3ADR011524

Vulnerability from csaf_abb - Published: 2026-02-24 00:30 - Updated: 2026-02-24 00:30
Summary
AC500 V3 Multiple vulnerabilities

Notes

Summary
ABB became aware of severe vulnerability in the products versions listed as affected in the advisory. An update is available that resolves these vulnerabilities. An attacker who successfully exploited these vulnerabilities could bypass the user management and read visualization files (CVE-2025-2595), read and write certificates and keys (CVE-2025-41659) or cause a denial-of-service (DoS) (CVE-2025-41691).
Support
For additional instructions and support please contact your local ABB service organization. For contact information, see www.abb.com/contactcenters. Information about ABB’s cyber security program and capabilities can be found at www.abb.com/cybersecurity.
Notice
The information in this document is subject to change without notice, and should not be construed as a commitment by ABB. ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if ABB or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from ABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners.
General security recommendations
For any installation of software-related ABB products we strongly recommend the following (non-exhaustive) list of cyber security practices: - Isolate special purpose networks (e.g. for automation systems) and remote devices behind fire-walls and separate them from any general-purpose network (e.g. office or home networks). - Install physical controls so no unauthorized personnel can access your devices, components, peripheral equipment, and networks. - Never connect programming software or computers containing programming software to any network other than the network for the devices that it is intended for. - Scan all data imported into your environment before use to detect potential malware infections. - Minimize network exposure for all applications and endpoints to ensure that they are not accessible from the Internet unless they are designed for such exposure and the intended use requires such. - Ensure all nodes are always up to date in terms of installed software, operating system, and firmware patches as well as anti-virus and firewall. - When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
Purpose
ABB has a rigorous internal cyber security continuous improvement process which involves regular testing with industry leading tools and periodic assessments to identify potential product issues. Occasionally an issue is determined to be a design or coding flaw with implications that may impact product cyber security. When a potential product vulnerability is identified or reported, ABB immediately initiates our vulnerability handling process. This entails validating if the issue is in fact a product issue, identifying root causes, determining what related products may be impacted, developing a remediation, and notifying end users and governmental organizations. The resulting Cyber Security Advisory intends to notify customers of the vulnerability and provide details on which products are impacted, how to mitigate the vulnerability or explain workarounds that minimize the potential risk as much as possible. The release of a Cyber Security Advisory should not be misconstrued as an affirmation or indication of an active threat or ongoing campaign targeting the products mentioned here. If ABB is aware of any specific threats, it will be clearly mentioned in the communication. The publication of this Cyber Security Advisory is an example of ABB’s commitment to the user community in support of this critical topic. Responsible disclosure is an important element in the chain of trust we work to maintain with our many customers. The release of an Advisory provides timely information which is essential to help ensure our customers are fully informed.
Frequently Asked Questions
What causes the vulnerability? - Refer to section “Vulnerability severity and details“. What is AC500 V3? - The AC500 V3 is a scalable range of Programmable Logic Controller (PLC). It provides solutions for small, medium and high-end applications. The AC500 V3 platform offers different performance levels and is the ideal choice for high availability, extreme environments, condition monitoring, motion control or safety solutions. It offers interoperability and compatibility in hardware and software from compact PLCs up to high end and safety PLCs. What might an attacker use the vulnerability to do? - An attacker who successfully exploited these vulnerabilities could bypass the user management and read visualization files (CVE-2025-2595), read and write certificates and keys (CVE-2025-41659) or cause a denial-of-service (DoS) (CVE-2025-41691). How could an attacker exploit the vulnerability? - Refer to section “Vulnerability severity and details“. Could the vulnerability be exploited remotely? - Yes, an attacker who has network access to an affected system node could exploit the vulnerabilities. Recommended practices include that process control systems are physically protected, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed. When this security advisory was issued, had this vulnerability been publicly disclosed? - Yes, the vulnerabilities have been publicly disclosed. When this security advisory was issued, had ABB received any reports that this vulnerability was being exploited? - No, ABB had not received any information indicating that this vulnerability had been exploited when this security advisory was originally issued.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en",
