Search
Find a vulnerability
Search criteria
8 vulnerabilities found for edge_controller_firmware by wago
CVE-2023-3379 (GCVE-0-2023-3379)
Vulnerability from nvd – Published: 2023-11-20 07:23 – Updated: 2024-10-02 05:34
VLAI
Title
WAGO: Improper Privilege Management in web-based management
Summary
Wago web-based management of multiple products has a vulnerability which allows an local authenticated attacker to change the passwords of other non-admin users and thus to escalate non-root privileges.
Severity
5.3 (Medium)
CWE
- CWE-863 - Incorrect Authorization
Assigner
References
1 reference
Impacted products
8 products
| Vendor | Product | Version | |
|---|---|---|---|
| WAGO | Compact Controller 100 (751-9301) |
Affected:
0 , ≤ FW25
(custom)
|
|
| WAGO | PFC100 (750-810x/xxx-xxx) |
Affected:
0 , ≤ FW22 Patch 1
(custom)
|
|
| WAGO | PFC200 (750-820x/xxx-xxx) |
Affected:
0 , ≤ FW25
(custom)
|
|
| WAGO | PFC200 (750-821x/xxx-xxx) |
Affected:
0 , ≤ FW22 Patch 1
(custom)
|
|
| WAGO | Touch Panel 600 Advanced Line (762-5xxx) |
Affected:
0 , ≤ FW25
(custom)
|
|
| WAGO | Touch Panel 600 Marine Line (762-6xxx) |
Affected:
0 , ≤ FW25
(custom)
|
|
| WAGO | Touch Panel 600 Standard Line (762-4xxx) |
Affected:
0 , ≤ FW25
(custom)
|
|
| Wago | Edge Controller (752-8303/8000-002) |
Affected:
0 , ≤ FW25
(custom)
|
Credits
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-02T06:55:03.365Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://cert.vde.com/en/advisories/VDE-2023-015/"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Compact Controller 100 (751-9301)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC100 (750-810x/xxx-xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22 Patch 1",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC200 (750-820x/xxx-xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC200 (750-821x/xxx-xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22 Patch 1",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Advanced Line (762-5xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Marine Line (762-6xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Standard Line (762-4xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Edge Controller (752-8303/8000-002)",
"vendor": "Wago",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "reporter",
"user": "00000000-0000-4000-9000-000000000000",
"value": "Panagiotis Bellonias from Secura"
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Wago web-based management of multiple products has a vulnerability which allows an local authenticated attacker to change the passwords of other non-admin users and thus to escalate non-root privileges."
}
],
"value": "Wago web-based management of multiple products has a vulnerability which allows an local authenticated attacker to change the passwords of other non-admin users and thus to escalate non-root privileges."
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "LOW",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"integrityImpact": "LOW",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-863",
"description": "CWE-863 Incorrect Authorization",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2024-10-02T05:34:25.860Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"url": "https://cert.vde.com/en/advisories/VDE-2023-015/"
}
],
"source": {
"advisory": "VDE-2023-015",
"defect": [
"CERT@VDE#64549"
],
"discovery": "EXTERNAL"
},
"title": "WAGO: Improper Privilege Management in web-based management",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2023-3379",
"datePublished": "2023-11-20T07:23:41.887Z",
"dateReserved": "2023-06-23T09:01:09.552Z",
"dateUpdated": "2024-10-02T05:34:25.860Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2023-4089 (GCVE-0-2023-4089)
Vulnerability from nvd – Published: 2023-10-17 06:00 – Updated: 2025-02-27 20:40
VLAI
Title
WAGO: Multiple products vulnerable to local file inclusion
Summary
On affected Wago products an remote attacker with administrative privileges can access files to which he has already access to through an undocumented local file inclusion. This access is logged in a different log file than expected.
