    <item>
      <title>fkie_cve-2026-17539</title>
      <link>https://db.gcve.eu/vuln/fkie_cve-2026-17539</link>
      <description>&lt;p&gt;RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.&lt;/p&gt;</description>
      <content:encoded>&lt;p&gt;RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.&lt;/p&gt;</content:encoded>
      <guid isPermaLink="false">https://db.gcve.eu/vuln/fkie_cve-2026-17539</guid>
    </item>
    <item>
      <title>GHSA-9w2f-4f52-qcj4</title>
      <link>https://db.gcve.eu/vuln/ghsa-9w2f-4f52-qcj4</link>
      <description>&lt;p&gt;RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.&lt;/p&gt;</description>
      <content:encoded>&lt;p&gt;RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.&lt;/p&gt;</content:encoded>
      <guid isPermaLink="false">https://db.gcve.eu/vuln/ghsa-9w2f-4f52-qcj4</guid>
    </item>
    <item>
      <title>ICSA-26-293-05 — Hitachi Energy RTU500 Product</title>
      <link>https://db.gcve.eu/vuln/icsa-26-293-05</link>
      <description>&lt;p&gt;Hitachi Energy is aware of vulnerabilities that affect RTU500 product versions listed in this document. These vulnerabilities if exploited can have impact on confidentiality, integrity and availability of the product. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation.&lt;/p&gt;</description>
      <content:encoded>&lt;p&gt;Hitachi Energy is aware of vulnerabilities that affect RTU500 product versions listed in this document. These vulnerabilities if exploited can have impact on confidentiality, integrity and availability of the product. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation.&lt;/p&gt;</content:encoded>