    "notes": [
      {
        "category": "summary",
        "text": "ABB became aware of severe vulnerability in the products versions listed as affected in the advisory. An update is available that resolves these vulnerabilities.\n\nAn attacker who successfully exploited these vulnerabilities could bypass the user management and read visualization files (CVE-2025-2595), read and write certificates and keys (CVE-2025-41659) or cause a denial-of-service (DoS) (CVE-2025-41691).",
        "title": "Summary"
      },
      {
        "category": "other",
        "text": "For additional instructions and support please contact your local ABB service organization. For contact information, see www.abb.com/contactcenters.\n\nInformation about ABB\u2019s cyber security program and capabilities can be found at www.abb.com/cybersecurity.",
        "title": "Support"
      },
      {
        "category": "legal_disclaimer",
        "text": "The information in this document is subject to change without notice, and should not be construed as a commitment by ABB.\n\nABB provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if ABB or its suppliers have been advised of the possibility of such damages.\n\nThis document and parts hereof must not be reproduced or copied without written permission from ABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose.\n\nAll rights to registrations and trademarks reside with their respective owners.\n",
        "title": "Notice"
      },
      {
        "category": "other",
        "text": "For any installation of software-related ABB products we strongly recommend the following (non-exhaustive) list of cyber security practices:\n\n- Isolate special purpose networks (e.g. for automation systems) and remote devices behind fire-walls and separate them from any general-purpose network (e.g. office or home networks).\n- Install physical controls so no unauthorized personnel can access your devices, components, peripheral equipment, and networks.\n- Never connect programming software or computers containing programming software to any network other than the network for the devices that it is intended for.\n- Scan all data imported into your environment before use to detect potential malware infections.\n- Minimize network exposure for all applications and endpoints to ensure that they are not accessible from the Internet unless they are designed for such exposure and the intended use requires such.\n- Ensure all nodes are always up to date in terms of installed software, operating system, and firmware patches as well as anti-virus and firewall.\n- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.",
        "title": "General security recommendations"
      },
      {
        "category": "other",
        "text": "ABB has a rigorous internal cyber security continuous improvement process which involves regular testing with industry leading tools and periodic assessments to identify potential product issues. Occasionally an issue is determined to be a design or coding flaw with implications that may impact product cyber security.\n\nWhen a potential product vulnerability is identified or reported, ABB immediately initiates our vulnerability handling process. This entails validating if the issue is in fact a product issue, identifying root causes, determining what related products may be impacted, developing a remediation, and notifying end users and governmental organizations.\n\nThe resulting Cyber Security Advisory intends to notify customers of the vulnerability and provide details on which products are impacted, how to mitigate the vulnerability or explain workarounds that minimize the potential risk as much as possible. The release of a Cyber Security Advisory should not be misconstrued as an affirmation or indication of an active threat or ongoing campaign targeting the products mentioned here. If ABB is aware of any specific threats, it will be clearly mentioned in the communication.\n\nThe publication of this Cyber Security Advisory is an example of ABB\u2019s commitment to the user community in support of this critical topic. Responsible disclosure is an important element in the chain of trust we work to maintain with our many customers. The release of an Advisory provides timely information which is essential to help ensure our customers are fully informed.",
        "title": "Purpose"
      },
      {
        "category": "faq",
        "text": "What causes the vulnerability?\n- Refer to section \u201cVulnerability severity and details\u201c.\n\nWhat is AC500 V3?\n- The AC500 V3 is a scalable range of Programmable Logic Controller (PLC). It provides solutions for small, medium and high-end applications. The AC500 V3 platform offers different performance levels and is the ideal choice for high availability, extreme environments, condition monitoring, motion control or safety solutions. It offers interoperability and compatibility in hardware and software from compact PLCs up to high end and safety PLCs.\n\nWhat might an attacker use the vulnerability to do?\n- An attacker who successfully exploited these vulnerabilities could bypass the user management and read visualization files (CVE-2025-2595), read and write certificates and keys (CVE-2025-41659) or cause a denial-of-service (DoS) (CVE-2025-41691).