Severity
SSVC
Exploitation: none
Automatable: no
Technical Impact: partial
CISA Coordinator (v2.0.3)
CWE
- CWE-610 - Externally Controlled Reference to a Resource in Another Sphere
Assigner
References
1 reference
Impacted products
7 products
| Vendor | Product | Version | |
|---|---|---|---|
| WAGO | Compact Controller CC100 |
Affected:
FW19 , ≤ FW26
(semver)
|
|
| WAGO | Edge Controller |
Affected:
FW18 , ≤ FW26
(semver)
|
|
| WAGO | PFC100 |
Affected:
FW16 , ≤ FW26
(semver)
|
|
| WAGO | PFC200 |
Affected:
FW16 , ≤ FW26
(semver)
|
|
| WAGO | Touch Panel 600 Advanced Line |
Affected:
FW16 , ≤ FW26
(semver)
|
|
| WAGO | Touch Panel 600 Marine Line |
Affected:
FW16 , ≤ FW26
(semver)
|
|
| WAGO | Touch Panel 600 Standard Line |
Affected:
FW16 , ≤ FW26
(semver)
|
Credits
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-02T07:17:11.728Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://cert.vde.com/en/advisories/VDE-2023-046/"
}
],
"title": "CVE Program Container"
},
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2023-4089",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-02-26T21:49:11.155380Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-02-27T20:40:32.064Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Compact Controller CC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW19",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Edge Controller",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW18",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC200",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Advanced Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Marine Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Standard Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "reporter",
"user": "00000000-0000-4000-9000-000000000000",
"value": "Floris Hendriks and Jeroen Wijenbergh from Radboud University"
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "On affected Wago products an remote attacker with administrative privileges can access files to which he has already access to through an undocumented local file inclusion. This access is logged in a different log file than expected."
}
],
"value": "On affected Wago products an remote attacker with administrative privileges can access files to which he has already access to through an undocumented local file inclusion. This access is logged in a different log file than expected."
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 2.7,
"baseSeverity": "LOW",
"confidentialityImpact": "LOW",
"integrityImpact": "NONE",
"privilegesRequired": "HIGH",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-610",
"description": "CWE-610 Externally Controlled Reference to a Resource in Another Sphere",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2023-10-17T06:00:28.908Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"url": "https://cert.vde.com/en/advisories/VDE-2023-046/"
}
],
"source": {
"advisory": "VDE-2023-046",
"defect": [
"CERT@VDE#64532"
],
"discovery": "EXTERNAL"
},
"title": "WAGO: Multiple products vulnerable to local file inclusion",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2023-4089",
"datePublished": "2023-10-17T06:00:28.908Z",
"dateReserved": "2023-08-02T07:20:35.600Z",
"dateUpdated": "2025-02-27T20:40:32.064Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2023-1698 (GCVE-0-2023-1698)
Vulnerability from nvd – Published: 2023-05-15 08:51 – Updated: 2025-01-23 19:13Title
WAGO: WBM Command Injection in multiple products
Summary
In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise.
Severity
9.8 (Critical)
SSVC
Exploitation: none
Automatable: yes
Technical Impact: total
CISA Coordinator (v2.0.3)
CWE
- CWE-78 - Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
Assigner
References
1 reference
Impacted products
7 products
| Vendor | Product | Version | |
|---|---|---|---|
| WAGO | Compact Controller CC100 |
Affected:
FW20 , ≤ FW22
(semver)
Affected: FW23 |
|
| WAGO | Edge Controller |
Affected:
FW22
|
|
| WAGO | PFC100 |
Affected:
FW20 , ≤ FW22
(semver)
Affected: FW23 |
|
| WAGO | PFC200 |
Affected:
FW20 , ≤ FW22
(semver)
Affected: FW23 |
|
| WAGO | Touch Panel 600 Advanced Line |
Affected:
FW22
|
|
| WAGO | Touch Panel 600 Marine Line |
Affected:
FW22
|
|
| WAGO | Touch Panel 600 Standard Line |
Affected:
FW22
|
Credits
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-02T05:57:24.816Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://cert.vde.com/en/advisories/VDE-2023-007/"
}
],
"title": "CVE Program Container"
},
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2023-1698",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "yes"
},
{
"Technical Impact": "total"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-01-23T19:12:48.907770Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-01-23T19:13:09.654Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Compact Controller CC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW20",
"versionType": "semver"
},
{
"status": "affected",
"version": "FW23"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Edge Controller",
"vendor": "WAGO",
"versions": [
{
"status": "affected",
"version": "FW22"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW20",
"versionType": "semver"
},
{
"status": "affected",
"version": "FW23"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC200",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW20",
"versionType": "semver"
},
{
"status": "affected",
"version": "FW23"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Advanced Line",
"vendor": "WAGO",
"versions": [
{
"status": "affected",
"version": "FW22"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Marine Line",
"vendor": "WAGO",
"versions": [
{
"status": "affected",
"version": "FW22"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Standard Line",
"vendor": "WAGO",
"versions": [
{
"status": "affected",
"version": "FW22"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "reporter",
"user": "00000000-0000-4000-9000-000000000000",
"value": "Quentin Kaiser from ONEKEY"
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise."
