CVE-2025-9495 (GCVE-0-2025-9495)

Vulnerability from cvelistv5 – Published: 2025-09-23 01:16 – Updated: 2025-09-23 13:33
VLAI?
Title
Viessmann Vitogate 300 Authentication Bypass
Summary
The Vitogate 300 web interface fails to enforce proper server-side authentication and relies on frontend-based authentication controls. This allows an attacker to simply modify HTML elements in the browser’s developer tools to bypass login restrictions. By removing specific UI elements, an attacker can reveal the hidden administration menu, giving them full control over the device.
CWE
  • CWE-602 - Client-Side Enforcement of Server-Side Security
Assigner
Impacted products
Vendor Product Version
Viessmann Vitogate 300 Affected: 1 , < 3.0.0.0 (date)
Create a notification for this product.
Credits
Souvik Kandar of MicroSec (microsec.io)
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-9495",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-09-23T13:33:41.544746Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-09-23T13:33:47.319Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "Vitogate 300",
          "vendor": "Viessmann",
          "versions": [
            {
              "lessThan": "3.0.0.0",
              "status": "affected",
              "version": "1",
              "versionType": "date"
            }
          ]
        }
      ],
      "credits": [
        {
          "lang": "en",
          "type": "reporter",
          "value": "Souvik Kandar of MicroSec (microsec.io)"
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "The Vitogate 300 web interface fails to enforce proper server-side authentication and relies on frontend-based authentication controls. This allows an attacker to simply modify HTML elements in the browser\u2019s developer tools to bypass login restrictions. By removing specific UI elements, an attacker can reveal the hidden administration menu, giving them full control over the device.\u003cbr\u003e"
            }
          ],
          "value": "The Vitogate 300 web interface fails to enforce proper server-side authentication and relies on frontend-based authentication controls. This allows an attacker to simply modify HTML elements in the browser\u2019s developer tools to bypass login restrictions. By removing specific UI elements, an attacker can reveal the hidden administration menu, giving them full control over the device."
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "NONE",
            "attackVector": "ADJACENT",
            "baseScore": 8.7,
            "baseSeverity": "HIGH",
            "privilegesRequired": "NONE",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "HIGH",
            "vulnIntegrityImpact": "HIGH",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-602",
              "description": "CWE-602 Client-Side Enforcement of Server-Side Security",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-09-23T01:16:53.619Z",
        "orgId": "e24e6442-3ae1-4538-a7b8-7ac95586db8f",
        "shortName": "Carrier"
      },
      "references": [
        {
          "url": "https://https://www.corporate.carrier.com/product-security/advisories-resources/"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cp\u003e\u003c/p\u003e\u003cp\u003eThese\nvulnerabilities have been fixed with Vitogate 300 software version 3.1.0.1. \u003c/p\u003e\n\n\u003cp\u003eCustomers\nare strongly encouraged to upgrade by downloading software version 3.1.0.1 or newer at the\n\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://connectivity.viessmann-climatesolutions.com/gb/mp-fp/vitogate/vitogate-300-bn-mb.html\"\u003eVitogate\n300 website.\u003c/a\u003e\u003c/p\u003e\u003cp\u003e\u003c/p\u003e"
            }
          ],
          "value": "These\nvulnerabilities have been fixed with Vitogate 300 software version 3.1.0.1. \n\n\n\nCustomers\nare strongly encouraged to upgrade by downloading software version 3.1.0.1 or newer at the\nVitogate\n300 website."
        }
      ],
      "source": {
        "discovery": "EXTERNAL"
      },
      "title": "Viessmann Vitogate 300 Authentication Bypass",
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "e24e6442-3ae1-4538-a7b8-7ac95586db8f",
    "assignerShortName": "Carrier",
    "cveId": "CVE-2025-9495",
    "datePublished": "2025-09-23T01:16:53.619Z",
    "dateReserved": "2025-08-26T17:40:58.043Z",
    "dateUpdated": "2025-09-23T13:33:47.319Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2025-9494 (GCVE-0-2025-9494)

Vulnerability from cvelistv5 – Published: 2025-09-23 01:12 – Updated: 2025-09-23 13:34
VLAI?