\n\nHow could an attacker exploit the vulnerability?\n- Refer to section \u201cVulnerability severity and details\u201c.\n\nCould the vulnerability be exploited remotely?\n- Yes, an attacker who has network access to an affected system node could exploit the vulnerabilities. Recommended practices include that process control systems are physically protected, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed.\n\nWhen this security advisory was issued, had this vulnerability been publicly disclosed?\n- Yes, the vulnerabilities have been publicly disclosed.\n\nWhen this security advisory was issued, had ABB received any reports that this vulnerability was being exploited?\n- No, ABB had not received any information indicating that this vulnerability had been exploited when this security advisory was originally issued.",
        "title": "Frequently Asked Questions"
      }
    ],
    "publisher": {
      "category": "vendor",
      "name": "ABB PSIRT",
      "namespace": "https://www.abb.com/global/en/company/about/cybersecurity/alerts-and-notifications"
    },
    "references": [
      {
        "category": "self",
        "summary": "ABB CYBERSECURITY ADVISORY - PDF Version ",
        "url": "https://search.abb.com/library/Download.aspx?DocumentID=3ADR011524\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
      },
      {
        "category": "self",
        "summary": "ABB CYBERSECURITY ADVISORY - CSAF Version ",
        "url": "https://psirt.abb.com/csaf/2026/3adr011524.json"
      },
      {
        "summary": "2025-05 CODESYS Visualization user management bypass in WebVisu ",
        "url": "https://api-www.codesys.com/fileadmin/user_upload/CODESYS_Group/Ecosystem/Up-to-Date/Security/Security-Advisories/Advisory2025-05_VIS-5003_.pdf"
      },
      {
        "summary": "2025-07 CODESYS Control V3 - Exposed PKI folder ",
        "url": "https://api-www.codesys.com/fileadmin/user_upload/CODESYS_Group/Ecosystem/Up-to-Date/Security/Security-Advisories/Advisory2025-07_CDS-93244.pdf"
      },
      {
        "summary": "2025-08 CODESYS Control V3 - NULL Pointer Dereference ",
        "url": "https://api-www.codesys.com/fileadmin/user_upload/CODESYS_Group/Ecosystem/Up-to-Date/Security/Security-Advisories/Advisory2025-08_CDS-94690.pdf"
      }
    ],
    "title": "AC500 V3 Multiple vulnerabilities",
    "tracking": {
      "current_release_date": "2026-02-24T00:30:00.000Z",
      "generator": {
        "date": "2026-02-24T11:42:21.476Z",
        "engine": {
          "name": "Secvisogram",
          "version": "2.5.43"
        }
      },
      "id": "3ADR011524",
      "initial_release_date": "2026-02-24T00:30:00.000Z",
      "revision_history": [
        {
          "date": "2026-02-24T00:30:00.000Z",
          "legacy_version": "A",
          "number": "1",
          "summary": "Initial version."
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c3.9.0",
                "product": {
                  "name": "ABB AC500 V3 \u003c3.9.0",
                  "product_id": "AV1"
                }
              },
              {
                "category": "product_version",
                "name": "3.9.0",
                "product": {
                  "name": "ABB AC500 V3 3.9.0",
                  "product_id": "FX1"
                }
              }
            ],
            "category": "product_name",
            "name": "AC500 V3"
          }
        ],
        "category": "vendor",
        "name": "ABB"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2025-2595",
      "cwe": {
        "id": "CWE-425",
        "name": "Direct Request (\u0027Forced Browsing\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "The visualization allows users to create browser-based visualizations for monitoring and controlling industrial processes. Access to these visualizations can be restricted using the built-in user management.\n\nHowever, an unauthenticated remote attacker can bypass the user management and read visualization files by means of forced browsing. The exposed files, accessible via a web browser, contain only static visualization data such as text lists, icons or images, but no live data from the controlled system.",
          "title": "CVE description"
        }
      ],
      "product_status": {
        "fixed": [
          "FX1"
        ],
        "known_affected": [
          "AV1"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "NVD - CVE-2025-2595",
          "url": "https://nvd.nist.gov/vuln/detail/CVE-2025-2595"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "The problem is corrected in the following product versions:\n- AC500 V3 firmware version 3.9.0\n\nABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.9.0. Automation Builder 2.9.0 is available for download from the related download site.\n\nhttps://www.abb.com/global/en/areas/motion/digital-tools/automation-builder/software-download",
          "product_ids": [
            "AV1"
          ]
        },
        {
          "category": "mitigation",
          "details": "Refer to section \u201cGeneral security recommendations\u201d for further advise on how to keep your system secure.",
          "product_ids": [
            "AV1"
          ]
        },
        {
          "category": "workaround",
          "details": "No workarounds are available",
          "product_ids": [