}
],
"value": "In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise."
}
],
"impacts": [
{
"capecId": "CAPEC-88",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-88 OS Command Injection"
}
]
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-78",
"description": "CWE-78 Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2023-05-15T08:51:27.453Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"url": "https://cert.vde.com/en/advisories/VDE-2023-007/"
}
],
"source": {
"advisory": "VDE-2023-007",
"defect": [
"CERT@VDE#64422"
],
"discovery": "EXTERNAL"
},
"title": "WAGO: WBM Command Injection in multiple products",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2023-1698",
"datePublished": "2023-05-15T08:51:27.453Z",
"dateReserved": "2023-03-29T13:00:05.618Z",
"dateUpdated": "2025-01-23T19:13:09.654Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2022-3738 (GCVE-0-2022-3738)
Vulnerability from nvd – Published: 2023-01-19 11:27 – Updated: 2025-04-02 14:55
VLAI
Title
WAGO: Missing authentication for config export functionality in multiple products
Summary
The vulnerability allows a remote unauthenticated attacker to download a backup file, if one exists. That backup file might contain sensitive information like credentials and cryptographic material. A valid user has to create a backup after the last reboot for this attack to be successfull.
Severity
5.9 (Medium)
SSVC
Exploitation: none
Automatable: no
Technical Impact: partial
CISA Coordinator (v2.0.3)
CWE
- CWE-306 - Missing Authentication for Critical Function
Assigner
References
1 reference
Impacted products
7 products
| Vendor | Product | Version | |
|---|---|---|---|
| WAGO | Series WAGO PFC100 |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | Series WAGO PFC200 |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | Series WAGO Touch Panel 600 Advanced Line |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | Series WAGO Touch Panel 600 Marine Line |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | Series WAGO Touch Panel 600 Standard Line |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | WAGO Compact Controller CC100 |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | WAGO Edge Controller |
Affected:
FW16 , ≤ FW22
(semver)
|
Date Public
2023-01-12 08:00
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-03T01:20:57.784Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://cert.vde.com/en/advisories/VDE-2022-054/"
}
],
"title": "CVE Program Container"
},
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2022-3738",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-04-02T14:55:30.723734Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-04-02T14:55:51.603Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Series WAGO PFC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Series WAGO PFC200",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Series WAGO Touch Panel 600 Advanced Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Series WAGO Touch Panel 600 Marine Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Series WAGO Touch Panel 600 Standard Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "WAGO Compact Controller CC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "WAGO Edge Controller",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
}
],
"datePublic": "2023-01-12T08:00:00.000Z",
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eThe vulnerability allows a remote unauthenticated attacker to download a backup file, if one exists. That backup file might contain sensitive information like credentials and cryptographic material. A valid user has to create a backup after the last reboot for this attack to be successfull.\u003c/span\u003e\u003cbr\u003e"
}
],
"value": "The vulnerability allows a remote unauthenticated attacker to download a backup file, if one exists. That backup file might contain sensitive information like credentials and cryptographic material. A valid user has to create a backup after the last reboot for this attack to be successfull.\n"
}
],
"impacts": [
{
"capecId": "CAPEC-1",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-1 Accessing Functionality Not Properly Constrained by ACLs"
}
]
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-306",
"description": "CWE-306 Missing Authentication for Critical Function",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2023-11-07T09:43:18.629Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"url": "https://cert.vde.com/en/advisories/VDE-2022-054/"
}
],
"source": {
"advisory": "VDE-2022-054",
"defect": [
"CERT@VDE#64273"
],
"discovery": "EXTERNAL"
},
"title": "WAGO: Missing authentication for config export functionality in multiple products",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2022-3738",
"datePublished": "2023-01-19T11:27:51.814Z",
"dateReserved": "2022-10-28T07:18:40.653Z",
"dateUpdated": "2025-04-02T14:55:51.603Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2023-3379 (GCVE-0-2023-3379)
Vulnerability from cvelistv5 – Published: 2023-11-20 07:23 – Updated: 2024-10-02 05:34
VLAI
Title
WAGO: Improper Privilege Management in web-based management
Summary
Wago web-based management of multiple products has a vulnerability which allows an local authenticated attacker to change the passwords of other non-admin users and thus to escalate non-root privileges.
