    2 vulnerabilities found for compact_guardlogix_5480 by rockwellautomation

    CVE-2024-5659 (GCVE-0-2024-5659)

    Vulnerability from nvd – Published: 2024-06-14 16:42 – Updated: 2024-08-01 21:18
    VLAI
    Title
    Rockwell Automation Multicast Request Causes major nonrecoverable fault on Select Controllers
    Summary
    Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: partial
    CISA Coordinator · CISA-ADP (v2.0.3)
    Decision recorded 2024-06-15 19:57 UTC
    CWE
    • CWE-670 - Always-Incorrect Control Flow Implementation
    Impacted products
    Vendor Product Version
    Rockwell Automation ControlLogix® 5580 Affected: 34.011
    Create a notification for this product.
    Rockwell Automation GuardLogix 5580 Affected: 34.011
    Create a notification for this product.
    Rockwell Automation 1756-EN4 Affected: 4.001
    Create a notification for this product.
    Rockwell Automation CompactLogix 5380 Affected: 34.011
    Create a notification for this product.
    Rockwell Automation Compact GuardLogix 5380 Affected: 34.011
    Create a notification for this product.
    Rockwell Automation CompactLogix 5480 Affected: 34.011
    Create a notification for this product.
    rockwellautomation controllogix_5580 Affected: 34.011
        cpe:2.3:h:rockwellautomation:controllogix_5580:-:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation guardlogix_5580 Affected: 34.011
        cpe:2.3:h:rockwellautomation:guardlogix_5580:-:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation 1756_en4 Affected: 4.001
        cpe:2.3:a:rockwellautomation:1756_en4:0:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation compact_logix_5480 Affected: 34.011
        cpe:2.3:a:rockwellautomation:compact_logix_5480:34.011:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation compact_guardlogix_5480 Affected: 34.011
        cpe:2.3:a:rockwellautomation:compact_guardlogix_5480:34.011:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation compactlogix Affected: 5480
        cpe:2.3:h:rockwellautomation:compactlogix:*:*:*:*:*:*:*:*
    Create a notification for this product.
    Date Public
    2024-06-13 13:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:h:rockwellautomation:controllogix_5580:-:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "controllogix_5580",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "34.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:h:rockwellautomation:guardlogix_5580:-:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "guardlogix_5580",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "34.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:1756_en4:0:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "1756_en4",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "4.001"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:compact_logix_5480:34.011:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "compact_logix_5480",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "34.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:compact_guardlogix_5480:34.011:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "compact_guardlogix_5480",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "34.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:h:rockwellautomation:compactlogix:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "compactlogix",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "5480"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-5659",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-06-15T19:57:53.882617Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-06-15T20:23:20.243Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          },
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-01T21:18:06.865Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_transferred"
                ],
                "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1673.html"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "ControlLogix\u00ae 5580",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "GuardLogix 5580",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "1756-EN4",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "4.001"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "CompactLogix 5380",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "Compact GuardLogix 5380",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "CompactLogix 5480",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            }
          ],
          "datePublic": "2024-06-13T13:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\n\n\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eRockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending \u003c/span\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eabnormal packets to the \u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003emDNS port.\u0026nbsp;\u003c/a\u003e\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eIf exploited, the availability of the device would be compromised.\u003c/span\u003e\n\n"
                }
              ],
              "value": "Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port.\u00a0If exploited, the availability of the device would be compromised."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-624",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-624 Hardware Fault Injection"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "ADJACENT",
                "baseScore": 8.3,
                "baseSeverity": "HIGH",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "HIGH",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "NONE",
                "vulnIntegrityImpact": "NONE",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-670",
                  "description": "CWE-670 Always-Incorrect Control Flow Implementation",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-06-14T16:42:20.699Z",
            "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
            "shortName": "Rockwell"