            "AV1"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "LOW",
            "environmentalScore": 4.9,
            "environmentalSeverity": "MEDIUM",
            "exploitCodeMaturity": "FUNCTIONAL",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "remediationLevel": "OFFICIAL_FIX",
            "reportConfidence": "CONFIRMED",
            "scope": "UNCHANGED",
            "temporalScore": 4.9,
            "temporalSeverity": "MEDIUM",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N/E:F/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "AV1"
          ]
        }
      ],
      "title": "CVE-2025-2595"
    },
    {
      "cve": "CVE-2025-41659",
      "cwe": {
        "id": "CWE-732",
        "name": "Incorrect Permission Assignment for Critical Resource"
      },
      "notes": [
        {
          "category": "description",
          "text": "A vulnerability in the runtime system allows low-privileged remote attackers to access the PKI folder via CODESYS protocol, enabling them to read and write certificates and keys. This exposes sensitive cryptographic data and allows unauthorized certificates to be trusted. However, all services remain available, only certificate based encryption and signing features are concerned. The issue affects systems using the optional CmpOpenSSL component for cryptographic operations.",
          "title": "CVE description"
        }
      ],
      "product_status": {
        "fixed": [
          "FX1"
        ],
        "known_affected": [
          "AV1"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "NVD - CVE-2025-41659",
          "url": "https://nvd.nist.gov/vuln/detail/CVE-2025-41659"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "The problem is corrected in the following product versions:\n- AC500 V3 firmware version 3.9.0\n\nABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.9.0. Automation Builder 2.9.0 is available for download from the related download site.\n\nhttps://www.abb.com/global/en/areas/motion/digital-tools/automation-builder/software-download",
          "product_ids": [
            "AV1"
          ]
        },
        {
          "category": "mitigation",
          "details": "Refer to section \u201cGeneral security recommendations\u201d for further advise on how to keep your system secure.",
          "product_ids": [
            "AV1"
          ]
        },
        {
          "category": "workaround",
          "details": "No workarounds are available",
          "product_ids": [
            "AV1"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "LOW",
            "baseScore": 8.3,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 7.7,
            "environmentalSeverity": "HIGH",
            "exploitCodeMaturity": "FUNCTIONAL",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "remediationLevel": "OFFICIAL_FIX",
            "reportConfidence": "CONFIRMED",
            "scope": "UNCHANGED",
            "temporalScore": 7.7,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L/E:F/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "AV1"
          ]
        }
      ],
      "title": "CVE-2025-41659"
    },
    {
      "cve": "CVE-2025-41691",
      "cwe": {
        "id": "CWE-476",
        "name": "NULL Pointer Dereference"
      },
      "notes": [
        {
          "category": "description",
          "text": "A vulnerability in the runtime system\u0027s CmpDevice component allows unauthenticated attackers to cause a denial-of-service (DoS) via specially crafted communication requests.\n\nThe issue is triggered by a NULL pointer dereference and also affects systems when outdated clients attempt to log in.",
          "title": "CVE description"
        }
      ],
      "product_status": {
        "fixed": [
          "FX1"
        ],
        "known_affected": [
          "AV1"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "NVD - CVE-2025-41691",
          "url": "https://nvd.nist.gov/vuln/detail/CVE-2025-41691"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "The problem is corrected in the following product versions:\n- AC500 V3 firmware version 3.9.0\n\nABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.9.0. Automation Builder 2.9.0 is available for download from the related download site.\n\nhttps://www.abb.com/global/en/areas/motion/digital-tools/automation-builder/software-download",
          "product_ids": [
            "AV1"
          ]
        },
        {
          "category": "mitigation",
          "details": "Refer to section \u201cGeneral security recommendations\u201d for further advise on how to keep your system secure.",
          "product_ids": [
            "AV1"
          ]
        },
        {
          "category": "workaround",
          "details": "No workarounds are available",
          "product_ids": [
            "AV1"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7,
            "environmentalSeverity": "HIGH",
            "exploitCodeMaturity": "FUNCTIONAL",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "remediationLevel": "OFFICIAL_FIX",
            "reportConfidence": "CONFIRMED",
            "scope": "UNCHANGED",
            "temporalScore": 7,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:F/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "AV1"
          ]
        }
      ],
      "title": "CVE-2025-41691"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…