Severity
5.3 (Medium)
CWE
- CWE-863 - Incorrect Authorization
Assigner
References
1 reference
Impacted products
8 products
| Vendor | Product | Version | |
|---|---|---|---|
| WAGO | Compact Controller 100 (751-9301) |
Affected:
0 , ≤ FW25
(custom)
|
|
| WAGO | PFC100 (750-810x/xxx-xxx) |
Affected:
0 , ≤ FW22 Patch 1
(custom)
|
|
| WAGO | PFC200 (750-820x/xxx-xxx) |
Affected:
0 , ≤ FW25
(custom)
|
|
| WAGO | PFC200 (750-821x/xxx-xxx) |
Affected:
0 , ≤ FW22 Patch 1
(custom)
|
|
| WAGO | Touch Panel 600 Advanced Line (762-5xxx) |
Affected:
0 , ≤ FW25
(custom)
|
|
| WAGO | Touch Panel 600 Marine Line (762-6xxx) |
Affected:
0 , ≤ FW25
(custom)
|
|
| WAGO | Touch Panel 600 Standard Line (762-4xxx) |
Affected:
0 , ≤ FW25
(custom)
|
|
| Wago | Edge Controller (752-8303/8000-002) |
Affected:
0 , ≤ FW25
(custom)
|
Credits
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-02T06:55:03.365Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://cert.vde.com/en/advisories/VDE-2023-015/"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Compact Controller 100 (751-9301)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC100 (750-810x/xxx-xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22 Patch 1",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC200 (750-820x/xxx-xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC200 (750-821x/xxx-xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22 Patch 1",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Advanced Line (762-5xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Marine Line (762-6xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Standard Line (762-4xxx)",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Edge Controller (752-8303/8000-002)",
"vendor": "Wago",
"versions": [
{
"lessThanOrEqual": "FW25",
"status": "affected",
"version": "0",
"versionType": "custom"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "reporter",
"user": "00000000-0000-4000-9000-000000000000",
"value": "Panagiotis Bellonias from Secura"
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Wago web-based management of multiple products has a vulnerability which allows an local authenticated attacker to change the passwords of other non-admin users and thus to escalate non-root privileges."
}
],
"value": "Wago web-based management of multiple products has a vulnerability which allows an local authenticated attacker to change the passwords of other non-admin users and thus to escalate non-root privileges."
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "LOW",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"integrityImpact": "LOW",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-863",
"description": "CWE-863 Incorrect Authorization",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2024-10-02T05:34:25.860Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"url": "https://cert.vde.com/en/advisories/VDE-2023-015/"
}
],
"source": {
"advisory": "VDE-2023-015",
"defect": [
"CERT@VDE#64549"
],
"discovery": "EXTERNAL"
},
"title": "WAGO: Improper Privilege Management in web-based management",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2023-3379",
"datePublished": "2023-11-20T07:23:41.887Z",
"dateReserved": "2023-06-23T09:01:09.552Z",
"dateUpdated": "2024-10-02T05:34:25.860Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2023-4089 (GCVE-0-2023-4089)
Vulnerability from cvelistv5 – Published: 2023-10-17 06:00 – Updated: 2025-02-27 20:40
VLAI
Title
WAGO: Multiple products vulnerable to local file inclusion
Summary
On affected Wago products an remote attacker with administrative privileges can access files to which he has already access to through an undocumented local file inclusion. This access is logged in a different log file than expected.
Severity
SSVC
Exploitation: none
Automatable: no
Technical Impact: partial
CISA Coordinator (v2.0.3)
CWE
- CWE-610 - Externally Controlled Reference to a Resource in Another Sphere
Assigner
References
1 reference
Impacted products
7 products
| Vendor | Product | Version | |
|---|---|---|---|
| WAGO | Compact Controller CC100 |
Affected:
FW19 , ≤ FW26
(semver)
|
|
| WAGO | Edge Controller |
Affected:
FW18 , ≤ FW26
(semver)
|
|
| WAGO | PFC100 |
Affected:
FW16 , ≤ FW26
(semver)
|
|
| WAGO | PFC200 |
Affected:
FW16 , ≤ FW26
(semver)
|
|
| WAGO | Touch Panel 600 Advanced Line |
Affected:
FW16 , ≤ FW26
(semver)
|
|
| WAGO | Touch Panel 600 Marine Line |
Affected:
FW16 , ≤ FW26
(semver)
|
|
| WAGO | Touch Panel 600 Standard Line |
Affected:
FW16 , ≤ FW26
(semver)
|
Credits
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-02T07:17:11.728Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://cert.vde.com/en/advisories/VDE-2023-046/"
}
],
"title": "CVE Program Container"
},
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2023-4089",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-02-26T21:49:11.155380Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-02-27T20:40:32.064Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Compact Controller CC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW19",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Edge Controller",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW18",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC200",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Advanced Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Marine Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Standard Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW26",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "reporter",
"user": "00000000-0000-4000-9000-000000000000",
"value": "Floris Hendriks and Jeroen Wijenbergh from Radboud University"
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "On affected Wago products an remote attacker with administrative privileges can access files to which he has already access to through an undocumented local file inclusion. This access is logged in a different log file than expected."