Title
Viessmann Vitogate 300 OS Command Injection
Summary
An OS command injection vulnerability has been discovered in the Vitogate 300, which can be exploited by malicious users to compromise affected installations. Specifically, the `/cgi-bin/vitogate.cgi` endpoint is affected, when the `form` JSON parameter is set to `form-0-2`. The vulnerability stems from the fact that that function at offset 0x21c24 does not properly sanitize supplied input before interpolating it into a format string which gets passed to `popen()`. Consequently, an authenticated attacker is able to inject arbitrary OS commands and thus gain code execution on affected devices.
CWE
  • CWE-78 - Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
Assigner
Impacted products
Vendor Product Version
Viessmann Vitogate 300 Affected: 1 , < 3.1.0.0 (SKU)
Create a notification for this product.
Credits
adhkr of LuwakLab working with Trend Micro Zero Day Initiative
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-9494",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-09-23T13:33:59.911370Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-09-23T13:34:06.974Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "Vitogate 300",
          "vendor": "Viessmann",
          "versions": [
            {
              "lessThan": "3.1.0.0",
              "status": "affected",
              "version": "1",
              "versionType": "SKU"
            }
          ]
        }
      ],
      "credits": [
        {
          "lang": "en",
          "type": "reporter",
          "value": "adhkr of LuwakLab working with Trend Micro Zero Day Initiative"
        }
      ],
      "datePublic": "2025-09-22T16:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "An OS command injection vulnerability has been discovered in the Vitogate 300, which can be exploited by malicious users to compromise affected installations. Specifically, the `/cgi-bin/vitogate.cgi` endpoint is affected, when the `form` JSON parameter is set to `form-0-2`. The vulnerability stems from the fact that that function at offset 0x21c24 does not properly sanitize supplied input before interpolating it into a format string which gets passed to `popen()`. Consequently, an authenticated attacker is able to inject arbitrary OS commands and thus gain code execution on affected devices.\u003cbr\u003e"
            }
          ],
          "value": "An OS command injection vulnerability has been discovered in the Vitogate 300, which can be exploited by malicious users to compromise affected installations. Specifically, the `/cgi-bin/vitogate.cgi` endpoint is affected, when the `form` JSON parameter is set to `form-0-2`. The vulnerability stems from the fact that that function at offset 0x21c24 does not properly sanitize supplied input before interpolating it into a format string which gets passed to `popen()`. Consequently, an authenticated attacker is able to inject arbitrary OS commands and thus gain code execution on affected devices."
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "NONE",
            "attackVector": "ADJACENT",
            "baseScore": 8.5,
            "baseSeverity": "HIGH",
            "privilegesRequired": "HIGH",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "HIGH",
            "vulnIntegrityImpact": "HIGH",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-78",
              "description": "CWE-78 Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-09-23T01:12:17.459Z",
        "orgId": "e24e6442-3ae1-4538-a7b8-7ac95586db8f",
        "shortName": "Carrier"
      },
      "references": [
        {
          "url": "https://www.corporate.carrier.com/product-security/advisories-resources/"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cp\u003eThese\nvulnerabilities have been fixed with Vitogate 300 software version 3.1.0.1. \u003c/p\u003e\n\n\u003cp\u003eCustomers\nare strongly encouraged to upgrade by downloading software version 3.1.0.1 at the\u0026nbsp;\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://connectivity.viessmann-climatesolutions.com/gb/mp-fp/vitogate/vitogate-300-bn-mb.html\"\u003eVitogate\n300\u0026nbsp;\u003c/a\u003ewebsite.\u003cb\u003e\u003c/b\u003e\u003c/p\u003e"
            }
          ],
          "value": "These\nvulnerabilities have been fixed with Vitogate 300 software version 3.1.0.1. \n\n\n\nCustomers\nare strongly encouraged to upgrade by downloading software version 3.1.0.1 at the\u00a0Vitogate\n300\u00a0website."
        }
      ],
      "source": {
        "discovery": "EXTERNAL"
      },
      "title": "Viessmann Vitogate 300 OS Command Injection",
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "e24e6442-3ae1-4538-a7b8-7ac95586db8f",
    "assignerShortName": "Carrier",
    "cveId": "CVE-2025-9494",
    "datePublished": "2025-09-23T01:12:17.459Z",
    "dateReserved": "2025-08-26T17:40:54.110Z",
    "dateUpdated": "2025-09-23T13:34:06.974Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}