Search
Find a vulnerability
Search criteria
1 vulnerability
CVE-2026-120387 (GCVE-0-2026-120387)
Vulnerability from cvelistv5 – Published: 2026-11-17 04:47 – Updated: 2026-11-17 18:42
VLAI
EPSS
VEX
Title
CIRCUTOR PowerStudio SCADA WAVE JWT Signature Validation Authentication Bypass
Summary
An improper JWT signature verification vulnerability in CIRCUTOR PowerStudio SCADA WAVE desktop version allows an unauthenticated remote attacker to bypass authentication by submitting an unsigned JWT with the algorithm set to “none”. The shared JWT validation component accepts the token without verifying a cryptographic signature, allowing the attacker to impersonate another user and access protected functionality with that user's privileges.
Severity
SSVC
Exploitation: poc
Automatable: yes
Technical Impact: total
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2026-11-17 18:40 UTC
CWE
- CWE-347 - Improper verification of cryptographic signature
Assigner
References
3 references
| URL | Tags |
|---|---|
| https://0day-rubbish.com/blog/circutor-powerstudi… | third-party-advisory |
| https://github.com/Exploit-Garbage/0day-Rubbish?u… | exploit |
| https://circutor.com/soporte/ciberseguridad/ | patch |
Impacted products
1 product
| Vendor | Product | Version | |
|---|---|---|---|
| Circutor | PowerStudio SCADA Wave |
Affected:
24.8.0 , < 24.11.17.0
(custom)
Unaffected: 24.11.17.0 (custom) |
Date Public
2026-11-17 08:08
{
"containers": {
"adp": [
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2026-120387",
"options": [
{
"Exploitation": "poc"
},
{
"Automatable": "yes"
},
{
"Technical Impact": "total"
}
],
"role": "CISA Coordinator",
"timestamp": "2026-11-17T18:40:54.316363Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2026-11-17T18:42:08.345Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"platforms": [
"Windows",
"64 bit"
],
"product": "PowerStudio SCADA Wave",
"vendor": "Circutor",
"versions": [
{
"lessThan": "24.11.17.0",
"status": "affected",
"version": "24.8.0",
"versionType": "custom"
},
{
"status": "unaffected",
"version": "24.11.17.0",
"versionType": "custom"
}
]
}
],
"datePublic": "2026-11-17T08:08:00.000Z",
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cdiv\u003eAn improper JWT signature verification vulnerability in CIRCUTOR PowerStudio SCADA WAVE desktop version allows an unauthenticated remote attacker to bypass authentication by submitting an unsigned JWT with the algorithm set to \u201cnone\u201d. The shared JWT validation component accepts the token without verifying a cryptographic signature, allowing the attacker to impersonate another user and access protected functionality with that user\u0027s privileges.\n\n\u003c/div\u003e"
}
],
"value": "An improper JWT signature verification vulnerability in CIRCUTOR PowerStudio SCADA WAVE desktop version allows an unauthenticated remote attacker to bypass authentication by submitting an unsigned JWT with the algorithm set to \u201cnone\u201d. The shared JWT validation component accepts the token without verifying a cryptographic signature, allowing the attacker to impersonate another user and access protected functionality with that user\u0027s privileges."
}
],
"impacts": [
{
"capecId": "CAPEC-39",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-39 Manipulating Opaque Client-based Data Tokens"
}
]
}
],
"metrics": [
{
"cvssV4_0": {
"Automatable": "NOT_DEFINED",
"Recovery": "NOT_DEFINED",
"Safety": "NOT_DEFINED",
"attackComplexity": "LOW",
"attackRequirements": "NONE",
"attackVector": "NETWORK",
"baseScore": 10,
"baseSeverity": "CRITICAL",
"exploitMaturity": "NOT_DEFINED",
"privilegesRequired": "NONE",
"providerUrgency": "NOT_DEFINED",
"subAvailabilityImpact": "HIGH",
"subConfidentialityImpact": "HIGH",
"subIntegrityImpact": "HIGH",
"userInteraction": "NONE",
"valueDensity": "NOT_DEFINED",
"vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H",
"version": "4.0",
"vulnAvailabilityImpact": "HIGH",
"vulnConfidentialityImpact": "HIGH",
"vulnIntegrityImpact": "HIGH",
"vulnerabilityResponseEffort": "NOT_DEFINED"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "The attacker has network connectivity to the affected PowerStudio services. No valid credentials or user interaction are required."
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-347",
"description": "CWE-347 Improper verification of cryptographic signature",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2026-11-17T04:47:30.045Z",
"orgId": "59aea6fb-2240-4284-b9fd-48e3851c2128",
"shortName": "Circutor"
},
"references": [
{
"tags": [
"third-party-advisory"
],
"url": "https://0day-rubbish.com/blog/circutor-powerstudio-jwt-alg-none-identity-forgery?utm_source=chatgpt.com"
},
{
"tags": [
"exploit"
],
"url": "https://github.com/Exploit-Garbage/0day-Rubbish?utm_source=chatgpt.com"
},
{
"tags": [
"patch"
],
"url": "https://circutor.com/soporte/ciberseguridad/"
}
],
"solutions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cdiv\u003eUpdate CIRCUTOR PowerStudio SCADA WAVE to version v24.11.17.0 or later.\n\n\u003c/div\u003e"
}
],
"value": "Update CIRCUTOR PowerStudio SCADA WAVE to version v24.11.17.0 or later."
}
],
"source": {
"discovery": "UNKNOWN"
},
"title": "CIRCUTOR PowerStudio SCADA WAVE JWT Signature Validation Authentication Bypass",
"x_generator": {
"engine": "Vulnogram 1.0.5"
}
}
},
"cveMetadata": {
"assignerOrgId": "59aea6fb-2240-4284-b9fd-48e3851c2128",
"assignerShortName": "Circutor",
"cveId": "CVE-2026-120387",
"datePublished": "2026-11-17T04:47:30.045Z",
"dateReserved": "2026-11-02T07:57:11.004Z",
"dateUpdated": "2026-11-17T18:42:08.345Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.2"
}