}
],
"value": "On affected Wago products an remote attacker with administrative privileges can access files to which he has already access to through an undocumented local file inclusion. This access is logged in a different log file than expected."
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 2.7,
"baseSeverity": "LOW",
"confidentialityImpact": "LOW",
"integrityImpact": "NONE",
"privilegesRequired": "HIGH",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:N/A:N",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-610",
"description": "CWE-610 Externally Controlled Reference to a Resource in Another Sphere",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2023-10-17T06:00:28.908Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"url": "https://cert.vde.com/en/advisories/VDE-2023-046/"
}
],
"source": {
"advisory": "VDE-2023-046",
"defect": [
"CERT@VDE#64532"
],
"discovery": "EXTERNAL"
},
"title": "WAGO: Multiple products vulnerable to local file inclusion",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2023-4089",
"datePublished": "2023-10-17T06:00:28.908Z",
"dateReserved": "2023-08-02T07:20:35.600Z",
"dateUpdated": "2025-02-27T20:40:32.064Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2023-1698 (GCVE-0-2023-1698)
Vulnerability from cvelistv5 – Published: 2023-05-15 08:51 – Updated: 2025-01-23 19:13Title
WAGO: WBM Command Injection in multiple products
Summary
In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise.
Severity
9.8 (Critical)
SSVC
Exploitation: none
Automatable: yes
Technical Impact: total
CISA Coordinator (v2.0.3)
CWE
- CWE-78 - Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
Assigner
References
1 reference
Impacted products
7 products
| Vendor | Product | Version | |
|---|---|---|---|
| WAGO | Compact Controller CC100 |
Affected:
FW20 , ≤ FW22
(semver)
Affected: FW23 |
|
| WAGO | Edge Controller |
Affected:
FW22
|
|
| WAGO | PFC100 |
Affected:
FW20 , ≤ FW22
(semver)
Affected: FW23 |
|
| WAGO | PFC200 |
Affected:
FW20 , ≤ FW22
(semver)
Affected: FW23 |
|
| WAGO | Touch Panel 600 Advanced Line |
Affected:
FW22
|
|
| WAGO | Touch Panel 600 Marine Line |
Affected:
FW22
|
|
| WAGO | Touch Panel 600 Standard Line |
Affected:
FW22
|
Credits
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-02T05:57:24.816Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://cert.vde.com/en/advisories/VDE-2023-007/"
}
],
"title": "CVE Program Container"
},
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2023-1698",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "yes"
},
{
"Technical Impact": "total"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-01-23T19:12:48.907770Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-01-23T19:13:09.654Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Compact Controller CC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW20",
"versionType": "semver"
},
{
"status": "affected",
"version": "FW23"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Edge Controller",
"vendor": "WAGO",
"versions": [
{
"status": "affected",
"version": "FW22"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW20",
"versionType": "semver"
},
{
"status": "affected",
"version": "FW23"
}
]
},
{
"defaultStatus": "unaffected",
"product": "PFC200",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW20",
"versionType": "semver"
},
{
"status": "affected",
"version": "FW23"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Advanced Line",
"vendor": "WAGO",
"versions": [
{
"status": "affected",
"version": "FW22"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Marine Line",
"vendor": "WAGO",
"versions": [
{
"status": "affected",
"version": "FW22"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Touch Panel 600 Standard Line",
"vendor": "WAGO",
"versions": [
{
"status": "affected",
"version": "FW22"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "reporter",
"user": "00000000-0000-4000-9000-000000000000",
"value": "Quentin Kaiser from ONEKEY"
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise."