          },
          "references": [
            {
              "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1673.html"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\n\n\u003ctable\u003e\u003ctbody\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eAffected Product\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eFirst Known in firmware revision\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eCorrected in firmware revision\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eControlLogix\u00ae 5580\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eGuardLogix 5580\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later \u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e1756-EN4\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV4.001\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV6.001 and later\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eCompactLogix 5380\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later \u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eCompact GuardLogix \u003c/a\u003e\u003cb\u003e\u0026nbsp;\u003c/b\u003e5380\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later \u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eCompactLogix 5480\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003c/tbody\u003e\u003c/table\u003e\u003cbr\u003e\n\n\u003cp\u003e\u003cb\u003eMitigations and Workarounds\u003c/b\u003e\u003c/p\u003e\u003cp\u003eUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply the risk mitigations, where possible.\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Users who do not use \u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eAutomatic Policy Deployment (APD)\u003c/a\u003e\u0026nbsp;should block \u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003emDNS port, 5353\u003c/a\u003e\u0026nbsp;to help prevent communication.\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Enable CIP \u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eSecurity. \u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://literature.rockwellautomation.com/idc/groups/literature/documents/at/secure-at001_-en-p.pdf\"\u003eCIP Security with Rockwell Automation Products Application Technique\u003c/a\u003e\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\"\u003eSecurity Best Practices\u003c/a\u003e\u003c/p\u003e\n\n\u003cbr\u003e"
                }
              ],
              "value": "Affected Product\n\nFirst Known in firmware revision\n\nCorrected in firmware revision\n\nControlLogix\u00ae 5580\n\nV34.011\n\nV34.014, V35.013, V36.011 and later\n\nGuardLogix 5580\n\nV34.011\n\nV34.014, V35.013, V36.011 and later \n\n1756-EN4\n\nV4.001\n\nV6.001 and later\n\nCompactLogix 5380\n\nV34.011\n\nV34.014, V35.013, V36.011 and later \n\nCompact GuardLogix \u00a05380\n\nV34.011\n\nV34.014, V35.013, V36.011 and later \n\nCompactLogix 5480\n\nV34.011\n\nV34.014, V35.013, V36.011 and later\n\n\n\n\nMitigations and Workarounds\n\nUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply the risk mitigations, where possible.\n\n\u00b7 \u00a0 \u00a0 \u00a0 Users who do not use  CIP Security with Rockwell Automation Products Application Technique https://literature.rockwellautomation.com/idc/groups/literature/documents/at/secure-at001_-en-p.pdf \n\n\u00b7 \u00a0 \u00a0 \u00a0  Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight"
            }
          ],
          "source": {
            "discovery": "EXTERNAL"
          },
          "title": "Rockwell Automation Multicast Request Causes major nonrecoverable fault on Select Controllers",
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "assignerShortName": "Rockwell",
        "cveId": "CVE-2024-5659",
        "datePublished": "2024-06-14T16:42:20.699Z",
        "dateReserved": "2024-06-05T16:47:18.275Z",
        "dateUpdated": "2024-08-01T21:18:06.865Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2024-5659 (GCVE-0-2024-5659)

    Vulnerability from cvelistv5 – Published: 2024-06-14 16:42 – Updated: 2024-08-01 21:18
    VLAI
    Title
    Rockwell Automation Multicast Request Causes major nonrecoverable fault on Select Controllers
    Summary
    Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: partial
    CISA Coordinator · CISA-ADP (v2.0.3)
    Decision recorded 2024-06-15 19:57 UTC
    CWE
    • CWE-670 - Always-Incorrect Control Flow Implementation
    Impacted products
    Vendor Product Version
    Rockwell Automation ControlLogix® 5580 Affected: 34.011
    Create a notification for this product.
    Rockwell Automation GuardLogix 5580 Affected: 34.011
    Create a notification for this product.
    Rockwell Automation 1756-EN4 Affected: 4.001
    Create a notification for this product.
    Rockwell Automation CompactLogix 5380 Affected: 34.011
    Create a notification for this product.
    Rockwell Automation Compact GuardLogix 5380 Affected: 34.011
    Create a notification for this product.
    Rockwell Automation CompactLogix 5480 Affected: 34.011
    Create a notification for this product.
    rockwellautomation controllogix_5580 Affected: 34.011
        cpe:2.3:h:rockwellautomation:controllogix_5580:-:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation guardlogix_5580 Affected: 34.011
        cpe:2.3:h:rockwellautomation:guardlogix_5580:-:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation 1756_en4 Affected: 4.001
        cpe:2.3:a:rockwellautomation:1756_en4:0:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation compact_logix_5480 Affected: 34.011
        cpe:2.3:a:rockwellautomation:compact_logix_5480:34.011:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation compact_guardlogix_5480 Affected: 34.011
        cpe:2.3:a:rockwellautomation:compact_guardlogix_5480:34.011:*:*:*:*:*:*:*
    Create a notification for this product.
    rockwellautomation compactlogix Affected: 5480
        cpe:2.3:h:rockwellautomation:compactlogix:*:*:*:*:*:*:*:*
    Create a notification for this product.
