "cve": "CVE-2022-22514",
      "cwe": {
        "id": "CWE-822",
        "name": "Untrusted Pointer Dereference"
      },
      "notes": [
        {
          "category": "description",
          "text": "An authenticated, remote attacker can gain access to a dereferenced pointer contained in a request. The accesses can subsequently lead to local overwriting of memory in the CmpTraceMgr, whereby the attacker can neither gain the values read internally nor control the values to be written. If invalid memory is accessed, this results in a crash.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.1,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "LOW",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "temporalScore": 7.1,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2022-22514"
    },
    {
      "cve": "CVE-2022-22513",
      "cwe": {
        "id": "CWE-476",
        "name": "NULL Pointer Dereference"
      },
      "notes": [
        {
          "category": "description",
          "text": "An authenticated remote attacker can cause a null pointer dereference in the CmpSettings component of the affected CODESYS products which leads to a crash.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "environmentalScore": 6.5,
            "environmentalSeverity": "MEDIUM",
            "integrityImpact": "NONE",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "temporalScore": 6.5,
            "temporalSeverity": "MEDIUM",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2022-22513"
    },
    {
      "cve": "CVE-2021-36763",
      "cwe": {
        "id": "CWE-552",
        "name": "Files or Directories Accessible to External Parties"
      },
      "notes": [
        {
          "category": "description",
          "text": "In CODESYS V3 web server before 3.5.17.10, files or directories are accessible to External Parties.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2021-36763"
    },
    {
      "cve": "CVE-2021-33485",
      "cwe": {
        "id": "CWE-787",
        "name": "Out-of-bounds Write"
      },
      "notes": [
        {
          "category": "description",
          "text": "CODESYS Control Runtime system before 3.5.17.10 has a Heap-based Buffer Overflow.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 9.8,
            "environmentalSeverity": "CRITICAL",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 9.8,
            "temporalSeverity": "CRITICAL",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2021-33485"
    },
    {
      "cve": "CVE-2020-12068",
      "notes": [
        {
          "category": "description",
          "text": "An issue was discovered in CODESYS Development System before 3.5.16.0. CODESYS WebVisu and CODESYS Remote TargetVisu are susceptible to privilege escalation.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "LOW",
            "environmentalScore": 6.5,
            "environmentalSeverity": "MEDIUM",
            "integrityImpact": "LOW",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 6.5,
            "temporalSeverity": "MEDIUM",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2020-12068"
    },
    {
      "cve": "CVE-2020-10245",
      "cwe": {
        "id": "CWE-787",
        "name": "Out-of-bounds Write"
      },
      "notes": [
        {
          "category": "description",
          "text": "CODESYS V3 web server before 3.5.15.40, as used in CODESYS Control runtime systems, has a buffer overflow.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 9.8,
            "environmentalSeverity": "CRITICAL",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 9.8,
            "temporalSeverity": "CRITICAL",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2020-10245"
    },
    {
      "cve": "CVE-2020-15806",
      "cwe": {
        "id": "CWE-401",
        "name": "Missing Release of Memory after Effective Lifetime"
      },
      "notes": [
        {
          "category": "description",
          "text": "CODESYS Control runtime system before 3.5.16.10 allows Uncontrolled Memory Allocation.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2020-15806"
    },
    {
      "cve": "CVE-2019-9011",
      "cwe": {
        "id": "CWE-668",
        "name": "Exposure of Resource to Wrong Sphere"
      },
      "notes": [
        {
          "category": "description",
          "text": "In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), an attacker can identify valid usernames.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "LOW",
            "environmentalScore": 5.3,
            "environmentalSeverity": "MEDIUM",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 5.3,
            "temporalSeverity": "MEDIUM",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2019-9011"
    },
    {
      "cve": "CVE-2019-9013",
      "cwe": {
        "id": "CWE-327",
        "name": "Use of a Broken or Risky Cryptographic Algorithm"
      },
      "notes": [
        {
          "category": "description",
          "text": "An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "ADJACENT_NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 8.8,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 8.8,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 8.8,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2019-9013"
    },
    {
      "cve": "CVE-2020-12067",
      "cwe": {
        "id": "CWE-640",
        "name": "Weak Password Recovery Mechanism for Forgotten Password"
      },
      "notes": [
        {
          "category": "description",
          "text": "In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), a user\u0027s password may be changed by an attacker without knowledge of the current password.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2020-12067"
    },
    {
      "cve": "CVE-2020-12069",
      "cwe": {
        "id": "CWE-916",
        "name": "Use of Password Hash With Insufficient Computational Effort"
      },
      "notes": [
        {
          "category": "description",
          "text": "In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "HIGH",
            "baseScore": 7.8,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 7.8,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "temporalScore": 7.8,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2020-12069"
    },
    {
      "cve": "CVE-2021-36764",
      "cwe": {
        "id": "CWE-476",
        "name": "NULL Pointer Dereference"
      },
      "notes": [
        {
          "category": "description",
          "text": "In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.",
          "title": "Vulnerability Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003"
        ]
      },
      "remediations": [
        {
          "category": "no_fix_planned",
          "details": "No fix planned. This issue will be handled with next hardware generation release.",
          "group_ids": [
            "CSAFGID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003"
          ]
        }
      ],
      "title": "CVE-2021-36764"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…