}
],
"value": "In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise."
}
],
"impacts": [
{
"capecId": "CAPEC-88",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-88 OS Command Injection"
}
]
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-78",
"description": "CWE-78 Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2023-05-15T08:51:27.453Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"url": "https://cert.vde.com/en/advisories/VDE-2023-007/"
}
],
"source": {
"advisory": "VDE-2023-007",
"defect": [
"CERT@VDE#64422"
],
"discovery": "EXTERNAL"
},
"title": "WAGO: WBM Command Injection in multiple products",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2023-1698",
"datePublished": "2023-05-15T08:51:27.453Z",
"dateReserved": "2023-03-29T13:00:05.618Z",
"dateUpdated": "2025-01-23T19:13:09.654Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2022-3738 (GCVE-0-2022-3738)
Vulnerability from cvelistv5 – Published: 2023-01-19 11:27 – Updated: 2025-04-02 14:55
VLAI
Title
WAGO: Missing authentication for config export functionality in multiple products
Summary
The vulnerability allows a remote unauthenticated attacker to download a backup file, if one exists. That backup file might contain sensitive information like credentials and cryptographic material. A valid user has to create a backup after the last reboot for this attack to be successfull.
Severity
5.9 (Medium)
SSVC
Exploitation: none
Automatable: no
Technical Impact: partial
CISA Coordinator (v2.0.3)
CWE
- CWE-306 - Missing Authentication for Critical Function
Assigner
References
1 reference
Impacted products
7 products
| Vendor | Product | Version | |
|---|---|---|---|
| WAGO | Series WAGO PFC100 |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | Series WAGO PFC200 |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | Series WAGO Touch Panel 600 Advanced Line |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | Series WAGO Touch Panel 600 Marine Line |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | Series WAGO Touch Panel 600 Standard Line |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | WAGO Compact Controller CC100 |
Affected:
FW16 , ≤ FW22
(semver)
|
|
| WAGO | WAGO Edge Controller |
Affected:
FW16 , ≤ FW22
(semver)
|
Date Public
2023-01-12 08:00
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-03T01:20:57.784Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://cert.vde.com/en/advisories/VDE-2022-054/"
}
],
"title": "CVE Program Container"
},
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2022-3738",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-04-02T14:55:30.723734Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-04-02T14:55:51.603Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Series WAGO PFC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Series WAGO PFC200",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Series WAGO Touch Panel 600 Advanced Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Series WAGO Touch Panel 600 Marine Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Series WAGO Touch Panel 600 Standard Line",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "WAGO Compact Controller CC100",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
},
{
"defaultStatus": "unaffected",
"product": "WAGO Edge Controller",
"vendor": "WAGO",
"versions": [
{
"lessThanOrEqual": "FW22",
"status": "affected",
"version": "FW16",
"versionType": "semver"
}
]
}
],
"datePublic": "2023-01-12T08:00:00.000Z",
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eThe vulnerability allows a remote unauthenticated attacker to download a backup file, if one exists. That backup file might contain sensitive information like credentials and cryptographic material. A valid user has to create a backup after the last reboot for this attack to be successfull.\u003c/span\u003e\u003cbr\u003e"
}
],
"value": "The vulnerability allows a remote unauthenticated attacker to download a backup file, if one exists. That backup file might contain sensitive information like credentials and cryptographic material. A valid user has to create a backup after the last reboot for this attack to be successfull.\n"
}
],
"impacts": [
{
"capecId": "CAPEC-1",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-1 Accessing Functionality Not Properly Constrained by ACLs"
}
]
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-306",
"description": "CWE-306 Missing Authentication for Critical Function",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2023-11-07T09:43:18.629Z",
"orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"shortName": "CERTVDE"
},
"references": [
{
"url": "https://cert.vde.com/en/advisories/VDE-2022-054/"
}
],
"source": {
"advisory": "VDE-2022-054",
"defect": [
"CERT@VDE#64273"
],
"discovery": "EXTERNAL"
},
"title": "WAGO: Missing authentication for config export functionality in multiple products",
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
}
},
"cveMetadata": {
"assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
"assignerShortName": "CERTVDE",
"cveId": "CVE-2022-3738",
"datePublished": "2023-01-19T11:27:51.814Z",
"dateReserved": "2022-10-28T07:18:40.653Z",
"dateUpdated": "2025-04-02T14:55:51.603Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}