    Date Public
    2024-06-13 13:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:h:rockwellautomation:controllogix_5580:-:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "controllogix_5580",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "34.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:h:rockwellautomation:guardlogix_5580:-:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "guardlogix_5580",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "34.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:1756_en4:0:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "1756_en4",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "4.001"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:compact_logix_5480:34.011:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "compact_logix_5480",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "34.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:a:rockwellautomation:compact_guardlogix_5480:34.011:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "compact_guardlogix_5480",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "34.011"
                  }
                ]
              },
              {
                "cpes": [
                  "cpe:2.3:h:rockwellautomation:compactlogix:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unknown",
                "product": "compactlogix",
                "vendor": "rockwellautomation",
                "versions": [
                  {
                    "status": "affected",
                    "version": "5480"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-5659",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-06-15T19:57:53.882617Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-06-15T20:23:20.243Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          },
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-01T21:18:06.865Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_transferred"
                ],
                "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1673.html"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "ControlLogix\u00ae 5580",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "GuardLogix 5580",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "1756-EN4",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "4.001"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "CompactLogix 5380",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "Compact GuardLogix 5380",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "CompactLogix 5480",
              "vendor": "Rockwell Automation",
              "versions": [
                {
                  "status": "affected",
                  "version": "34.011"
                }
              ]
            }
          ],
          "datePublic": "2024-06-13T13:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\n\n\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eRockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending \u003c/span\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eabnormal packets to the \u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003emDNS port.\u0026nbsp;\u003c/a\u003e\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eIf exploited, the availability of the device would be compromised.\u003c/span\u003e\n\n"
                }
              ],
              "value": "Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port.\u00a0If exploited, the availability of the device would be compromised."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-624",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-624 Hardware Fault Injection"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "ADJACENT",
                "baseScore": 8.3,
                "baseSeverity": "HIGH",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "HIGH",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "NONE",
                "vulnIntegrityImpact": "NONE",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-670",
                  "description": "CWE-670 Always-Incorrect Control Flow Implementation",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-06-14T16:42:20.699Z",
            "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
            "shortName": "Rockwell"
          },
          "references": [
            {
              "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1673.html"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "\n\n\u003ctable\u003e\u003ctbody\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eAffected Product\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eFirst Known in firmware revision\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eCorrected in firmware revision\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eControlLogix\u00ae 5580\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eGuardLogix 5580\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later \u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e1756-EN4\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV4.001\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV6.001 and later\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eCompactLogix 5380\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later \u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eCompact GuardLogix \u003c/a\u003e\u003cb\u003e\u0026nbsp;\u003c/b\u003e5380\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later \u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eCompactLogix 5480\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eV34.014, V35.013, V36.011 and later\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003c/tbody\u003e\u003c/table\u003e\u003cbr\u003e\n\n\u003cp\u003e\u003cb\u003eMitigations and Workarounds\u003c/b\u003e\u003c/p\u003e\u003cp\u003eUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply the risk mitigations, where possible.\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Users who do not use \u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eAutomatic Policy Deployment (APD)\u003c/a\u003e\u0026nbsp;should block \u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003emDNS port, 5353\u003c/a\u003e\u0026nbsp;to help prevent communication.\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; Enable CIP \u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003e\u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eSecurity. \u003c/a\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://literature.rockwellautomation.com/idc/groups/literature/documents/at/secure-at001_-en-p.pdf\"\u003eCIP Security with Rockwell Automation Products Application Technique\u003c/a\u003e\u003c/p\u003e\u003cp\u003e\u00b7 \u0026nbsp; \u0026nbsp; \u0026nbsp; \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\"\u003eSecurity Best Practices\u003c/a\u003e\u003c/p\u003e\n\n\u003cbr\u003e"
                }
              ],
              "value": "Affected Product\n\nFirst Known in firmware revision\n\nCorrected in firmware revision\n\nControlLogix\u00ae 5580\n\nV34.011\n\nV34.014, V35.013, V36.011 and later\n\nGuardLogix 5580\n\nV34.011\n\nV34.014, V35.013, V36.011 and later \n\n1756-EN4\n\nV4.001\n\nV6.001 and later\n\nCompactLogix 5380\n\nV34.011\n\nV34.014, V35.013, V36.011 and later \n\nCompact GuardLogix \u00a05380\n\nV34.011\n\nV34.014, V35.013, V36.011 and later \n\nCompactLogix 5480\n\nV34.011\n\nV34.014, V35.013, V36.011 and later\n\n\n\n\nMitigations and Workarounds\n\nUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply the risk mitigations, where possible.\n\n\u00b7 \u00a0 \u00a0 \u00a0 Users who do not use  CIP Security with Rockwell Automation Products Application Technique https://literature.rockwellautomation.com/idc/groups/literature/documents/at/secure-at001_-en-p.pdf \n\n\u00b7 \u00a0 \u00a0 \u00a0  Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight"
            }
          ],
          "source": {
            "discovery": "EXTERNAL"
          },
          "title": "Rockwell Automation Multicast Request Causes major nonrecoverable fault on Select Controllers",
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "assignerShortName": "Rockwell",
        "cveId": "CVE-2024-5659",
        "datePublished": "2024-06-14T16:42:20.699Z",
        "dateReserved": "2024-06-05T16:47:18.275Z",
        "dateUpdated": "2024-08-01T21:18:06.865Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }